8
AMV OND1000-X-C1
Terminal
Wire color
Wire length /
gauge
Line (L)
Black (120 VAC), Brown (230 VAC)
AC
OUTPUT
Neutral (N)
White (120 VAC), Blue (230 VAC)
Line (L)
Black (120 VAC), Brown (230 VAC)
AC INPUT
Neutral (N)
White (120 VAC), Blue (230 VAC)
Chassis Ground or FG
Green / Yellow or Bare copper
Within 16 feet /
AWG#
14~16
26~32 feet /
AWG#
12~14
Note. Please double check and review all the connections to ensure that the
wires are connected to the correct terminals and that the connections are tight.
3-1-3. AC output socket:
110VAC
NEMA
230VAC
I.E.C 60320 C13
3-1-4
.
Chassis Ground: Must be connected to earth ground prior to
making any other connections to the equipment.
3-1-5
.
RS-232: Serial port monitoring and control through computer interface.
3-1-6
.
Remote control and Dry contact terminal:
RELAY
ENABLE -
GROUND
COM.
NO
NC
ENB
ENB
GN
D