AMV OND1000-X-C1
▌
Remote Control Terminal:
1). Before installing the inverter, ensure that the main switch “OFF”.
2). Before using the remote function, ensure that the main switch pressed
toward “REMOTE”.
3). Ensure that the remote contacts are off.
4). Use 20 ~ 24 #AWG wire to connect the remote control terminals.
5). Remote control ON/OFF inverter setup status:
ENB
GND
ON:INV. ON
OFF:INV. OFF
LOW:INV. OFF
HI:INV. ON
GND
ENB
TR
(TR ON)
(TR OFF)
OFF:INV. OFF
ON:INV. ON
ENB
BAT+
BAT-
GND
ON:INV. ON
OFF:INV. OFF
ENB
+
-
DC
POWER
NOTE: At one time, only one remote function should used to control the inverter.
The maximum voltage value is the same as input DC voltage.
▌
Dry Contact Terminals:
Dry contact terminals may be connected to a Form C relay for “FAULT”
indication. When “FAULT” occurs, the relay switches.
NOTE: Fault conditions include Input under/over voltage, Output Short Circuit,
Over Temperature, Over-load and, Fan Failure.
Specifications of the Relay
Contact Rating
Maximum
Voltage
Load
N.O.
N.C.
Number of
operations
Operating/Storage
Temperature
240 VAC Resistive
16 A
100,000
240 VAC Resistive
8 A
30 VDC
Resistive
16 A
30 VDC
Resistive
8 A
-30
℃
~70
℃