Suggested Piping Diagrams
PRESSURE
SWITCH
RELIEF VALVE
DRAIN
TO TITAN
PRESSURE
GAUGE
SUBMERSIBLE PUMP
AIR CAP
Installation
System Connection
Models:
TC-20 through TC-32: 1" NPT
TC-44 through TC-119: 1¼" NPT
For PVC System Connection:
1.
Plumb tank with standard NPT threaded connection or plumb
tank with glue joint fitting by first cutting hex and NPT fitting off.
2.
If cut was made, glue a Sch 80 PVC coupling (not included).
Pre Installation
DO NOT LOCATE IN AN AREA WHERE LEAKAGE
OF THE TANK OR CONNECTIONS COULD CAUSE
PROPERTY DAMAGE TO THE AREA ADJACENT TO THE APPLIANCE
OR TO LOWER FLOORS.
Installation Surface:
The surface on which the Titan is installed should be capable of
supporting its operating weight (including the weight of water).
The Titan should be installed as close as possible to the pressure
switch. This will reduce the adverse effects of added friction loss
and differences in elevation between Titan and/or water supply
main and switch.
Installation Location:
Adjacent to pump:
This is the location chosen most often. The
Titan tank can be used whether pumps are above or below the
surface. In either case, it protects the pump by reducing surge,
dampening pressure spikes, offering a point of pressure control,
and providing minimum run time. This location also permits all
equipment to be placed in an area that’s both serviceable and
secure.
At the end of long pipe runs:
The Titan tank can be positioned
at the end of a long run of pipe so it can provide rapid
system response and adequate protection. When this location is
chosen, the pressure switch should either be relocated with the
Titan tank or the setting should be adjusted to compensate for
any line pressure drop.
Tank Prep/Install:
1.
Remove protective air valve cap.
2.
Check pre-charge pressure from valve core.
3.
Release or add air as necessary to set the pre-charge
pressure 2 psig below the pressure switch pump cut-in
setting. (Example, 38 psig precharge for a 40/60 pressure.)
4.
Replace protective air valve cap.
5.
Plumb tank per the chosen system diagram.
6.
Wire in pressure switch.
PRESSURE SWITCH
RELIEF VALVE
DRAIN
AIR CAP
HEX
CONNECTION TO TANK
NPT PLUMBING CONNECTION