18
Press the T3 (OPT) key.
3. Press the T1 ( ‡ ) or T2 ( ‚ ) keys to set the desired
parameters
for the analogue output
signal.
The following parameters can be selected:
Voltage U
„V…
Current I
„A…
Frequency f
„Hz…
Active power P,
received
„W…
Reactive power Q,
inductive
„var…
Power factor,
inductive /value/
„cos †…
Accumulated values
„sum…
T3
‰
Accumulated active power
„W sum…
Accumulated reactive power „var sum…
Power factor entire network „cos † sum…
Additional option:
Deactivation
„AUS…
see below
ŠDeactivation of the analogue output•
After the selection has been made press the T3 (OPT) key to proceed to the next step.
4. Press the T1 ( ‡ ) or T2 ( ‚ ) keys to select the
phase
(channel).
The following options are available:
for voltage
L1-N
L2-N
L3-N
L1-L2
L2-L3
L3-L1
for current, frequency, power, power factor
L1
L2
L3
for accumulated active power, accumulated reactive
no selection (phase-independent)
power, power factor entire network
After the selection has been made press the T3 (OPT) key to proceed to the next step.
5. Setting the
start value
(
additional display: “
min
”
). A preset value relevant to the selection of
parameters and phases is displayed with the first digit flashing.
With the T1 ( ‡ ) key the value can be increased starting at …0ˆ through to …9ˆ. To access a lower
value press the T1 ( ‡ ) key past …9ˆ to start again with …0ˆ.
Press the T2 ( ‚ ) key to access the next digit. The digit starts flashing. To change the value press
T1 ( ‡ ) key.
After setting the last digit the decimal point starts flashing and can now be moved by pressing the
T1 ( ‡ ) key. Also the measuring range …kˆ can be selected where required.
By pressing the T2 ( ‚ ) key the complete process of setting start value can be repeated.
Press T3 (OPT) to proceed.
6. Setting the
final value
(additional display: „
max
“)
. A preset value relevant to the selection of
parameters and phases is displayed with the first digit flashing.