Dual-Feed 350A 6-Circuit
Breaker/TFD Distribution
Panel with 5 GMTs
If possible, avoid placing high-current circuit breakers side-by-side. Not doing so causes concentrated heat collection
and subsequent power loss. Also, if not all circuit breaker positions are occupied, allow non-populated positions
between breakers.
Install the GMT fuses so that the failure indicator flags are at the top.
36. Do one of the following:
•
Switch breakers to ON
•
Install fuses
Then test power and polarity at input of each equipment load or distribution unit fed by a circuit breaker or fuse.
37. If possible, temporarily replace one of the operable GMT fuses with a blown fuse to check that the applicable
ALARM
LED lights up red. Also, check the
ALARM
terminal on the rear of the panel:
Cover plate
Breaker cover plate
Mounting
screw
Circuit
breaker
Fig. 9: Installing Circuit Breaker
Fig. 10: Installing GMT Fuses