9
Conductor
Insulation
Part 1
Keep tight to cable jacket
Recommended crimp length is 8±0.5mm
Notes: The recommended crimp sizes are only for reference. The customer should adjust them according to cable
specification and crimp tool and test results including temperature rise and metallographic analysis and pullout force.
Reference gap is 1mm MAX
12±1mm
3.
Wire cutting and stripping (applies to 16mm
2
& 25mm
2
cables).
Strip conductor: 12±1mm
4.
Install the cable conductor into the connector body lug
5.
Crimp wire well as shown below
F
Cable Size
Cable Range
Recommended crimp
dist across Flats F
Cable Pullout Force
Applicable Current
25 mm
2
10.20±0.20 mm
7.5±0.1mm
1900N Min.
120A Max.
16 mm
2
8.10±0.20 mm
TBD
1500N Min.
100A Max.