background image

Interference

1) Background magnetic field signals or interference may be present in any 

location and may not be anything to do with the loop system. Monitor this 

with a loop receiver (such as an ILR3). If the interference is still present with 

the loop system switched off, then you need to locate and eliminate the 

source of interference before switching the loop system back on.
2) Magnetic fields can be induced into any low impedance electrical path or 

loop. Multiple ground earth systems may experience the pick up of the loop 

signal, and cause difficulties with other systems that are not designed to 

reject such interference. Check entire sound system for evidence of loop 

signal, and trace source of pick-up.
3) Under certain circumstances, the loop signal may appear as jagged lines 

or hum bars on a CCTV picture. This could be due to running CCTV (low 

impedance unbalanced 2-wire circuit) cables in close proximity to the loop 

cable. Separate the cables to reduce the effect.
4) Remote (and apparently unconnected) PA systems can sometimes pick 

up loop signals. This is usually because the loop cable becomes damaged 

(see point 1 of Instability) or induces signals into the remote system through 

long unbalanced cables. Always run long audio signal cables as 3-wire 

balanced circuits and keep away from loop cables.
5) See also point 1 of Instability.

Failed AC power fuse in rear of unit

Unplug the loop and AC power supply from amplifier, and replace the failed 

fuse with the spare fuse in AC power input fuse tray.

 

Reconnect the AC 

power supply and switch on. If the fuse fails again, return the unit to 

Ampetronic for evaluation - it may well be covered under warranty, which 

will be invalidated by removing the cover.

 

If the fuse does not fail a 'loop 

error' may be indicated, but shows that the unit is working correctly.         

Re-connect the loop and switch the power off then on again to reset loop 

error.

 

If the fuse fails when the loop is re-connected to the unit, then the 

loop could be shorted to electrical mains (and building) earth. This can 

happen even if no audio signal is present, as the short to earth is likely to 

cause an instability / oscillation / feedback condition to develop. A loop 

cable short to earth most commonly occurs where flat copper tape is 

installed on a metal-clad raised access flooring system. If the insulation on 

the flat copper tape is abraded (for example by a piece of metal swarf 

trapped below the copper tape), the conductor could short to the earthed 

tiles. 

 

When installing on raised access floors, it is advisable to insulate 

beneath the flat copper tape installation using Ampetronic PWT or similar 

tape.  The loop short to earth may only be completed when a person steps 

on the tape in the affected location, which can create significant difficulties 

when diagnosing the cause of fuse failure. Contact Ampetronic for further 

advice if a unit is suffering recurring but untraceable failure of the rear panel 

fuse.

AC Power Supply:

Output: 

3-pole IEC320 connector.

NL4 speakon (1+ & 2+ connected 

85W nominal for either version.

internally as are 1- & 2- to allow ‘star-

45-65Hz

quad’ method of cable connection).

Current: >9A peak (6.4A ) into 1

W

RMS

230V Version

Voltage: >20V peak (14.1V )

RMS

Nominal: 230V AC

Loop Resistance: 0.3

W

 

 to 2.0

W

Fuse: T 630mA L

resistive or 2.2

W

 max impedance

Range: 207-253V AC

reactive at 1.6kHz.

Quiescent: 100mA

THD+N <0.2% @ 1kHz @ 9.0A

pk

Typical: 400mA (O/P 3A  pink noise)

RMS

Frequency Response: 

120V Version

Measured at low level with no metal

Nominal: 120V AC

loss correction.

Fuse: T 1.25A L

80Hz to 6.5kHz -3.0dB 

Range: 108-132V AC

100Hz to 5.5kHz ± 1.5dB 

Quiescent: 200mA

Typical: 800mA (O/P 3A  pink noise)

RMS

Metal Loss Correction:

0dB (flat) to 3dB/Octave boost. 

 Microphone Input:

Gain at 1kHz remains constant.

XLR socket.

Input Impedance: 200-600

W

 

Loop Monitor:

Sensitivity: -70dBu (245uV ) for full

RMS

3.5mm 3-pole (stereo) jack socket

output.

0.675Vpk at 9.0Apk output

Overload: >-5dBu (436mV ) 

RMS

±15V 150mA DC Output:

Line Input:

3 pin power Mini DIN socket.

6.4mm 3-pole Jack socket.

Regulated DC output for powering

Input Impedance: 1M

W

Ampetronic pre-amps & accessories.

Sensitivity: -30dBu (24mV ) for full

RMS

Environmental:

output.

Ventilation: See 

Installation

 section

Overload: >+20dBu (7.75V )

RMS

for details.

0

0

Ambient temperature: -10 C to +40 C

Slave I/O:

Relative Humidity: < 90%

6.4mm 3-pole Jack socket.

Input Impedance: 100k

W

Source impedance: 220

W

Output level: 0dBu (0.775V )

RMS

Compression (AGC): 

>36dB dynamic range

Controlled by adjusting input level.

Standards:

Loop Design:

Meets relevant CE, EMC and

Depends on application, see

safety standards.

Designing induction loops handbook

or consult Ampetronic.

Please contact Ampetronic if you need 

further assistance. 

IP rating: IP20

Physical:

Weight: 3.75kg

Width: 430mm

Depth: 220mm

Height: 44mm

19” rack width, 1U high.

TECHNICAL SPECIFICATIONS

Summary of Contents for ILD500

Page 1: ...is damaged liquid has been spilled or objects have fallen into the apparatus the apparatus has been exposed to any rain or moisture does not operate normally or has been dropped 9 WARNING To reduce risk of fire or electric shock do not expose this apparatus to rain or moisture The apparatus shall not be exposed to dripping or splashing and no objects filled with liquids such as vases shall be plac...

Page 2: ...9 Repeat step 6 for the other input if used 10 Listen to the magnetic field produced inside the loop area using a receiving device e g Ampetronic ILR3 or examine the performance in more detail with a field strength meter 11 Adjust METAL LOSS CORRECTION to achieve a flat frequency response QUICK START INTRODUCTION The ILD500 Induction Loop Driver has been designed as a high quality amplifier for us...

Page 3: ... the loop cable METAL LOSS CORRECTION Screwdriver adjustable control which compensates for the frequency dependent effects of metal SLAVE I O Post compressor signal for use with ancillaries 15V 150mA DC OUTPUT 3 pin power Mini DIN LINE INPUT 6 4mm Jack socket for balanced line level signals MIC INPUT XLR socket for use with balanced microphones GAIN BOOST Increases gain of MIC input by 15dB PHANTO...

Page 4: ...l cold LINE INPUT MIC INPUT SLAVE I O LOOP CONNECTOR Signal TIP SOURCE TO ILD500 SLEEVE RING LINE INPUT Connection of 3 pole plug Use Twin screened cable Must be 3m or less Unbalanced Balanced TIP RECORDING DEVICE TO ILD500 SLAVE I O SLEEVE RING Connection of 3 pole Plug to use Slave I O socket for recording output Signal 8 00mm 20 00mm use either NL4 connections 1or 2 or both as required 1 2 LOOP...

Page 5: ...nel exhaust of the unit Both of these vents must be unobstructed for satisfactory cooling If the unit is installed in an enclosed environment sufficient air flow into the enclosure must be provided through vents fans or other means such that the units exhaust air is not recycled to the inlet causing it to OVERHEAT Slave I O Output Metal Loss Correction Compression LEDs Current LEDs Overheat LED Mi...

Page 6: ...llary units such as microphone pre amps or signal processing units 1 Turn all controls fully anti clockwise 2 Connect the loop cable into the Loop connector supplied Where using a perimeter loop floor ceiling level the feed cable should be tightly twisted and less than 20m in length Total resistance of loop and feed must be between 0 3W and 2 0W at DC The Designing Induction Loops handbook contain...

Page 7: ...nce with respect to a Magnetic field strength This will vary across the coverage area due to layout metal loss and LOOP CURRENT b Frequency response Metal losses tend to increase with frequency and may require the adjustment of the METAL LOSS CORRECTION As a result of this analysis adjust the LOOP CURRENT and set the METAL LOSS CORRECTION on the rear of the unit to achieve best sound quality This ...

Page 8: ...eck that the LOOP ERROR or OVERHEAT LEDs are not illuminated Ensure the POWER LED is illuminated and not flashing Remove any connection to the SLAVE I O socket Check that the loop cable is connected terminated correctly and inserted into the LOOP OUTPUT socket Check the loop cable is not open circuit short circuit or connected to earth see Instability or high frequency noise section of Troubleshoo...

Page 9: ... currents at audio frequencies If the loop cable is run close to sensitive signal cables it may be possible to induce a signal back into the input of the amplifier causing feedback Cable runs and loop wires should be kept well apart from each other To avoid interference a proximity of 300mm should only be run for a few meters Always used balanced 3 wire circuits where possible 3 Instability can ca...

Page 10: ...e in rear of unit Unplug the loop and AC power supply from amplifier and replace the failed fuse with the spare fuse in AC power input fuse tray Reconnect the AC power supply and switch on If the fuse fails again return the unit to Ampetronic for evaluation it may well be covered under warranty which will be invalidated by removing the cover If the fuse does not fail a loop error may be indicated ...

Page 11: ...200 600W Loop Monitor Sensitivity 70dBu 245uV for full RMS 3 5mm 3 pole stereo jack socket output 0 675Vpk at 9 0Apk output Overload 5dBu 436mV RMS 15V 150mA DC Output Line Input 3 pin power Mini DIN socket 6 4mm 3 pole Jack socket Regulated DC output for powering Input Impedance 1MW Ampetronic pre amps accessories Sensitivity 30dBu 24mV for full RMS Environmental output Ventilation See Installati...

Page 12: ...e year parts and labour warranty from date of shipment from Ampetronic To qualify for the five year warranty the product must be registered at www ampetronic com products warranty without which the warranty will be valid for two years only The five year warranty is dated from the time the equipment leaves Ampetronic and NOT when it is installed Manufacturer Ampetronic Ltd Northern Road Newark Nott...

Reviews: