BC9740 | 24V DC AUTOMATIC BATTERY CHARGER

Page 3

+

+

DC OUT

BACK UP

12V

+

-

12V

+

-

O

I

9400

PS

amperes

BC9740 

amperes

AUTOMATIC BATTERY CHARGER

MENU

ENTER

PREV

NEXT

CHARGING

POWER

FAULT

BC 9740

Connecting the unit Diagram

Note 1 :

It is important to use correct cable size for back up supplies, ie. cable from battery bank to charger and from charger to load. 

Incorrect size may cause serious consequences whenever takeover is activated and the load is high. This may cause fire.

PLEASE REFER TO SECTION : USING CORRECT CABLE SIZE FOR BACK UP BATTERIES

Note 2 :

It is recommended that external that draw high current uses external contactor or high power relay for back up changeover, 

equipment. ie. power amplifiers.

AC contractor is recommended as it shall provide faster change over to battery DC supply as compared to DC contractor.

BACK UP 

DC OUT 

TERMINALS

Amperes PS9400

24V power supply

Cable Type: Refer Note 2

TO EQUIPMENTS

DC SUPPLY

CONTACTOR (24V DC COIL)

TO HEAVY LOAD 

(POWER AMPS)

OPTIONAL HIGH AMP. 

RATING CONTRACTOR

Refer Note 2

bypass for 

heavy load

24V DC 

BATT. BANK

BATT IN 

TERMINALS

Refer Note 1

Summary of Contents for BC9740

Page 1: ...aving various protective circuitries to prolong the battery life span and the charger itself and the new communication feature which enables remote monitoring by Amperes PMX II Software through LAN We invite you to experience this innovative product which we developed by taking challenges into reality You shall be assured of quality and performance in years to come INSTRUCTION MANUAL BC9740 24V DC...

Page 2: ...ND LOAD CONNECTORS 24V battery bank shall be connected to the BATT IN connectors whereas the back up load to BACK UP DC OUT Ensure correct polarity for battery connections The back up or EM load shall not exceed 25 Amps and use external relays or contactors if necessary DO NOT CONNECT LOAD DIRECTLY TO BATTERY TERMINALS AS THIS MAY CAUSE DAMAGE TO YOUR EQUIPMENT 6 BATTERY INPUTS REVERSED POLARITY L...

Page 3: ...gh This may cause fire PLEASE REFER TO SECTION USING CORRECT CABLE SIZE FOR BACK UP BATTERIES Note 2 It is recommended that external that draw high current uses external contactor or high power relay for back up changeover equipment ie power amplifiers AC contractor is recommended as it shall provide faster change over to battery DC supply as compared to DC contractor BACK UP DC OUT TERMINALS Ampe...

Page 4: ...e between the setting On or Off Once selected press Enter and the display shall return to the main menu 2 CASCADE Enter Menu 2 1 UNIT SET Use Next Prev button to toggle between the unit set from 1 32 1 32 Once selected press Enter and the display shall return to the main menu 2 Cascade It is used to set the cascade 3 Info Device information 3 INFO Next 3 2 BATTERY BAT 00 2V 00 1A Next 3 1 MAIN POW...

Page 5: ...e monitored remotely via PMX II LAN version iPX5500 Comm Box Communication Interface Box is required to convert the RS485 data to IP and thereafter captured by the software Maximum 16 nos of nodes including other equipment in the rack can be connected Each unit should be addressed individually to avoid data crash Please refer to instruction manual of relevant IP product for its setup procedures BC...

Page 6: ...t point of charging process The current shall reduce to a constant value upon full charge STEP 1 STEP 2 STEP 3 STEP 4 Sum up total current drawn and the operating period required e g Total current under 24V DC is 30A and 2 hours standby time C1 30 x 2 60Ah Determine residual voltage to remain to avoid total discharge ie 30 C2 60 0 7 Refer to battery data sheet for recommended value 85 7Ah Optimum ...

Page 7: ...put EM load 4 15 kg 482 W X 44 H X 180 D mm It is important to use correct cable size for back up batteries Errors may cause cable overheating whenever take over is activated eventually leads to cable insulation being melted and short circuit In worst case this may lead to fire Why so Batteries would provide whatever current required by load which may run into hundreds of amp for a very short peri...

Page 8: ...performed by unauthorized personnel or service centres This warranty covers only repairs and replacement of defective parts cost and risks of transportation as well as removal and installation of the product from the main system are for the account of the purchaser This warranty shall not extend to the replacement of the unit This warranty does not cover damages caused by misuse neglect accident o...

Reviews: