Specifications 

 

Items 

Specifications 

Testable Detector 

Heat: Rate of Rise Heat Detector, Fixed Temperature Heat Detector 

Smoke: Ionization Smoke Detector, Photoelectric Smoke Detector 

Option: Analog Type Detector, Unexploded Type (Heat) 

Head Size 

150mm (Detector Insertion) 

Inspection Pole Length 

Minimum Approx. 127cm / Maximum approx. 250cm 

If longer pole is needed 6m and 10m poles are available upon request. 

Weight 

2.3kg 

Material 

Aluminum 

Input 

AC100 ~ 240V 50~60Hz 2A 

Output 

DC12V 2A 

Operating Temperature Range 

Approx. 0°C to 40°C 

Keeping Temperature Range 

Approx. -10°C to 40°C 

Operating Humidity Range 

Approx. 0% to 85%, No Frost 

Smoke Generator Ability 

Approx. 50 testable based on 1.00ml smoke detector 

Battery 

14.8V Li-ION 

Charging Time 

Full charge consumes approx. 5 hours 

Charger 

Input: AC 100-240V, 50-60Hz, 0.5A / Output: DC 12V2A 

Running Time 

Up to 5 hours  

Duration may vary due to operating conditions; battery has limited 

recharge cycles and may eventually need to be replaced. 

Tester Ability (One Time of 

Charge) 

Approximately 200 Heat Detectors and 300 Smoke Detectors 

 

Summary of Contents for FIREVIEW

Page 1: ...FIREVIEW PORTABLE FIRE DETECTOR TESTER World s first all in one unified tester for heat and smoke detector MAN 3141 ...

Page 2: ...er Description 4112 1012 Ampac FireView Portable Fire Detector Tester 4112 1007 Smoke Oil 100ML 4112 1008 FireView 6M Extension Pole 4112 1009 FireView 10M Extension Pole 4112 1010 FireView Smoke Detector Removal Tool 4112 1011 FireView Heat Detector Removal Tool 4112 1013 FireView Replacement Head Unit ...

Page 3: ...3kg Material Aluminum Input AC100 240V 50 60Hz 2A Output DC12V 2A Operating Temperature Range Approx 0 C to 40 C Keeping Temperature Range Approx 10 C to 40 C Operating Humidity Range Approx 0 to 85 No Frost Smoke Generator Ability Approx 50 testable based on 1 00ml smoke detector Battery 14 8V Li ION Charging Time Full charge consumes approx 5 hours Charger Input AC 100 240V 50 60Hz 0 5A Output D...

Page 4: ...ging jack with the dedicated charger DC 12V2A 2 The CHARGE LED lights up while charging 3 The charging time is approximately 5 hours When the charging is complete the red FULL LED will turn on and the charging will stop The instrument will not have any problems even if the charging jack is plugged in for a long time 4 If a different charger voltage higher than 12V is used it may cause a breakdown ...

Page 5: ... LED lights will blink 3 times and make a beep sound 8 2 Controller Instructions 1 Power up the controller using the Power On switch 2 Locate detector tester rubber gaiter over the detector located on the ceiling adjust the length of the pole where required 3 Press either the Heat or Smoke switch according to the detector type under test 4 Heat and smoke are created in 5 and 3 seconds after the he...

Page 6: ...5 FireView Detector Test Kit WWW AMPAC NET UNCONTROLLED DOCUMENT NOTE Due to AMPAC s commitment to continuous improvement specifications and information contained within this document may change without notice ...

Reviews: