Gas Release Panel Short Form Installation Guide
Item Numbers: 2983-0304
Connecting the Standby Batteries
CAUTION: There is a risk of explosion if the battery is replaced by
an incorrect type. Always dispose of used batteries in accordance
with the battery manufacturers’ instructions.
Note
: On a standard ‘as-supplied’ unit, PLK1 (‘Battery Monitoring’ link) is
not fitted and a fault will occur on initial power-up if fully charged batteries
are NOT connected. For the emergency standby power supply, only use
good quality, sealed VRLA batteries. Position and connect the 2x12Vdc,
7Ahr batteries, as shown in diagram (see right).
Connecting Circuits to the Main Control PCB
Terminate incoming and outgoing circuits at the Main Control PCB connectors (see Figure 2 overleaf).
Technical Specification
POWER SUPPLY
Mains Supply Voltage:
230Vac, 50/60 Hz
Internal Power Supply
24Vdc Nominal
Max. Output Current:
3A@230Vac
Power Rating (including charging):
1.5A cont, 3A peak
Battery Type:
2 x 12Vdc, 7Ahr VRLA type, connected in series
Battery charge Current:
0.7A
Earth Fault Monitoring:
YES
Mains supply/ Battery charger monitored for failure
YES
Quiescent Current drain on mains fail
40mA
DETECTOR CIRCUITS
Number of Conventional detector circuits:
3 @ 21-28Vdc
Line Monitored for open and short circuit faults:
YES
Max. Cable length per circuit:
250m
Max. Number of smoke/heat detectors per circuit:
20
Max. Combined number of detectors and call points per circuit:
32
Zone quiescent current:
2mA max.
End-of-line resistor value:
6K8 Ohm +/- 5%, 0.25W
SOUNDER CIRCUITS
Number of conventional sounder circuits:
3 (two x 1
st
stage, one x 2
nd
stage)
Line monitored for open and short circuits:
YES
Sounder output rating:
21-28Vdc, fused @ 200mA per circuit
Max. Sounder cable length per circuit:
50m
Max. Number of polarised sounders per circuit:
10 @ 20mA each
End-of-line resistor value:
6K8 Ohm +/- 5%, 0.25W
MONITORED INPUTS
Number of monitored inputs:
6 (Manual release, Flow switch, Low pressure, Mode, Hold, Abort)
Thresholds:
8K to 2K ohms (normal); 1.8K to 200 ohms (active); 150 to 0 ohms (short circuit)
End-of-line resistor value:
6K8 Ohm +/- 5%, 0.25W
AUXILIARY OUTPUTS
Number of auxiliary outputs*:
6 (Fire, Local fire, Extract, 1st stage, 2nd stage, Fault)
Extract time:
Adjustable 1-900 seconds (1 second steps)
Relay contact rating:
30Vdc, 1A max. Note: DO NOT switch mains voltage using these outputs
*Note; 5 Additional relay outputs (Reset, Mode, Discharged, Hold, Abort) are available on the GR Output Expansion Relay Board (Item No. 2980-0004)
REMOTE INPUTS
Number of remote inputs:
4 (SIL, AL, FLT, RST)
Auxiliary output:
24V, 100mA electronic fuse
EXTINGUISHANT RELEASE OUTPUTS
Extinguishant release output:
21-28Vdc, rated at 1A for 5 minutes
Extinguishant release time delay:
Adjustable 1-60 seconds (1 second steps)
Extinguishant release duration:
Adjustable 1-300 seconds (1 second steps)
Extinguishant release flooding time:
Adjustable 60-1800 seconds (1 second steps)
Extinguishant release end-of-line:
GR System Line Terminator (Item No. 2980-0005)
FUSES Compliant with IEC (EN60127 Pt2)
Mains supply fuse (F1): 1A HRC 20mm ceramic; Battery fuse (F2): 5A F 20mm glass; Auxiliary output fuse: 100mA electronic; Sounder circuit fuse: 200mA per
i
it
DIMENSIONS & WEIGHT
Physical Dimensions (W mm x H mm x D mm):
Back box = 439 x 276 x 70 approx (Metal); Lid = 467 x 293 x 29 approx (Plastic)
Weight:
1.75kg (without batteries)
Accessory Pack
1 x Installation Instructions; 1 x User Manual Log Book, 1 x Allen key; 1 x 1A HRC Fuse; 1 x 5A F Fuse; 1 x set of links for PLK1 & PLK2; 1 x set of battery
connection leads.
Introduction
The Gas Release panel is a three zone automatic extinguisher control panel that is compliant with EN12094-1
and EN54-2. The panel incorporates a 3A, EN54-4 compliant switch mode PSU and a 128 x 64 pixel LCD that
facilitates system programming.
Installation
Location
The panel must be mounted indoors on a dry, flat surface in an area that is well ventilated. Ideally the panel
indicators should be at eye level and the ambient light level should allow the status of any indicators to be clearly
seen.
Fixing
Note
: The panel’s base PCBs should be removed prior to first fix installation.
Using the five mounting holes provided, fix the base securely onto a wall. The mounting holes are suitable for
use with No.8-10, or 4-5mm countersunk screws. Assess the condition and construction of the wall and use
suitable screw fixings. Any dust or swarf created during the fixing process must be kept out of the enclosure and
care must be taken not to damage any wiring or components.
Wiring and Cable Entry
All wiring should be installed in accordance with the current edition of the IEE Wiring
Regulations (BS7671), or the relevant national standards.
The requirement for the mains supply to the panel is fixed wiring, using 3-core cable (no
less than 1mm
2
and no greater than 2.5mm
2
), or a suitable three conductor system, fed
from an isolating switched spur, fused at 3A.
In order to maintain cable segregation, the incoming mains cable should be fed into the
panel via the top right hand side knockouts (provided on the base unit). Knockouts
should be removed with a sharp, light tap using a flat 6mm broadsided screwdriver as
shown in diagram (see right). Always ensure that if a knockout is removed, the hole is
filled with a good quality 20mm cable gland. Any unused knockouts must be securely
blanked off.
WARNING: DO NOT ATTEMPT TO CONNECT THE MAINS SUPPLY TO THE POWER SUPPLY PCB UNTIL
ALL PCBs ARE SECURELY INSTALLED IN THE ENCLOSURE.
Connecting Mains Supply to the Power Supply PCB