Step 3: Air Evacuation of the equipment: 

 

Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. 

 

There is no extra refrigerant in the outdoor unit for air purging. 

 

1.  Connect a charging hose with a push pin to 

the Low side of a charging set and the service 
port of the gas side 3-way valve. 

o

 

Be sure to connect the end of the 
charging hose with the push pin to the 
service port. 

2.  Connect the center hose of the charging set to 

a vacuum pump. 

3.  Turn on the power switch of the vacuum pump 

and make sure that the needle in the gauge 
moves from 0 cmHg (0 MPa) to -76 cmHg 
(-0.1 MPa). Then evacuate the air 
approximately ten minutes. 

4.  Close the Low side valve of the charging set 

and turn off the vacuum pump. Make sure that 
the needle in the gauge does not move after 
approximately five minutes. 
Note : BE SURE TO TAKE THIS 
           PROCEDURE IN ORDER TO AVOID 
           REFRIGERANT GAS LEAKAGE. 

5.  Disconnect the charging hose from the 

vacuum pump and from the service port of the 
3-way valve. 

6.  Tighten the service port caps of gas side 

3-way valve at a torque of 18 N•m with a 
torque wrench. 

7.  Remove the valve caps of both of the gas side 

and liquid side 3-way valve. Position both of 
the valves to “OPEN” using a hexagonal 
wrench (4 mm). 

8.  Mount valve caps onto the gas side and liquid 

side of the 3-way valve. 

o

 

Be sure to check for gas leakages. 

CLOSE

Vacuum pump adaptor

Outdoor unit

Liquid side

Gas

side

OPEN

Vacuum

pump

Liquid side 3-way valve

Gas side 3-way valve

Liquid side

Gas

side

Tube connector

Tube connector

Tube connector

Tube connector

Close

Close

Indoor Unit

Indoor Unit

 

 
 
 
 
 
 
 
 
 
 
 

 

CAUTION

 

 

If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 

 above take the following measure: 

If the leak stops when the piping connections are tightened further, continue working from step 

If the leak does not stop when the connections are retightened, repair location of leak. 

Do not release refrigerant during piping work for installation and reinstallation. 

Take care of the liquid refrigerant, it may cause frostbite. 

11.5  Connect The Cable To The Outdoor Unit 

1.  Remove the particular plate from the unit by 

loosening two screws. 

2.  Cable connection to the power supply through 

isolating Devices (Disconnecting means). 

o

 

Connect approved type polychloroprene 
sheathed 

power supply cord 

CU-4Z80*** (3 x 2.5 mm

2

), CU-5Z90***  

(3 x 4.0 mm

2

) 60245 IEC 57 type 

designation or heavier cord to the 
terminal board, and connect the others 
end of the cord to Isolating Devices 
(Disconnecting means). 

3. 

Connection cable 

between indoor unit and 

outdoor unit shall be approved 
polychloroprene sheathed 4 x 1.5 mm

2

 flexible 

cord, type designation 60245 IEC 57 or 
heavier cord. Allowable connection cable 

length of each indoor unit shall be 30 m or 
less. 

4.  Connect the power supply cord and 

connection cable between indoor unit and 
outdoor unit according to the diagram as 
shown. 

 

Screws

Particular plate

 

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for CU-4Z80 Series

Page 1: ...iping Amin M 2 5 LFL 5 4 h0 2 Amin Required minimum room area in m2 M Required charge amount in appliance in kg LFL Lower flammable limit 0 306 kg m3 h0 Installation height of the appliance 1 8 m for...

Page 2: ...Unit Installation Diagram 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut 10 mm 2 When installing at roof please consider strong wind and earthquake Please fasten the ins...

Page 3: ...side of CS MZ16 CS TZ25 CS MTZ16 CS TZ35 CS Z20 CS TZ42 CS Z25 CS TZ50 CS Z35 CS TE20 CS Z42 CS TE25 CS Z50 CS TE35 CS XZ20 CS TE42 CS XZ25 CS TE50 CS XZ35 CS E9 CS XZ50 CS E12 CS TZ20 CS E18 Liquid s...

Page 4: ...if there is a constant pressure drop Move to next step Step 2 Refrigerant leak detection if there is any pressure drop Otherwise release the Nitrogen gas and move to Step 3 Evacuation of the equipmen...

Page 5: ...ptor Outdoor unit Liquid side Gas side OPEN Vacuum pump Liquid side 3 way valve Gas side 3 way valve Liquid side Gas side Tube connector Tube connector Tube connector Tube connector Close Close Indoor...

Page 6: ...s at the interface point are sufficient for the installation of the equipment CU 4Z80 Unit D Unit C Unit A Unit B Indoor Outdoor connection cable Power Supply Cord Isolating Devices Indoor Unit A Indo...

Page 7: ...remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please make flare after in...

Reviews: