OMEGA F ilt ers – Ins tal lati on & Oper atio n Manu al
Pag e 2 of 8
Control Philosophy
Control Concept – Single Filter
a. Control Concept – Single Filter
This section describes the basic principles of the Omega Filter's control system. This information is
applicable for both; control panels provided by Amiad or for panels provided by others.
Electrical Components and Instrumentations
•
0.55, 0.75, or 1.2KW, 3 Phase motor (Two rotation directions)
•
2 X NC Proximity Switches or mechanical limit switches
•
3-way NC Solenoid - Operating Pneumatic Actuated Butterfly Valve with or without limit switches.
(Motorized valve is optional)
•
One of the below instrumentation options:
a. PDT
4-20 mA pressure differential transmitter
b. 2 x PT 4-20 mA pressure transmitters (inlet / outlet)
c. PDS
pressure differential switch
PLC I/O Basic List
Digital Inputs:
Function
Comments
01
Test
Local start of flush cycle
Push-Button or command from HMI
02
START
Remote start flush cycle
Signal from remote supervision system
03
RESET
Stop flush cycle and clear faults / alarms
Push-Button (Remote signal is not
recommended )
04
PAUSE
Flushing prevention
Signal from remote supervision system
05
PDS
N.O. Pressure Differential Switch
Option c
06
TLS 1
Top Limit Switch (N.C.)
Mechanical or Proximity Switch
07
BLS 1
Bottom Limit Switch (N.C)
Mechanical or Proximity Switch
08
O.L. 1
Overload Motor Protector
Fault or run indication from motor starte
10
ZSO
Valve Position Limit Switch - OPEN
Option - Mechanical or Proximity Switch
11
ZSC
Valve Position Limit Switch - CLOSE
Option - Mechanical or Proximity Switch
Digital Outputs:
01
CON
Cycle On (Flushing in process)
Lamp and/or free potential signal
02
SOK
No Fault (System OK)
Lamp and/or free potential signal
03
F
Fault Lamp
Blinking when Alarm; On in Fault Mode
04
XV1
Solenoid Valve
Motorized actuator as an option
05
CU1
Motor Starter Up (CCW)
Contactor
06
CD1
Motor Starter Down (CW)
Contactor
Analog Inputs:
01
DPT
Differential Pressure 4-20 mA
Option a
02
PT1
Inlet Pressure 4-20 mA
Option b
03
PT2
Outlet Pressure 4-20 mA
Option b
Analog Outputs:
01
DP Value (Optional)
Analog signal to remote supervision sys
Summary of Contents for Omega 13.5K
Page 2: ......
Page 5: ...3 Safety Instructions ...
Page 10: ...4 Technical Specifications ...
Page 12: ...5 Drawings ...
Page 18: ......
Page 19: ...6 Description of Filter Operation ...
Page 23: ...7 Control Philosophy ...
Page 31: ...8 Installation Instructions ...
Page 35: ...9 Commissioning Start up and First Operation ...
Page 38: ...10 Part Schedule ...
Page 52: ...11 Maintenance ...
Page 88: ...12 Troubleshooting ...
Page 90: ...13 Amiad Limited Warranty ...