pressure and the filtration degree of the filter.
Press SUBMIT to submit the data.
Technician Settings
See the following table.
About
Displays the current device ID, App version, Firmware version, Hardware version, Bootloader
version, controller installation date. If updated firmware is available this screen prompts the user to
update the system by pressing the Update Now button.
Technician Settings screens:
This section of the application contains the
system’s
basic and fundamental settings. Do not change any of these settings if you
are not totally familiar with the specific filtration system, filters and controller. Incorrect settings may cause the system to
become nonoperational.
Access to the Technician Settings screens requires a password. Please contact your dealer to obtain a password.
The upper black line
Allows the technician to search for a specific data item.
Filter Type
Select the specific filter(s) model controlled by the current controller.
Operation Mode
Select the operation mode of this controller;
Controller = Primary
Primary = the first controller in a chain of controllers or a stand-alone controller.
Secondary = a member of a chain of controllers which is controlled by a Primary controller.
DP Sensor = set this controller as the source of DP signal for the controller chain.
Pause Interval flush if DP
is less than
Set a DP value to serve as a minimal DP level for starting a flush cycle by the time intervals
parameter. If the DP reading is lower than this value the flush cycle by time interval will not start.
Interval Flush Pause
Enable or disable the operation of the Time Operation Mode Threshold parameter.
DP Delay
Set the time that the DP signal should be ON before starting flushing according to a DP signal. This
parameter is used to eliminate unnecessary flushing due to a momentary high differential pressure.
High DP Alarm Set Point
Set the DP level for issuing a High DP Alarm Message (System Log).
Repeated Flushes to
Start Fault Mode
Set the number of continuous flush cycles so the ADI-P controller enter to Fault Mode .
Cycle Time for
Continuous
Set the cycle time for counting a flush cycle as continuous flushing. If the time between two flush
cycles is shorter than “Minimum Cycle Time for Continuous Status” –
then it’s counted as
continuous flushing.
Action in Continuous
Select the Action to Take when Continuous Fault Mode is detected: Ignore: Ignore the alert and
continue flushing according to DP Set Point. Time only: Stop flushing according to DP measurement
and flush according to Time Interval only.
Ignore DP After Flush
Set the time duration after the end of a flush cycle during which the DP reading is ignored.
End of Cycle
Set the time for the end of cycle signal to be ON after the flush cycle ends.
Relay Output
Set the operation of the Output relay to EOC (end of cycle ON), Alarm (set this output as an Alarm
output) or Disable (the relay is not active).
Valve 2 Mode
It is possible to connect a second solenoid to the system that can operate as a second filter or a
downstream valve.
Set the task for the second solenoid: Disable, 2
nd
filter or Downstream.
When a downstream valve is selected a new entry field is added to the Technician Screens List for
setting the delay time for the downstream valve.
IO Screen
This screen displays the status of the system's I/Os according to the currently designated filter
model:
Digital Input 1 type, Digital Input 3 type, the maximal reading of the Inlet pressure, the minimal
reading of the Outlet pressure, the Piston pressure and the current Battery Voltage.
This screen also allows the technician to test the operation of the system outputs:
Solenoid 1, Solenoid 2 and the Output Relay. Select ON or OFF.
Freezing Protection
Freezing Protection - This function is come to prevent from the filter to freeze in low temperature
while it connected to water source. Default: Enable