background image

 

ADI-P

 

                                                                            910101-000992 / 0

5.20 0

2  

Page 12 of 21 

pressure and the filtration degree of the filter. 
Press SUBMIT to submit the data. 

Technician Settings 

See the following table. 

About 

Displays the current device ID, App version, Firmware version, Hardware version, Bootloader 
version, controller installation date. If updated firmware is available this screen prompts the user to 
update the system by pressing the Update Now button. 

 

Technician Settings screens: 

 
This section of the application contains the 

system’s 

basic and fundamental settings. Do not change any of these settings if you 

are  not  totally  familiar  with  the  specific  filtration  system,  filters  and  controller.  Incorrect  settings  may  cause  the  system  to 
become nonoperational.   
Access to the Technician Settings screens requires a password. Please contact your dealer to obtain a password. 
  
The upper black line 

Allows the technician to search for a specific data item. 

Filter Type 

Select the specific filter(s) model controlled by the current controller. 

Operation Mode 

Select the operation mode of this controller;  
Controller = Primary 
Primary = the first controller in a chain of controllers or a stand-alone controller.  
Secondary = a member of a chain of controllers which is controlled by a Primary controller.  
DP Sensor = set this controller as the source of DP signal for the controller chain. 

Pause Interval flush if DP 
is less than 

Set a DP value to serve as a minimal DP level for starting a flush cycle by the time intervals 
parameter. If the DP reading is lower than this value the flush cycle by time interval will not start.  

Interval Flush Pause    

Enable or disable the operation of the Time Operation Mode Threshold parameter. 

DP Delay 

Set the time that the DP signal should be ON before starting flushing according to a DP signal. This 
parameter is used to eliminate unnecessary flushing due to a momentary high differential pressure. 

High DP Alarm Set Point 

Set the DP level for issuing a High DP Alarm Message (System Log). 
 

Repeated Flushes to 
Start Fault Mode 

Set the number of continuous flush cycles so the ADI-P controller enter to Fault Mode . 

Cycle Time for 
Continuous 

Set the cycle time for counting a flush cycle as continuous flushing. If the time between two flush 

cycles is shorter than “Minimum Cycle Time for Continuous Status” –

 

then it’s counted as 

continuous flushing. 

Action in Continuous  

Select the Action to Take when Continuous Fault Mode is detected: Ignore:  Ignore the alert and 
continue flushing according to DP Set Point. Time only: Stop flushing according to DP measurement 
and flush according to Time Interval only. 

Ignore DP After Flush 

Set the time duration after the end of a flush cycle during which the DP reading is ignored. 

End of Cycle 

Set the time for the end of cycle signal to be ON after the flush cycle ends. 

Relay Output 

Set the operation of the Output relay to EOC (end of cycle ON), Alarm (set this output as an Alarm 
output) or Disable (the relay is not active).  

Valve 2 Mode 

It is possible to connect a second solenoid to the system that can operate as a second filter or a 
downstream valve.  
Set the task for the second solenoid: Disable, 2

nd

 filter or Downstream. 

When a downstream valve is selected a new entry field is added to the Technician Screens List for 
setting the delay time for the downstream valve.  

IO Screen 

This screen displays the status of the system's I/Os according to the currently designated filter 
model:  
Digital Input 1 type, Digital Input 3 type, the maximal reading of the Inlet pressure, the minimal 
reading of the Outlet pressure, the Piston pressure and the current Battery Voltage. 
 
This screen also allows the technician to test the operation of the system outputs: 
Solenoid 1, Solenoid 2 and the Output Relay. Select ON or OFF. 

Freezing Protection 

Freezing Protection - This function is come to prevent from the filter to freeze in low temperature 
while it connected to water source. Default: Enable  

Summary of Contents for ADI-P

Page 1: ... 000992 05 2020 Page 1 of 21 AMIAD Water Systems Ltd ADI P Smartphone Operated Controller for Filtration Systems Installation Operation and Maintenance Instructions Original Instructions Patent Pending Ref 05 2020 ...

Page 2: ... embodied therein Amiad may alter remove or change the Content without any further notice You may not reproduce copy modify create derivative works from sell or participate in any sale of or exploit in any way in whole or in part any of this document or its content The confidential nature of and or privilege in the file enclosed is not waived or lost as a result of a mistake or error in this file ...

Page 3: ...ontrol 5 Before any maintenance or non standard operation 5 Introduction 6 ADI P Controller Quick Guide 6 Screens Details 10 Download and Export Reports 13 Specifications Table 14 ADI P Terminal Blocks Connections 15 Annex A Chaining ADI P Controllers 16 Annex B Remarks on connecting the ADI P Controller to an AC DC Adaptor 19 Amiad Limited Warranty 20 ...

Page 4: ...rer prior to any non standard use of this equipment Do not carry out system cleaning and or maintenance in an explosive atmosphere Installation General Install the controller according to the detailed installation instructions provided in this manual or in the Quick Guide provided with the filter or controller Make sure to leave enough side and top clearance to enable easy access for safe maintena...

Page 5: ... do not perform any operation other than those given in this manual Do not operate or use the controller for purposes other than its original design The system is for use for non hazardous liquids only Do not carry out system cleaning and or maintenance in an explosive atmosphere Before any maintenance or non standard operation Servicing the controller should be done only by technicians authorized...

Page 6: ...nd configured for that specific filter model or as a standalone unit to be connected and configured for an existing installed filter s This document covers both product configurations ADI P Controller Quick Guide for detailed information see Understanding the application s screens data items on page 10 Take few moments to familiarize yourself with the ADI P Controller components 1 ADI P panel for ...

Page 7: ...ree ADI P application by Amiad Water Systems is available for download on Google Play Android version 5 and up or the App Store iOS version 9 and up Pairing the controller with your mobile phone 1 Activate your phone s Bluetooth discovery mode and start the ADI P application 2 Select the applicable SYSTEM UNITS 3 REGISTER your filter to create an account 4 Click CONNECT The application scans for c...

Page 8: ...rchased separately Name your site select the filter model and enter your controller s serial number You may add a site photo by clicking on 8 Enter the SITE INFO details optional 9 Once done click SUBMIT to add your new filter to the SITE LIST 10 In order to view data from your controller select the active controller from the SITE LIST marked by the active Bluetooth icon 11 The ONLINE STATUS scree...

Page 9: ...ize yourself with the ADI P mobile application interface Once running and controlling the filter the application has 5 main screens Scroll through these screens by sliding to the right or to the left You may also reach the desired screen by clicking on the designated icons that appear at the bottom of the screen ...

Page 10: ...The upper red line Displays the name of the currently connected controller and the communication status The second line Enables sorting alerts between two dates and resetting an alert The alerts list see below Display the alert messages according to their occurrence time and date Alarms and faults list Alert Possible cause Recommended Action Low battery Low battery voltage Replace all 4 controller...

Page 11: ...scription User Manual This screen shows the user manual Support Contact Us screen App Version Displays the current version of the ADI P Application Messages Messages from the Amiad system The Settings screens Enter the setup screens by tapping on the Settings icon in the upper right corner of any of the 5 main screens The upper red line Displays the name of the currently connected controller and t...

Page 12: ... momentary high differential pressure High DP Alarm Set Point Set the DP level for issuing a High DP Alarm Message System Log Repeated Flushes to Start Fault Mode Set the number of continuous flush cycles so the ADI P controller enter to Fault Mode Cycle Time for Continuous Set the cycle time for counting a flush cycle as continuous flushing If the time between two flush cycles is shorter than Min...

Page 13: ...Settings Allows the user to delete all of the controller s data and restore the factory default settings The default filter model will be according to the filter provided with the controller or according to the customer s initial settings Delete Allows the user to delete a site from the smartphone Download and Export Reports In addition to the on screen reports the ADI P is capable of logging stor...

Page 14: ...rnal Piston Pressure Sensor Optimized flush time duration IP Rating IP65 User Interface Via Smartphone Application Filter models Sigma Pro Mini Sigma M104LPN M104XLP M106LP M106XLP M108LP M110P M102C M103C M103CL M104C M104CL MG 110 MG 112 M MG 112 S MG 114 M MG 114 S SK Compact 2 Digital Inputs DP Switch Pause Chain Controller Options Onboard End of Cycle Pulse NO NC Standards FCC 47CFR part 15 2...

Page 15: ...ding on the filter type NO versus NC solenoids a Please note that NO solenoids have black manual overriding handles while NC solenoids have red manual overriding handles b For both solenoid types do not change the wires connection at the controller s terminal strip the black wire should be connected to the black solenoid connector and the red wire should be connected to the red solenoid connector ...

Page 16: ... to the DP input of the rest This type of connection can be spanned over as many controllers as needed See page 17 Stage 1 Wires Connection When the actual DP switch sends a signal the Primary Controller starts a flush cycle Once this cycle is completed the Primary Controller sends a signal through its EC output to the second controller to start its flush cycle and so on to the last controller in ...

Page 17: ...ntroller s NO relay output and the Secondary controller s external DP input Important For your safety and in order to avoid damaging the controller remove the batteries before starting the wiring process 2 Make sure that the wires gauge the diameter of the cable used is similar to the solenoid wires gauge 4 mm This is critical for maintaining the IP65 rating of the controller dust tight and protec...

Page 18: ...Technician Settings D Enter the password E Select Mode of Operation F Click on the current status of the controller generally set to Controller G Under Choose Mode select Primary mode for the current controller To change from Primary controller to Secondary controller perform Steps A F as above and under Step G select Secondary mode Check the controller s operation by starting a flush cycle throug...

Page 19: ...n indoor outdoor external power source All external connections must be done by an authorized electrician with qualifications to perform this type of work Type of Adaptor Not supplied by Amiad The adaptor should be a standard DC adaptor that supplies 7 14 VDC at its output connection The system must be protected by a max 1A external fuse and it must use a minimum of 22 AWG wires Connections and Co...

Page 20: ...tative of Amiad 8 This Warranty will not apply to damaged or defective products resulting from or related to i Fire flood power surges or failures or any other catastrophe and or unforeseen occurrence such as but not limited to those for which the Buyer is customarily insured for or any force majeure events ii Fault abuse or negligence of the Buyer iii Intake water not meeting the agreed standards...

Page 21: ... 1 1233500 Israel Tel 972 4690 9500 Fax 972 48141159 Email info amiad com European Authorised Representative for CE Obelis s a Bd Général Wahis 53 1030 Brussels Belgium Tel 32 2732 5954 Fax 32 27326003 Email mail obelis net EU Declaration of Conformity https www amiad com certificatesDownload asp ...

Reviews: