30 mm between the insert box and the wall of the fireplace structure.
If the floor is made of a flammable material, the opening must be at least 300 mm over the
floor.
The fireplace structure must have ventilation holes. An entry hole with a surface of at least
300 cm2 must be placed at a level under the insert. The air that enters through the entry hole
must be able to flow freely up past the insert. An exit hole with a surface of at least 400 cm2
must be placed at a level above the insert. The exit hole must be at least 500 mm from the
ceiling.
Right above the exit hole, a nonflammable heat stop sheet or slab (25 mm Rockwool or
similar) must cover the fireplace structure. The distance between the heat stop sheet or slab
and top of exit hole is about 100 mm.
A nonflammable floor protection must cover the floor at least 300 mm to the front of the
firing door and at least 150 mm to each side of the firing opening. Please note that the floor
must be capable of supporting the installation.
Distance from insert door to furniture must be at least 700 mm.
Mounting
The insert is positioned in the opening of the fireplace structure and levelled.The insert is
connected to the chimney by a 125 mm diameter flue pipe that is fastened to the flue collar.
The smoke in the chimney gets hot. Therefore, ensure that the distances to flammable
materials are observed.
Caution must therefore be observed with regard to children touching the stove.