B. SPECIFICATIONS OF CONCRETE
(See Fig. 3)
Specifications of concrete must be adhered to the specification as following.
Failure to do so may result in lift and/or vehicle falling.
1. Concrete must be thickness 100 mm minimum and without reinforcing steel bars
,
and must be dried completely before the installation.
2. Concrete must be in good condition and must be of test strength 3,000 psi
minimum.
3. Floors must be level and no cracks.
C. AIR SUPPLY
Air pressure requirement: 0.5Mpa~0.8Mpa, Air line size
Φ
8 *
Φ
6
and
Φ
6 *
Φ
4
.
D. POWER SUPPLY
The electrical source must be 2.0HP minimum. The source cable size must be
2.5mm² and in good condition of contacting with floor.
III. STEPS OF INSTALLATION
A. Location of installation
Check and insure the installation location (concrete, layout, space size etc.) is
suitable for lift installation.
B. Check the parts before assembly
1. Packaged lift and hydraulic power unit
(See Fig. 4)
.
Fig. 3
Fig. 4
混凝土强度必须大于
3000PSI
;
Fig. 3
Concrete intensity must be 3,000psi minimum