Online Battery Backup

 

 

 

 
 

 
 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

© 2019 AMETEK Electronic Systems Protection | 1-800-645-9721 | surgex.com | UM-UPS-Global-6kVA-REV-A                                                          

UPS-17602-52R – 6000 VA UPS 

 

 

User Manual

 

 

 

Summary of Contents for Surgex UPS-17202-53R

Page 1: ...Online Battery Backup 2019 AMETEK Electronic Systems Protection 1 800 645 9721 surgex com UM UPS Global 6kVA REV A UPS 17602 52R 6000 VA UPS User Manual...

Page 2: ...2 2019 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com User Manual _________________________________________________________________...

Page 3: ...ing 6 2 Rack Tower Installation 7 2 1 Tower Installation 7 2 2 Rack Installation 8 2 2 1 Attaching the mounting ears 8 2 2 2 Mechanical Fixing of 19 inch Units 8 2 2 3 Assembly Steps 9 2 3 Electrical...

Page 4: ...5 8 Turn off the UPS without utility power supply in Battery mode 21 3 6 LCD Operation 22 3 6 1 Main Interface Home Page 23 3 6 2 Operation Menu 23 4 Interfaces 33 4 1 Serial Interface COM3 33 4 2 Int...

Page 5: ...operating in a commercial environment The UPS generates uses and can radiate radio frequency energy If installation and use is not in accordance with the instruction manual it may cause harmful inter...

Page 6: ...a cold environment to the operating room condensation may occur Before you switch on the equipment it must be absolutely dry An acclimatization period of at least two hours is required The equipment m...

Page 7: ...e not covered by warranty 1 3 Emergency WARNING The supply to the load may be operated by opening all the switches WARNING DO NOT USE WATER to extinguish any fires that may occur in the area in which...

Page 8: ...Since new batteries often do not provide full capacity after an initial charge it may be necessary to carry out a number of discharge recharge cycles before optimum performance is achieved In order to...

Page 9: ...at the con tents are undamaged 1 11 2 Storage If it is not intended that the UPS be used immediately upon delivery attention shall be paid to the storage conditions If the batteries or the equipment i...

Page 10: ...future use 1 13 Handling The equipment must be kept upright at all times and handled with care damage may be caused if dropped or subjected to severe impact 1 14 Environmental Conditions The UPS must...

Page 11: ...in the Tower configuration A Install Stand a lone Refer to Figure 1 Assemble two feet and one short extension as one tower stand as shown in Step 1 Align the two stands approximately 35 cm apart as s...

Page 12: ...Fixing of 19 inch Units Selection of the mounting location Figure 3 NOTE The UPS and its battery cabinets are designed to be mounted horizontally in 19 racks When installing the units please consider...

Page 13: ...M6 screws to mount the right and left rail sliders to the two front posts of the four post rack Refer to Figure 5 below Figure 5 Step 2 Use 4 M6 screws to mount the right and left rail sliders to the...

Page 14: ...right and left ears attached onto the rail guide until the ears are in contact with the front of the rail guide Refer to Figure 8 below Figure 8 Step 5 Fasten each ear to the rack with the M6 screws R...

Page 15: ...ing to the UPS 2 3 1 External Protection and Isolating Devices WARNING A disconnect switch shall be provided by others for the AC input circuit To reduce the risk of fire connect only to a circuit pro...

Page 16: ...account for electrical losses Table 5 Term ID Description UPS Part Number UPS 17602 52R Wire gauge awg Term torque in lbs min wire temp C Input Mains L Input Line 6 10 70 N Input Neutral 6 10 70 GND I...

Page 17: ...USB communication port 12 Input terminals 3 EPO Emergency Power Off connector 13 Input ground terminal 4 Share current port for parallel function 14 Output terminals 5 Parallel port for parallel funct...

Page 18: ...l the connected devices before connecting to the UPS 2 4 1 Prepare input and output cables Prepare the input and output cables as described in Table 5 on page 12 and as shown in the figure below The s...

Page 19: ...andard battery pack there is one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external ba...

Page 20: ...battery at this mode There is no bypass at this mode Battery Mode When the input voltage is out of the acceptable range or power failure and the UPS is turned on the inverter is running the UPS will b...

Page 21: ...urn off the UPS Or press it to return to last menu UP Press this button to jump up to an item in the menu Or press this button to jump to the previous page in the screen Or press this button to increa...

Page 22: ...ck breaker is in the ON position Set the external mains input breaker to the ON position The fan will now be running and the UPS will supply power to the loads via bypass The UPS is operating in Bypas...

Page 23: ...consume a large amount of power If inductive loads such as a printer need to be connected the inrush current should be calculated to ensure the capacity of the UPS is not exceeded 3 If the UPS is ove...

Page 24: ...gh the LCD panel or the communication port 3 5 6 Test the batteries 1 To check the battery status or the performance when the UPS is running in Line Converter mode enter Control Batt Test to instruct...

Page 25: ...ess the OFF ESC button The LCD will show a prompt page of Turn Off Move the arrow to Yes using the up or down button then press ON ENTER The UPS will turn off and go to bypass mode with beeping once A...

Page 26: ...User Manual _________________________________________________________________ fdfefd fd 2019 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 22...

Page 27: ...me page 4 Press the UP or DOWN button to enter the operation menu see 3 7 2 1 5 When the LCD displays the home page and if the UPS is in bypass press ON ENTER button to turn on the UPS to AC converter...

Page 28: ...and confirmed the UPS will transfer to AC mode or to converter mode or to battery mode according to the setting and input status Control Line Mode Turn On Turn On Batt Test IP 208 0V 50 0Hz Mute Yes O...

Page 29: ...be muted only when the UPS is in battery bypass fault mode a reminder will pop up in the screen After the selec tion is confirmed the display will return back to the home page and the mute icon will...

Page 30: ...lays the measured value of the parameters such as voltage current frequency power capac ity time etc Press the UP or DOWN button to explore the pages Input 1 5 Output 2 5 Battery 3 5 Volt 208 0V Volt...

Page 31: ...s F 54Hz LowLoss F 48Hz LowLoss F 46Hz Battery 4 6 UPS Info 5 6 Others 6 6 Backup Time UPS Model XXXX Hot Standby 990 Minute DSP Ver XXXX Disable Batt Test Type MCU Ver XXXX Bypass Mute Short Time Uni...

Page 32: ...atic bypass is acceptable but manual bypass is not available Manual bypass means the user manually puts the UPS into Bypass mode for example in AC mode turning off the UPS will put the UPS into Bypass...

Page 33: ...e output frequency to 60Hz ATO If selected the output frequency will be decided according to the latest normal utility frequency If the utility frequency is in the range 46Hz to 54Hz then the output f...

Page 34: ...ed When the UPS has been continuously operating in battery battery test mode the UPS will automatically shut down when the discharge time set by option 1 2 below has expired Disable Battery discharge...

Page 35: ...e 3 Chg Adjust the Charger output voltage The adjustable range is from 0V to 6 9V The default value is 0V Charger calibra tion is only available in bypass line converter mode NOTE Before making any ch...

Page 36: ...6 The default value is 1 group Batt Cap Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Factor Calibrate the displayed backup time by ad...

Page 37: ...fer of operational states to external alarm systems via voltage free contacts The necessary communication software packages and interface cables are available as options 4 1 Serial Interface COM 3 The...

Page 38: ...above the USB connector in the upper rear of the unit If the circuit between the two EPO connector pins is opened the output of the UPS is immediately switched off To restart the UPS the procedures ou...

Page 39: ...and the ground terminal 6 2 Test Replacement and Disposal of Batteries The UPS does not require maintenance by the user however battery maintenance is recommended in accordance with IEEE Recommended P...

Page 40: ...e of used batteries according to the instructions Do not open or damage the battery cases Released electrolyte is harmful to the skin and eyes and may be toxic A battery can present a risk of electric...

Page 41: ...inet in the case of fixed connections 3 After 5 hours unplug from the mains supply or switch off the input miniature circuit breaker of the UPS in case of fixed connections and switch off the circuit...

Page 42: ...l immediately 3 In an emergency immediately disconnect the UPS from the connection to the utility external battery and output to avoid more risk or danger 7 3 Troubleshooting table Refer to the table...

Page 43: ...input fuse on the power stage board is open Check the input fuse and replace the fuse if it is open Warning 33 Overload 3 Times The UPS is locked in bypass after an overload has occurred three times...

Page 44: ...e internal converter failed 1 Shut down and restart the system and observe if the fault reoccurs 2 Contact the dealer for repair Fault 03 Bus Under The internal converter failed so that the DC bus vol...

Page 45: ...on is not securely connected in the parallel system Securely connect the parallel cable Fault 36 OP I Unbalance The output current is extremely unbalanced between the parallel UPSs or there is an erro...

Page 46: ...er Manual _________________________________________________________________ fdfefd fd 2019 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 42 9 APPENDIX A SPECIFICATIO...

Page 47: ...User Manual _________________________________________________________________ fdfefd fd 2019 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 43...

Page 48: ...ent temperature site specific usage patterns and load conditions 10 540 92 233 402 593 801 16 hrs 16 hrs 16 hrs 20 1080 46 118 204 301 406 519 639 765 30 1620 30 75 130 192 259 331 408 488 40 2160 21...