A01-00150 Rev B
03: Voltage Range for Bypass
Interface
Setting
Parameter 1 & 2:
Setting acceptable voltage range
for bypass mode. Set up the range by setting high and
low points. When it shows “LLS” in parameter 2, please
press “Enter” key and it will show “LS” in parameter
1. Now the low point in parameter 2 can be set up by
pressing the “Up” or “Down” key.
LS:
Set the acceptable low voltage for bypass. Setting
range is from 110V to 209V and the default value is
110V.
Pressing “Enter” key to confirm the setting value for
low point. Then, it will show HS in parameter 1. Please
set up high point in parameter 2 by pressing “Up” or
“Down” key.
HS:
Set the acceptable high voltage for bypass. Setting
range is from 231V to 276V and the default value is
264V.
04: Frequency Range for Bypass
Interface
Setting
Parameter 1 & 2:
Setting acceptable frequency range
for bypass mode. Set up the range by setting high and
low points. When it shows “LLS” in parameter 2, please
press “Enter” key and it will show “LS” in parameter
1. Now the low point in parameter 2 can be set by
pressing “Up” or “Down” key.
LS:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46 Hz to 49 Hz. 60
Hz system: Setting range is from 56 Hz to 59 Hz. The
default value is 46 Hz/56 Hz.
Pressing “Enter” key to confirm the setting value for low
point. Then, it will show HS in parameter 1. Set up high
point in parameter 2 by pressing “Up” or “Down” key.
HS:
Set the acceptable high frequency for bypass. 50
Hz: Setting range is from 51 Hz to 54 Hz.
60 Hz: Setting range is from 61 Hz to 64 Hz. The default
value is 54 Hz/64 Hz.