14
A01-00150 Rev B
2) 120V and 240V Output
Figure 2: Output wiring – 120V & 240V
NOTE 1:
Static Switch Output (SSO) must match the output
voltage. Install a jumper between 0-208V or 0-240V.
NOTE 2:
Split phase wiring, load shall be balanced 50 / 50 on each
side of transformer taps.
NOTE 3:
Make sure that the wires are connected tightly to the
terminals.
NOTE 4:
Install the output breaker between the output terminal and
the load. The breaker should be qualified with leakage
current protection if necessary.
Summary of Contents for POWERVAR ABCDEF10.2-22