background image

 

 

 

 

Security Plus II 
User’s Manual

 

Online UPS with Isolation Transformer

 

2kVA / 3kVA / 4kVA / 5.2kVA / 6kVA / 8kVA / 10kVA

 

 

 

 

Summary of Contents for POWERVAR ABCDEF10.2-22

Page 1: ...Security Plus II User s Manual Online UPS with Isolation Transformer 2kVA 3kVA 4kVA 5 2kVA 6kVA 8kVA 10kVA...

Page 2: ...e Batteries 23 5 7 Battery Mode Operation 24 5 8 Test the Batteries 24 5 9 Turn Off the UPS with Utility Power Supply in AC Mode 24 5 10 Turn Off the UPS Without Utility Power Supply in Battery Mode 2...

Page 3: ...h international sales and distribution offices in United Kingdom Germany Canada and Mexico The company s primary products include transformer based power conditioners and uninterruptible power supplie...

Page 4: ...can cause operator injury and or equipment damage Other warning symbols may appear along with the Danger and Caution symbol and are used to specify special hazards These warnings describe areas where...

Page 5: ...to a grounding electrode conductor The UPS is connected to a DC energy source battery The output terminals may be live when the UPS is not connected to an AC supply Operation DANGER Do not disconnect...

Page 6: ...loadequipment please ensure the UPS is connected to a properly grounded electrical supply 2 This UPS has dangerously high voltages on both its inputand output connections Contact with these voltages m...

Page 7: ...t breaker for the branch circuit supplying power to the UPS ensure that the breaker selected is not an ELCB type circuit breaker that detects earth leakage current 10 Please contact the manufacturer o...

Page 8: ...battery terminal and the ground terminal 7 UPS batteries represent a high voltage source and a potential hazard to personal safety Please pay attention to proper safety precautions and use insulated t...

Page 9: ...011 EMI Conducted Emission IEC EN 62040 2 FCC PART15 CLASS A Radiated Emission IEC EN 62040 2 FCC PART15 CLASS A EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level...

Page 10: ...commends the use of the following method to increase the stability of your UPS Before removing the UPS from its shipping pallet remove the shipping brackets from both sides of the UPS Do not discard R...

Page 11: ...O 4 Intelligent pocket 5 Maintenance bypass switch 6 Input circuit breaker 7 Input output terminal block connections 8 Power stage cooling fan 9 Power stage cooling fan 10 Maintenance bypass cover pla...

Page 12: ...mains wire and breakers in the building aresuitable for the rated capacity of the UPS to avoid the hazards of electric shock or fire 2 Switch off mains power before installation 3 Turn off all the co...

Page 13: ...lations in North America For international installations please refer to the local and national electrical codes and standards INPUT CONDUCTOR AWG OUTPUT CONDUCTOR AWG GROUND AWG RATING MIN MAX TORQUE...

Page 14: ...TAP JUMPER 208 208 60 120 10 0 88 0 120 SEE DIAGRAM 60 208 0 240 240 60 120 8 0 88 0 120 60 240 0 NOTE The neutral to ground bond connection must be properly connected for domestic or international co...

Page 15: ...d output voltage Install a jumper between 0 208V or 0 240V NOTE 2 208 is obtained by using the 120 and 88 terminals NOTE 3 Make sure that the wires are connected tightly to the terminals NOTE 4 Instal...

Page 16: ...a jumper between 0 208V or 0 240V NOTE 2 Split phase wiring load shall be balanced 50 50 on each side of transformer taps NOTE 3 Make sure that the wires are connected tightly to the terminals NOTE 4...

Page 17: ...r between 0 208V or 0 240V NOTE 2 There are 2 sets of 120V outputs Each set can carry half of the total UPS capacity NOTE 3 Make sure that the wires are connected tightly to the terminals NOTE 4 Insta...

Page 18: ...11 35 AMP ABCDEF3002 11 45 AMP 208V 240V ABCDEF2002 22 20 AMP 15 AMP ABCDEF3002 22 25 AMP 20 AMP ABCDEF4002 22 35 AMP 25 AMP ABCDEF5202 22 40 AMP 30 AMP ABCDEF6002 22 45 AMP 35 AMP ABCDEF8002 22 60 AM...

Page 19: ...by proper sized AC disconnect device The recommended disconnect device ratings at full rated load are listed below ABCDEF2002 11 20 AMP ABCDEF2002 22 10 AMP ABCDEF3002 11 30 AMP ABCDEF3002 22 15 AMP A...

Page 20: ...urn to last menu in setting menu Test Up Button Battery test Press and hold the button at least 0 5 seconds to test the battery while in AC mode or CVCF mode UP key Press this button to display next s...

Page 21: ...icators LED Indicators There are 4 LEDs on front panel to show the UPS working status LED Mode Bypass Line Battery Fault UPS Startup No Output mode Bypass mode AC mode Battery mode CVCF mode Battery T...

Page 22: ...and fault occurs Indicates the fault codes and the codes are listed in details in section 3 9 Mute Operation Indicates that the UPS alarm is disabled Output Battery voltage information Indicates the o...

Page 23: ...circuit is working Indicates the output is working Battery information Indicates the Battery capacity by 0 25 26 50 51 75 and 76 100 5 3 Audible Alarm Description Buzzer status Muted UPS status Bypass...

Page 24: ...ss and hold the ON button for 0 5 seconds to turn on the UPS and the buzzer will beep once 7 A few seconds later the UPS will enter to AC mode If the utility power is abnormal the UPS will operate in...

Page 25: ...s nominal powercapacity 5 If the overload time is over acceptable time listed in the spec at AC mode the UPS will automatically transfer to Bypass mode After the overload is reduced it will return to...

Page 26: ...e buzzer 3 The backup time may vary with different environment temperatures and load types 4 Battery discharge protection can be enabled or disabledthrough LCD panel control Refer to LCD setting Secti...

Page 27: ...Without Utility Power Supply in Battery Mode 1 Turn off the UPS by pressing the OFF button until the buzzer beeps once or about 0 5 seconds 2 The UPS will cut off power to output and there is no displ...

Page 28: ...roubleshooting table in Section 8 for a list of fault codes 2 If still problem still exists contact AMETEK Powervar Technical Support 5 14 Operation of Changing Charging Current If using extended batt...

Page 29: ...O mode enable disable Y 06 Voltage range for ECO mode Y 07 ECO mode frequency range setting Y 08 Bypass mode setting Y Y 09 Battery backup time setting Y Y Y Y Y Y 10 Reserved Reserved for future 11 R...

Page 30: ...connection Normal UPS shutdown means turning off input breaker in bypass no output mode 01 Output Voltage Interface Setting Parameter 2 Output voltage You may choose the following output voltage in pa...

Page 31: ...ynchronize with the input frequency within 46 54 Hz UPS will transfer to battery mode when input frequency is not within 46 54 Hz 60NC Setting UPS to normal mode not CVCF mode If selected the output f...

Page 32: ...is from 231V to 276V and the default value is 264V 04 Frequency Range for Bypass Interface Setting Parameter 1 2 Setting acceptable frequency range for bypass mode Set up the range by setting high an...

Page 33: ...2 Setting acceptable voltage range for ECO mode Set up the range by setting high and low points When it shows LLS in parameter 2 please press Enter key and it will show LS in parameter 1 Now the low...

Page 34: ...nfirm the setting value for low point Then it will show HS in parameter 1 Set up high point in parameter 2 by pressing Up or Down key HS Set high frequency point for ECO mode 50 Hz Setting range is fr...

Page 35: ...lt value is DIS 10 Reserved Interface Setting Reserved 11 Reserved Interface Setting Reserved 12 Hot Standby Function Enable disable Interface Setting Parameter 2 HS H To Enable or disable Hot standby...

Page 36: ...ng current from 1A to 4A in Parameter 1 Then calibrate the charging current by selecting or in Parameter 2 0 5 You may choose as Add or as Sub to adjust charging current This setting number is the fir...

Page 37: ...stable AC power to output The UPS will also charge the battery at AC mode ECO Mode When the input voltage is within voltage regulation range and ECO mode is enabled UPS will bypass voltage to output...

Page 38: ...ass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two min utes Battery Test While UPS is in AC mode or CVCF mode press the Test key for at least 0 5 seconds Then the UPS...

Page 39: ...ltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 Inverter output short circuited 14 Battery turn on failure 6A None Negative power fault 1A None PFC current fai...

Page 40: ...n 30min Beeping every second 8 2 Warning Code Warning Code Warning Event Warning Code Warning Event 01 Battery unconnected 10 L1 IP fuse broken 07 Over charge 33 Locked in bypass after overload 3 time...

Page 41: ...e external or internal battery is incorrectly connected Check if all batteries are connected well The icon and flash on LCD display and alarm beeps twice every second UPS is on overload Remove excess...

Page 42: ...curred There are two possible results 1 The load is still sup plied but directly from AC power via bypass Contact Technical Support 2 The load is no longer supplied by power Battery backup time is Bat...

Page 43: ...ied out only by qualified maintenance personnel CAUTION Even after the unit is disconnected from the mains components inside the UPS system are still connected to the battery packs which are potential...

Page 44: ...objects before maintenance or repair and only use tools with insulated grips and handles for maintaining or repairing CAUTION When replace the batteries install the same number and same type of batter...

Page 45: ...is limited to AMETEK Powervar depot service See the Limitations of Warranty section below for additional limitations and exclusions 11 2 Limitations This limited warranty does not cover any losses or...

Page 46: ...ry discharge charge cycles that are potentially far more numerous than those for which the battery was designed As a result Products used in such applications will experience substantially reduced bat...

Page 47: ...A01 00150 Rev B 45...

Page 48: ...ation and support on the web at www powervar com A01 00150 Rev A 12 2020 2020 AMETEK Powervar Inc Europe Asia Address Unit 5 Birch Kembrey Park Swindon Wilts SN2 8UU UK P 44 1793 553980 F 44 1793 5353...

Reviews: