Operation 

GUPS 2400A

–107 Operation Manual 

3-5 

3.7

 

Start-Up and Shutdown Sequences 

To run the GUPS 2400A-107 from an AC input, perform the following steps: 

1. 

Turn on the AC input circuit breaker located on the front panel.  

2. 

Wait approximately 10 seconds for completion of the start-up routines. During this 
time, the GUPS performs a self-test to assure proper functionality, and the rectifier 
undergoes a soft-start so that current surges on the AC input are prevented. 

3. 

After  the  start-up  delay,  the  inverter  will  turn  on  (fan  will  be  energized),  but  the 
output will be off. Also, the charger will be on to charge the internal battery. 

4. 

To turn ON the output, press the OUTPUT ON switch. The output relay will close 
and connect the inverter to the load. The inverter will momentarily turn off prior to 
closing of the output relay to prevent switching load current with the relay. 

 

If  the  AC  input  voltage  exceeds  the  allowed  range,  the  unit  will  draw  power from 
the internal battery and continue to run until the battery is depleted. If the AC input 
returns to the allowed range, and low battery shutdown of the inverter has not yet 
occurred, the unit will again draw power from the AC input and also recharge the 
battery with the battery charger. 

5. 

To  turn  OFF  the  output,  press  the  OUTPUT  ON  switch  again;  the  switch  has  a 
alternating  ON/OFF  action.  The  inverter  will  momentarily  turn  off  and  the  output 
relay will open. The inverter will again turn on after the relay is open. The inverter is 
turned  off  while  the  relay  is  opening  to  prevent  switching  load  current  with  the 
relay.  

 

If the AC input voltage exceeds the allowed range while the output is turned off, the 
unit will shut down; the inverter, charger, and all control circuits will be turned off. 

3.8

 

Battery Operation 

To run the GUPS 2400A-107 from battery when an AC input is not present or outside the 
allowed operating range, perform the following: 

1. 

The AC input circuit breaker located on the front panel could be either in the on or 
off positions.  

2. 

To  turn  ON  the  output,  press  the  OUTPUT  ON  switch.  After  a  short  delay,  the 
output relay will close and the inverter will start, supplying power to the load. The 
unit  will  run  until  the  battery  is  depleted.  If  the  AC  input  returns  to  the  allowed 
range, and the AC input breaker is closed, power will be drawn from the AC input 
and the battery charger will recharge the battery.  

 

CAUTION!

 

If the battery module is not inserted when the unit is started, all 
front panel LED’s will indicate RED, and the unit will not operate. 

 

Summary of Contents for GUPS 2400A-107

Page 1: ...Fax 858 458 0267 Email Domestic Sales domorders sd ametek com International Sales intlorders sd ametek com Customer Service service ppd ametek com Web www programmablepower com GLOBAL UNINTERRUPTIBLE...

Page 2: ......

Page 3: ...ly Notice of Copyright Global Uninterruptible Power Supply Operation Manual 2010 AMETEK Programmable Power Inc All rights reserved Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING...

Page 4: ...ii This page intentionally left blank...

Page 5: ...nnel and equipment safety Always ensure that facility AC input power is de energized prior to connecting or disconnecting any cable In normal operation the operator does not have access to hazardous v...

Page 6: ...uctions of AMETEK is opened modified or disassembled in any way without AMETEK s consent or is used in combination with items articles or materials not authorized by AMETEK The Buyer may not assert an...

Page 7: ...Installation 2 2 2 4 Air Intake and Exhaust 2 2 2 5 Input Output Connectors 2 2 2 6 Wire Gauge Selection 2 6 SECTION 3 OPERATION 3 1 3 1 Introduction 3 1 3 2 Control and Indicator Panel 3 1 3 2 1 Ind...

Page 8: ...shooting 4 2 LIST OF FIGURES Figure 2 1 GUPS 2400A 107 Front View 2 3 Figure 2 2 GUPS 2400A 107 Rear View 2 4 Figure 2 3 GUPS 2400A 107 Dimensions Top Side and Front Views 2 5 Figure 3 1 GUPS 2400A 10...

Page 9: ...input and output connections are made at the rear panel Cooling air is drawn in through a filter on the front panel and exhausted out the rear panel Operational and input output power status is indica...

Page 10: ...imum low line voltage 232V minimum high line voltage Battery to AC Crossover 169V maximum low line voltage 232V minimum high line voltage AC Input Voltage Unbalance 7V RMS maximum difference in line v...

Page 11: ...orm a visual inspection of the shipping container prior to accepting the package from the carrier If extensive damage is evident a description of the damage should be noted on the carrier s receipt an...

Page 12: ...take is located on the front panel of the instrument and the exhaust is through the rear panel Care must be taken not to block the air intake and exhaust No special vertical separation is required whe...

Page 13: ...Installation GUPS 2400A 107 Operation Manual 2 3 Figure 2 1 GUPS 2400A 107 Front View...

Page 14: ...Installation 2 4 GUPS 2400A 107 Operation Manual Figure 2 2 GUPS 2400A 107 Rear View...

Page 15: ...Installation GUPS 2400A 107 Operation Manual 2 5 Figure 2 3 GUPS 2400A 107 Dimensions Top Side and Front Views...

Page 16: ...ge and insulation properties are recommended for power source applications Avoid using published commercial utility wiring codes These codes are designed for the internal wiring of homes and buildings...

Page 17: ...e length in feet Vloss Maximum loss in volts permitted within cable SPECIAL CASE Should the Vloss requirement be very loose Ipeak may exceed the maximum amperes Column 2 In this case the correct wire...

Page 18: ...rom any source The differential voltage to other nearby conductors and Safety margins to accommodate degradations due to age mechanical abrasion and insulation migration caused by bending and temperat...

Page 19: ...control panel 3 2 1 Indicators AC INPUT Three green LED s that indicate the presence of line voltage at the AC input The indicators turn on when the line voltage is greater than 90V phase voltage grea...

Page 20: ...normal operating conditions and red when an over temperature shutdown occurs TEST A two color LED that indicates the results of the internal self test The LED blinks while a self test is in progress W...

Page 21: ...dible alarm will again be sounded 3 5 Control Signals The Data Alarm Port provides an interface to remote alarms or a host computer The control signals provide annunciation of the mode of operation co...

Page 22: ...Connectors The GUPS 2400A 107 has cylindrical metal shell connectors with bayonet coupling for all input output connections of power and signal All connectors are located on the rear panel Pin assign...

Page 23: ...power from the AC input and also recharge the battery with the battery charger 5 To turn OFF the output press the OUTPUT ON switch again the switch has a alternating ON OFF action The inverter will m...

Page 24: ...the effective surface area of the plates which reduces the available backup time Allowing the batteries to self discharge for too long may result in recharging problems or in battery degradation Stori...

Page 25: ...PS F Signal Ground Table 3 3 RS 232 Connector Pin Out 3 9 2 Software Interface The RS 232 interface firmware in the GUPS 2400A 107 has the following communication features Two sets of remote terminal...

Page 26: ...S 232 text data mode commands have been developed for a user interface utilizing a dumb terminal interface The text data mode commands provide formatted responses that include both the name of data pa...

Page 27: ...3 Output voltage readback calibration in Vout rdbk dvm 114 5 floating point format 3 9 4 3 Display Status Registers and A D Values Enter a command s lowercase S character to display the two 16 bit sta...

Page 28: ...age in hexadecimal Battery Bad Voltage Battery Shutdown Voltage Output Voltage Measurement scale factor in floating point Output Voltage Measurement 3 9 5 2 Provide Status Words and Hexadecimal A D Va...

Page 29: ...d 1 Alarm Sensed 2 Alarm Silence 0 Alarm Silence Not Enabled 1 Alarm Silence Enabled 3 Charger Status 0 Charger Not On 1 Charger On 4 Current Overload 0 Normal Operation 1 Current Overload 5 Battery S...

Page 30: ...ects the condition of the charger enabled logic of the GUPS 2400A 107 A binary value of 0 indicates that the charger is not on while a binary value of 1 indicates that the charger is on Current Overlo...

Page 31: ...ectifier slow start mode Equalization Charge Status Word 1 Bit 11 The Equalization Charge status bit indicates that the unit is in equalization charge enable mode A binary value of 0 indicates that th...

Page 32: ...tery 1 Running on AC Line 6 150 Overload Sense 0 Normal Operation 1 150 Overload Detected 7 Float Timer Time out 0 Not Float Charging 1 Float Timer Time out 8 Wait to equalize 0 No Equalization Pendin...

Page 33: ...m shutdown mode Status Word 2 Bit 4 Reserved Running on AC Line Status Word 2 Bit 5 The Running on Line status bit indicates that the unit is operating on the AC input A binary value of 0 indicates th...

Page 34: ...ified input range while a binary value of 1 is not within the specified input range Delayed Event Flag Status Word 2 Bit 12 The Delayed Event Flag status bit indicates the status of pending delayed ev...

Page 35: ...l number in any correspondence concerning this instrument DO NOT return the unit to the factory without prior authorization 4 3 Spare and Repair Parts When ordering spare parts or repair parts specify...

Page 36: ...indicator is illuminated red The filter is clogged Clean the filter if required The BATTERY indicator is illuminated red 1 Low battery voltage or 2 a defective battery 1 Recharge the battery or 2 repl...

Reviews: