SECTION 1 – INSTALLATION 1-1
Section 1 - Installation
Unpacking the Instrument
After the consistometer is unpacked, the operating equipment and spare parts on the packing
list should be checked to affirm that all have been received and none are damaged.
File an insurance claim with your freight carrier if damage has occurred during shipment.
Utility Requirements
Your unit will require dry, oil free compressed shop air (not instrument quality) of 75 to 125
psi (618-963 kPa), and a water supply of 20-80 psi (138-552 kPa). The unit is capable of
operating in ambient temperatures from 40°F to 120°F.
Tools/Equipment Required
A standard maintenance or mechanics tool set is adequate for the installation, operation, and
maintenance of the instrument. No special tools are required.
This unit is supplied with an installation kit, which includes the necessary hardware for the
water, air, and electrical hook-ups. The water and air hose may be cut to length and the
appropriate barbed fittings inserted into the hose and clamped into place.
Caution: The laboratory electrical power wiring must be capable of a 15-ampere
load and comply with local electrical codes. The instrument must be
securely connected to an appropriate earth ground. The ground wire
must have a larger diameter than that of the supply voltage conductors.
Safety Requirements
Warning:
Read before attempting operation of instrument
.
This instrument is capable of extremely high temperatures and
pressures and must always be operated with CAUTION. The
instrument is designed for operator safety. To ensure of that safety it is
essential to follow the instructions outlined below.
The following safety procedures are advisable:
•
Locate the instrument in a low traffic area.
•
Post signs where the instrument is being operated to warn other personnel.
•
Read and understand the instructions and caution notes before attempting operation.
•
Always close the pressure valve before disconnecting the quick-connect fitting to
prevent water from being forced out and spraying directly on operator.
Summary of Contents for CHANDLER ENGINEERING Twin UCA 4262
Page 6: ...P 2 PREFACE This page is intentionally left blank...
Page 10: ...1 4 SECTION 1 INSTALLATION This page is intentionally left blank...
Page 20: ...2 10 SECTION 2 OPERATING INSTRUCTIONS This page is intentionally left blank...
Page 24: ...3 4 SECTION 3 MAINTENANCE AND SERVICING This page is intentionally left blank...
Page 28: ...4 4 SECTION 4 TROUBLESHOOTING GUIDE This page is intentionally left blank...
Page 32: ......
Page 33: ...CHANDLER ENGINEERING...
Page 34: ......
Page 37: ......
Page 38: ...CHANDLER ENGINEERING...
Page 39: ......
Page 40: ...CHANDLER ENGINEERING...