193111
-
055
MAINTENANCE
November 17, 2020 6
-
2
1. Locate charging rate adjustment label inside charger
cabinet (same as Table 6
-
1). The factory set
charging rate is indicated on this label by circles
around terminal numbers to which YELLOW jumper
and ORANGE lead were connected.
2. Locate YELLOW jumper and ORANGE lead on each
transformer terminal block present in your unit (one
transformer for single
-
phase, three for three
-
phase).
3. Mark present location of YELLOW jumper and
ORANGE lead on charger rate adjustment label and
on Table 6
-
1 if different from that marked by factory.
4. Reconnect YELLOW jumper and ORANGE lead to
the terminals giving the desired change of charging
rate, as shown in Table 6
-
1.
CAUTION: Do not change connections
more than one step before observing
effect on charging rate. On fully charged
battery (approx. 1.270 to 1.290 specific
gravity), rate should not exceed 22% of
“
MAX AMPS
”
on charger nameplate.
On fully discharged battery (approx.
1.140 specific gravity), rate should not
exceed 110% of
“
MAX AMPS
”.
On three
-
phase chargers, all
transformer terminal blocks must
be identically connected.
Fuse Replacement
The silicon diodes in this charger are protected by a
“
fast
-
clearing
”
type fuse.
CAUTION: The use of any other type
fuse besides the
“
fast
-
clearing
”
type
may cause damage to silicon diodes.
Silicon Diode Testing
WARNING: ELECTRICAL SHOCK
HAZARD —
Before checking electrical
components, turn OFF and remove
fuses of disconnect switch (supplying
AC power to charger), disconnect
battery, and check for voltage on
capacitors. Discharge through insulated
screwdriver if there is any reading.
1. Disconnect one diode lead to isolate diode on each
transformer from electrical circuitry.
2. Use a good quality ohmmeter (preferably one having
a mid
-
scale value of approximately 50 ohms) to
measure resistance values.
3. Zero ohmmeter on R x 1 scale.
4. Record indicated resistance while placing either
ohmmeter lead on threaded end of diode and other
ohmmeter lead on diode lead.
5. Reverse ohmmeter leads on diode and record
indicated resistance.
Table 6
-
1 Charging Rate Adjustment Table
Summary of Contents for AC1000 Control
Page 2: ......
Page 4: ......
Page 6: ...November 17 2020 193111 055 TABLE OF CONTENTS This page intentionally left blank...
Page 8: ...193111 055 INTRODUCTION 1 2 November 17 2020 This page intentionally left blank...
Page 12: ...193111 055 DESCRIPTION OF EQUIPMENT 3 2 November 17 2020 This page intentionally left blank...
Page 19: ...193111 055 OPERATION November 17 2020 5 4 Figure 5 1...
Page 30: ...193111 055 PARTS LIST 8 1 November 17 2020 Figure 8 1 A Case...
Page 32: ...8 3 November 17 2020 193111 055 PARTS LIST Figure 8 2 B Case...
Page 34: ...193111 055 PARTS LIST 8 5 November 17 2020 Figure 8 3 C Case...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ...SCHEMATIC LEGEND NOTES...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......