
5
6/07
Control / Motor Starter Package (Ref: Drawing CPMS)
a) Factory installed motor starter package includes a service disconnect, motor starter,
and transformers pre-wired to the PLC. These systems require a single point
electrical connection to the service disconnect. Line service must be rated to pump
motor requirements.
Standard systems are factory set for 460V, 3ph service. Optional power supply
factory wired as ordered.
b) Wire the pump motor from the motor starter with seal tight (provided).
NOTE: If optional backwash booster pump is used and a second motor starter is
factory supplied, refer (drawing CPMS) for proper connection points.
NOTE: Do not operate pump(s) dry. Damage to pump seal and shaft may occur.
Control Package (Ref: Drawing CPIO)
a) The control package is pre-wired at factory
b) Two sets of terminals, located in the control panel, are provided for pump control.
Reference drawing CPMS for terminals.
c) Power for motorized valves is supplied from control panel terminal strip.
(See Section 1.4 for instructions).
d) Fuse holders connected to output terminals 9 & 11 are intentionally left with no
fuses.
Fuses should not be installed or removed unless specific instructions are
received from AmeriWater 800.535.5585.
Output #9 will be fused, (if applicable), at start up to convert from city water to
system water backwash.
e) Output #11 will be fused, (if applicable) to change timed backwash from 24 hours to
7 days.
Timed backwash should be changed only for systems operating on a
closed loop and only after consultation with AmeriWater.
NOTE: Changes to these options without instructions from AmeriWater may void
the filter warranty.
Summary of Contents for CW130 Series
Page 1: ...Rev 6 07 High Efficiency Sand Filters CW130 Series ...
Page 21: ...18 6 07 2 4 Startup Data Sheet ...
Page 22: ...19 6 07 2 5 Filter Log Sheet ...
Page 31: ...28 6 07 ...
Page 36: ...33 CP Control Panel Enclosure with Labeled Components ...
Page 37: ...34 ...
Page 38: ......
Page 39: ...36 TBIO Input output strips on Terminal block labeled to indicate connection points ...
Page 40: ...37 CPIO Input output strips on PLC labeled to indicate connection points ...
Page 42: ......
Page 44: ...41 6 System Component Cut Sheets ...
Page 45: ...Model MCC INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS INSTRUCTION MANUAL IM060R04 ...