![AmeriWater 00HRO64800 Operation & Maintenance Manual Download Page 5](http://html1.mh-extra.com/html/ameriwater/00hro64800/00hro64800_operation-and-maintenance-manual_2930532005.webp)
4
2.2
FEED WATER REQUIREMENTS
The quality of the feed water to the reverse osmosis unit must meet the following
requirements:
- Hardness, max ........................................................................ . 0.5grains
- Free Chlorine, max ................................................................... 0.01 ppm
- Turbidity, max ................................................................................ 1 NTU
- Silt Density Index (SDI), max ................................................................. 5
Hardness
:
If the feed water exceeds 0.5 grains, use a softener to reduce the
hardness.
Free Chlorine
: If the feed water exceeds the free chlorine limit, remove the chlorine
with a carbon filter. Chlorine is destructive to RO membranes.
Particulates
: The feed water should always be processed through an inlet filter of no
greater than 5 microns to remove any particles or silt that may
potentially clog the membranes.