background image

22

SAFETY EQUIPMENT 

For protection against excessive pressures in the collector 
loop a pressure relief valve is integrated into the solar 
pump station.  Drain tubing must be installed in the valve 
outlet so that any discharge will exit only within 6 inches 
above, or at any distance below the structural fl oor.  Be 
certain that no contact is made with any live electrical part.  
The discharge opening must not be blocked or reduced in 
size under any circumstances.  Excessive length, over 15 
feet, or use of more than two elbows can cause restriction 
and reduce the discharge capacity of the valve.
Do not connect tubing directly to discharge drain unless a 
6” air gap is provided.  To prevent bodily injury, hazard to 
life, or damage to property, the relief valve must be allowed 
to discharge fl uid in quantities should circumstances 
demand.  If the discharge pipe is not connected to a drain 
or other suitable means, the fl uid may cause property 
damage.

ATTENTION: 

TO PREVENT DAMAGE TO PROPERTY, 

THE LOCATION OF INSTALLATION MUST BE DRY, 
LOAD-CARRYING AND FROST-PROOF TO PREVENT 
MATERIAL DAMAGE TO THE INSTALLATION.

When following the ‘PUMP STATION INSTALLATION’ see 
Figure 21. 

WALL MOUNTING THE SOLAR PUMP STATION 

1.  Choose the position to install the solar pump station 

next to the storage tank .

2.  Mark the location of the hanging holes on the wall (15” 

apart vertically)

CAUTION

DUE TO THE WEIGHT OF THE SOLEX PUMP STATION THE
HANGAR ANCHORS MUST BE ATTACHED TO A STRUCTURAL
SUPPORT LIKE A STUD

3.  Pre-drill holes and insert the enclosed 4.5” hanging 

screws so that about 1” of each screw still stick out..

4.  Remove the front cover of the solar station and hang 

the station onto the screws then tighten the screws.

5.  Mount the solar safety group to the connection above 

the return ball valve.

CONNECTION FOR

EXPANSION TANK

CONNECTION FOR

DISCHARGE LINE

DRAIN
VALVE

CONNECTION SET

WITH EXPANSION TANK

Figure 22.

6.  Connect a discharge line to the pressure relief valve 

in the solar circuit

7.  Connect the stainless steel corrugated hose to the 

safety group. Do not forget to insert the seal.

8.  Choose the position for the expansion tank bracket  

on the wall beside the solar pump station.  Fasten the 
bracket to the wall with the enclosed hardware (masonry 
or drywall).

9.  Unscrew the tank connector to separate the two halves.  

The top half should be pushed onto the mounting 
bracket and the lock ring tightened.  The bottom half 
should be attached to the ¾” threads on the expansion 
tank.

NOTE:

  The tank connector allows you to isolate the 

expansion tank from the solar circuit. See Figure 23. When 
the nut is unscrewed the valves in each half of the tank 
connector are automatically closed tightly by the integrated 
springs.  Each side remains closed until the two halves are 
screwed back together and the valves are forced open.  Do 
not forget to insert the seal.

The expansion tank should not be connected to the system 
until it has been flushed and charged.

 

FLOW

CLOSED

Figure 23.

10. Check and set the pressure of the air bladder in the 

expansion tank to 25 psi.  If the pressure is higher bleed 
pressure out until it is correct.  If the pressure is too low 
add air by use of a compressor or bicycle pump until 
the pressure is correct.

11. Plumb the solar pump station to the storage tank 

and to the collector:  The tank connections should 
use ¾” copper pipe and can be connected using 
the threaded adaptors provided.  The collector 
connections should use ½” copper pipe and can be 
connected with the compression fittings provided. 
 The total piping run in the solar loop should not exceed 
200 equivalent feet.  Failure to limit the line length may 
cause poor system performance and lead to premature 
pump failure.

12.  Install a discharge pipe to the pump station relief valve 

that must terminate a maximum of six inches above a 
floor drain or external to the building.

PUMP STATION INSTALLATION

Summary of Contents for SRCC OG-100

Page 1: ...TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOUARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER Instruction Manual RESIDENTIAL SOLAR WAT...

Page 2: ...he water heater as they relate to the installation of electric water heaters The qualified installer must have a thorough understanding of the water heater Instruction Manual Service Agency A service...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...erated to keep the water hot throughout the rest of the day and night However on days when the sky is cloudy or when large quantities of hot water are being used we recommend leaving the backup heater...

Page 5: ...R COLLECTOR INSTALLATION 13 Collector Location 13 General Considerations 13 Collector Orientation 13 14 Spanner Mounting 15 17 Attaching Collector to Mounting Brackets 18 Collector Piping 19 Collector...

Page 6: ...G THE SOLAR WATER HEATER SECTION INSTALL THERMAL EXPANSION TANK OR DEVICE IF WATER HEATER IS INSTALLED IN A CLOSED WATER SYSTEM 6 Maximum Air Gap Piped To An Adequate Drain At Least 2 Greater Than The...

Page 7: ...PRESSURE RELIEF VALVE For protection against excessive pressures and temperatures in this water heater install temperature pressure protective equipment required by local codes but not less than a com...

Page 8: ...e a choice of where to install the solar water heater these ideas may help you decide 1 Put the solar water heater indoors as close as possible to where you use the most hot water This water heater is...

Page 9: ...ater heater is installed in a closed water system such as one having a back flow preventer check valve or water meter with check valve in the cold water supply line means shall be provided to control...

Page 10: ...t voltage can cause problems which can result in DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE If you have any questions or doubts consult your electric company If wiring from the fuse box or circuit...

Page 11: ...rclockwise to decrease the temperature 4 Fold the insulation back in place and replace the access panel 5 Turn ON the power supply A non adjustable high temperature limit control operates before steam...

Page 12: ...al anode rod may be available if water odor or discoloration occurs NOTE This rod may reduce but not eliminate water odor problems The water supply system may require special filtration equipment from...

Page 13: ...rated assemblies Ensure the mounting surface is solid and able to with stand in excess of 330lbs 150kg of pull force that may be encountered during high winds Consult a structural engineer if in doub...

Page 14: ...204 244 295 9 2 12 69 78 90 104 123 139 157 180 205 14 3 12 63 69 78 88 101 111 123 136 149 18 4 12 59 64 71 78 88 96 105 115 123 23 5 12 54 59 64 70 77 83 89 96 102 27 6 12 52 55 59 64 70 75 80 86 9...

Page 15: ...en determined that the spanner mounting method is the most suitable for this application Consult with your installer if other mounting means are required for your installation 1 After locating the mou...

Page 16: ...HORIZONTAL MOUNTING RAFTER MOUNTING BRACKET RAFTER Figure 14 Figure 15 B B C C A DRILL POINTS CLEARANCE HOLE for 5 16 BOLT RAFTER D BASED ON 16 CENTER RAFTERS B B C C A DRILL POINTS CLEARANCE HOLE for...

Page 17: ...SCREWS FENDER WASHER LOCK WASHER NUT ROOF RAFTER SPACER BLOCK Figure 16 Table 4 IF MOUNTING WITH AN OPTIONAL TILT MOUNT KIT FOR OPTIMAL COLLECTOR ANGLE REFER TO ITS INSTRUCTION SHEET FOR THE APPLICAB...

Page 18: ...unting brackets prior to raising the collectors The collector can then be set on the lower mounting brack ets while the top clips are fastened over the lip on the collector frame 4 After the solar col...

Page 19: ...spacing of collectors as attachment of piping is easiest with properly aligned collectors The connection between the collector panels is made with copper unions or couplings To aid in installation th...

Page 20: ...ration Ensure that all roof penetrations required to plumb and mount the solar collector are properly flashed and sealed in accordance with standard roofing practices The return and supply lines shoul...

Page 21: ...a com parable level of knowledge specialist The following must be observed during installation and start up Relevant local and national codes Accident prevention regulations of the professional associ...

Page 22: ...HARGE LINE DRAIN VALVE CONNECTION SET WITH EXPANSION TANK Figure 22 6 Connect a discharge line to the pressure relief valve in the solar circuit 7 Connect the stainless steel corrugated hose to the sa...

Page 23: ...ed to pump to the tank return threaded fitting Figure 25 FUNCTION Check valves The solar station is equipped with check valves in the supply and the return ball valve J Q For filling venting and flush...

Page 24: ...priate drain 12 Turn the supply ball valve b to 90 horizontal so that the valve is closed 13 Turn on the supply water and open the fill valve d then leave running for 15 minutes to flush debris out of...

Page 25: ...st the solar pump speed using the pump speed selector on the side of the pump f Set the speed to the lowest level possible to achieve the recommended system flow rate See Table 5 NUMBER OF COLLECTORS...

Page 26: ...r loop pump upper primary and one for the water loop pump lower secondary Relay 1 primary pump 18 Line power R1 17 Neutral N 13 Ground Relay 2 secondary pump 16 Line power R2 15 Neutral N 14 Ground Th...

Page 27: ...d button down for 2 seconds and the system setting screens can then be shown If an adjustable value is shown on the display is indicated To change the set value press the Set button 3 so that flashes...

Page 28: ...quickly blinking if there is a sensor error Operation control lamp indication Constantly green system operation normal Red green blinking initialization phase manual operation Red blinking sensor err...

Page 29: ...ssioning menu press button 3 The controller is now ready for operation with typical settings to suit the system layout The settings made in the commissioning menu can be changed later on in the corres...

Page 30: ...e value for heat quantity will be set to 0 In order to finish the reset procedure the set button 3 must be pressed in order to confirm In order to interrupt the reset procedure no button should be pre...

Page 31: ...ep If the temperature decreases the secondary pump will decrease by 1 step followed by the primary pump n1MN n2MN Minimum pump speed Adjustment range 30 to 100 Recommended setting 30 A relative minimu...

Page 32: ...available when OCF is active CFRF Antifreeze temperature off Adjustment range 40 to 50 F Recommended setting 41 F Channel only available when OCF is active O TC Tube collector function Adjustment OFF...

Page 33: ...MAN1 MAN2 as follows Operating mode OFF relay off flashing AUTO relay in automatic operation ON relay on flashing n1 2 LO minimum speed Note Always adjust the operating mode back to Auto when the cont...

Page 34: ...valve in solar pump station Inspect valve and repair or replace Cold water supply dip tube Missing or defective Replace dip tube Collectors Absorber coating degradation Replace collector Collector pan...

Page 35: ...er fuse Repair or replace Flow rated too high or too low Adjust flow rate Faulty pump Listen for irregular noises in pump operation Feel collector feed and return line for temperature difference Ensur...

Page 36: ...tial set too low Reset off differential according to recommendation Controller set to on position Set system operation to Auto Pump operated but no fluid flows from collectors Air Scoop System air loc...

Page 37: ...pressure drops unexpectedly contact your installation contractor immediately to diagnose the problem and recharge the system SOLAR PANEL CLARITY If you live in a dusty climate once a month wash off d...

Page 38: ...Loop Dip Tube w Nipple 9006790005 12 Plastisert Nipple 9003976015 13 T P Valve 9000728015 14 Drain Valve 9003906015 SOLEX DWHX PUMP STATION SERVICE PARTS 15 Temperature Gauge Supply Red 9007789005 16...

Page 39: ...l Protection Exposure Limits Component List Type Value Propylene glycol Personal Protection Eye Face Protection Use safety glasses Skin Protection Wear clean body covering clothing Hand protection Use...

Page 40: ...40...

Reviews: