Water Supply Systems, ANSI Z21.22 - current edition. This 
valve must be marked with the maximum set pressure not 
to exceed the marked maximum working pressure of the 
water heater. Install the valve into an opening provided and 
marked for this purpose in the water heater, and orient it or 
provide tubing so that any discharge from the valve exits 
only within 6 inches above, or at any distance below, the 
structural 

fl

 oor, and does not contact any live electrical part. 

The discharge opening must not be blocked or reduced in 
size under any circumstance. 
IMPORTANT:  Only a new temperature and pressure relief 

valve should be used with your water heater. Do not use an 

old or existing valve as it may be damaged or not adequate 

for the working pressure of the new water heater. Do not 

place any valve between the relief valve and the tank.

The Temperature & Pressure Relief Valve:   

• 

Shall not be in contact with any electrical part.

• 

Shall be connected to an adequate discharge line.

• 

Shall not be rated higher than  the working pressure  
shown on the data plate of the water heater.

The Discharge Line:

• 

Shall not be smaller than the pipe size of the relief  
valve or have any reducing coupling installed in the 
discharge line.

• 

Shall not be capped, blocked, plugged or contain    
any valve between the relief valve and the end of the 
discharge line.

• 

Shall terminate a maximum of 6 inches above a floor 
drain or external to the building.  In cold climates, it is 
recommended that the discharge pipe be terminated at 
an adequate drain inside the building.

• 

Shall be of material listed for hot water distribution.

• 

Shall be installed to allow complete drainage of both 
the valve and discharge line.

Solar Installation

If this water heater is used as a solar storage heater or 
as a backup for the solar system, the inlet water supply 
temperatures to the water heater tank may be in excess of 
120°F.  A mixing valve or other temperature limiting valve 
must be installed in the inlet water supply line to limit the 
supply temperature to 120°F.

NOTE: Solar water heating systems can often supply water 
with temperatures exceeding 180°F and may result in water 
heater malfunction.

Water Heater Location

  Centrally located with the water piping system.

  Located indoors and in a vertical position. Protected  

from freezing temperatures.

  Provisions made to protect the area from water    

damage.  A suitable drain pan installed and piped to an 
adequate drain.

  Sufficient room to service the water heater.

Water System Piping

  Temperature and pressure relief valve properly    

installed with a discharge line run to an open drain  
and protected from freezing.

  All piping properly installed and free of leaks.

  Heater completely filled with water. (See Figure 2)

  Closed system pressure buildup precautions    

installed.

  Mixing valve (when applicable) installed per 

manufacturer’s instructions (see “Water Temperature 
Regulation” section).

Electrical Connections

  Wiring and connections comply with all applicable  

codes.

  Water heater and electrical supply are properly    

grounded.

  Proper overload fuse or circuit breaker protection  

installed.

INSTALLATION
CHECKLIST

Summary of Contents for Residentian Electric Water Heater

Page 1: ...ber 4 Date of installation 5 Place of Purchase Water Heater Safety 2 Installing Your Water Heater 3 8 Unpacking Instructions 3 Location Requirements 4 Electrical Requirements 5 Water System Piping 6 I...

Page 2: ...heater that has not been used for a long period of time 2 weeks or more Hydrogen gas is extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water fau...

Page 3: ...manual If you lack the necessary skills required to properly install this water heater or you have difficulty following the directions you should not proceed but have a qualified person perform the i...

Page 4: ...area or call 1 800 999 9515 and request instructions 2 1 2 Maximum Pipe to adequate drain At least 2 greater than the diameter of the water heater IMPORTANT The water heater should be located in an a...

Page 5: ...e electrical supply to the water heater A standard 1 2 inch opening has been made in the junction box for conduit connections 5 Connect ground wire to green ground screw in the junction box of the wat...

Page 6: ...lable Contact a licensed plumber or the local plumbing authority for more information 4 If installing the water heater in a closed water system install an expansion tank in the cold water line as spec...

Page 7: ...the installation of a thermal expansion tank IMPORTANT Do not plug or remove the temperature and pressure relief valve Closed System Thermal Expansion For protection against excessive pressures and t...

Page 8: ...nded that the discharge pipe be terminated at an adequate drain inside the building Shall be of material listed for hot water distribution Shall be installed to allow complete drainage of both the val...

Page 9: ...the high limit control switch continues to shut off the water heater contact a qualified person for service Water Temperature Regulation Water temperature over 125 F can cause severe burns instantly o...

Page 10: ...d person 1 Disconnect the electric power 2 Remove the access cover s and fold up the insulation from the thermostat s Do not remove the plastic cover 3 Using a screwdriver to adjust the thermostat poi...

Page 11: ...ngth are visible If the anode rod shows signs of either or both it should be replaced NOTE Whether reinstalling or replacing the anode rod check for any leaks and immediately correct if found In repla...

Page 12: ...r s Fold up the insulation from the heater element s Remove the plastic thermostat cover from the thermostat s making sure to disengage the attachment point from the thermostat 4 Disconnect the electr...

Page 13: ...for source of trouble and correct 3 Replace thermostat or element INSUFFICIENT HOT WATER 1 Non Functioning thermostats 2 Non Functioning lower element 3 Improper calibration 4 Thermostats set too low...

Page 14: ...14 REPAIR PART ILLUSTRATION 1 1 2 3 5 6 7 2 6 4 5 8 7 10 9 8 11 12 14 13 ALTERNATE T P LOCATION 7 17 18 8 13 6 16 2 3 5 6 5 2 4 15 14 9 11 TABLE TOP MODEL...

Page 15: ...TUBE COMBINATION 20 FLANGE REPAIR PARTS Repair parts may be ordered through your plumber local distributor home improvement center or by calling 1 800 999 9515 When ordering repair parts always give...

Page 16: ...AL SERVICE GROUND GROUND SCREW 1 2 1 2 FUSED DISCONNECT OR CIRCUIT BREAKER LOWER ELEMENT BLACK BLACK BLUE BLUE UPPER ELEMENT YELLOW YELLOW L1 L2 FUSED DISCONNECT OR CIRCUIT BREAKER RED UPPER THERMOSTA...

Reviews: