
The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor
should use only industry-recognized procedures.
Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM
nominally.
Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver air along the perimerter of the space. If
they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Air grilles must be properly sized
to carry air back to the blower.If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living
space.
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size
external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat
operation.
TMM5A0B24M21SAA
TMM5A0B30M21SAA
TMM5A0B36M31SAA
Airflow Performance(Standard CFM)
--- Shaded boxes represent airflow outside the required 300-450 cfm/ton.
NOTES:
9
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
TAP5
1014
961
925
877
836
777
742
685
637
TAP4-Factory
830
776
737
677
636
569
510
478
426
TAP3
814
773
724
680
626
556
509
464
426
*TAP2
683
575
475
391
324
284
227
171
/
TAP1
655
540
388
227
147
/
/
/
/
TAP5
1252
1214
1182
1144
1113
1072
1019
957
883
TAP4
1149
1117
1077
1042
1007
973
938
893
841
TAP3
1125
1094
1054
1023
983
951
909
864
827
TAP2-Factory
1036
1003
962
929
891
857
812
766
719
TAP1
959
912
879
838
808
752
695
651
593
TAP5
1252
1214
1182
1144
1113
1072
1019
957
883
TAP4-Factory
1149
1117
1077
1042
1007
973
938
893
841
TAP3
1125
1094
1054
1023
983
951
909
864
827
TAP2
1036
1003
962
929
891
857
812
766
719
TAP1
959
912
879
838
808
752
695
651
593
MODEL SIZE
EXTERNAL STATIC PRESSURE (INWC.)
BLOWER SPEEDS
1. Airflow based upon dry coil at 230V with no electric heat
ˈ
no filter. For 24, 30and36 sizes, airflow at 208V is approximately the same as
230V because the mult-tap ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds in which the motor operates.
2. Airflow is equivalent for front or bottom return configurations.
3. SCFM is nearly the same with cooling performance airflow, the gap is in the 1 to 2%.
Section 6. Performance and Electrical Data
7)0575$16)250(5
)/)86(/,1.
)0)$102725
&$3
)$1 &$3$&,725
*1'
*5281'
),(/' 32:(5 :,5,1*
*1'
9ᨺ
&20
9
9
7)05
FM
%51&
%/8
<**1'
:+,7(
<(/1
%/./
NOTES:
1: Use Copper Wire (75
Min) Only Between Disconnect Swicth And Unit .
2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same
Or Equivalent Type Wire.
4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.
ć
7)0575$16)250(5
)/)86(/,1.
)0)$102725
&$3
)$1 &$3$&,725
*1'
*5281'
),(/' 32:(5 :,5,1*
*1'
9ᨺ
&20
9
9
7)05
FM
%51&
%/8
<**1'
:+,7(
<(/1
%/./
NOTES:
1: Use Copper Wire (75
Min) Only Between Disconnect Swicth And Unit .
2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same
Or Equivalent Type Wire.
4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.
ć
7)0575$16)250(5
)/)86(/,1.
)0)$102725
*1'
&20
9
9
7)05
NOTES:
1: Use Copper Wire (75
Min) Only Between Disconnect Swicth And Unit .
2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same
Or Equivalent Type Wire.
4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Green Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
ć
FM
<**1'
1
&
/
* When
TMM5A0B24M21SAA
use 18KBTUH outdoor unit ,select SCFM between 450 and 675.
Summary of Contents for TMM5A0B24M21SAA
Page 11: ......