American Standard TMM5A0B24M21SAA Installer'S Manual Download Page 9

The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor 

should use only industry-recognized procedures.

Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM 

nominally.

Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.

Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver air along the perimerter of the space. If 

they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Air grilles must be properly sized 

to carry air back to the blower.If they are too small, they also cause noise.

The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living 

space.

Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size 

external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat 

operation. 

TMM5A0B24M21SAA

TMM5A0B30M21SAA

TMM5A0B36M31SAA

Airflow Performance(Standard CFM)

--- Shaded boxes represent airflow outside the required 300-450 cfm/ton.

NOTES:

9

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

TAP5

1014

961

925

877

836

777

742

685

637

TAP4-Factory

830

776

737

677

636

569

510

478

426

TAP3

814

773

724

680

626

556

509

464

426

*TAP2

683

575

475

391

324

284

227

171

/

TAP1

655

540

388

227

147

/

/

/

/

TAP5

1252

1214

1182

1144

1113

1072

1019

957

883

TAP4

1149

1117

1077

1042

1007

973

938

893

841

TAP3

1125

1094

1054

1023

983

951

909

864

827

TAP2-Factory

1036

1003

962

929

891

857

812

766

719

TAP1

959

912

879

838

808

752

695

651

593

TAP5

1252

1214

1182

1144

1113

1072

1019

957

883

TAP4-Factory

1149

1117

1077

1042

1007

973

938

893

841

TAP3

1125

1094

1054

1023

983

951

909

864

827

TAP2

1036

1003

962

929

891

857

812

766

719

TAP1

959

912

879

838

808

752

695

651

593

MODEL SIZE

EXTERNAL STATIC  PRESSURE (INWC.)

BLOWER SPEEDS

1. Airflow based upon dry coil at 230V with no electric heat

ˈ

no filter. For 24, 30and36 sizes, airflow at 208V is approximately the same as 

230V because the mult-tap ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds in which the motor operates.

2. Airflow is equivalent for front or bottom return configurations.

3. SCFM is nearly the same with cooling performance airflow, the gap is in the 1 to 2%.

Section 6. Performance and Electrical Data

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

7)0575$16)250(5

)/)86(/,1.

)0)$102725

*1'

&20

9

9

7)05

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Green Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.

ć

FM

<**1'

1

&

/

* When 

TMM5A0B24M21SAA

 

use 18KBTUH outdoor unit ,select SCFM between 450 and 675.

Summary of Contents for TMM5A0B24M21SAA

Page 1: ...ed for upflow applications only 208 230 VAC OPERATION MULTI SPEED DIRECT DRIVE BLOWER CONSTANT TORQUE ECM MOTOR WITH FAN OFF TIME DELAY PROGRAMMING FACTORY INSTALLED R 410A THERMAL EXPANSION VALVE 1 2...

Page 2: ...ause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servi...

Page 3: ...bracket on the wall by using 3 wood screws not provided Make sure the bracket is level in order to provided proper drainage from the unit Note Do not attach the wall mounting bracket into unsupported...

Page 4: ...ACCA Manual 0 Design for Residential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Wa...

Page 5: ...will energize the fan on a demand for heat or cool Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other...

Page 6: ...uspension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4...

Page 7: ...onnect R To R G To G Etc See Outdoor Instruction For Details 5 To Change Speed Tap Move Blue Wire Desird Terminal 6 See Airflow Tables For Tap Usage 7 Factory Wires May Be Present DO NOT USE 2 Fig 4 2...

Page 8: ...0 1 02725 3 1 3 725 1 5281 32 5 5 1 1 1 COMPONENT ARRANGEMENT NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION 9 9...

Page 9: ...ing and electric heat operation TMM5A0B24M21SAA TMM5A0B30M21SAA TMM5A0B36M31SAA Airflow Performance Standard CFM Shaded boxes represent airflow outside the required 300 450 cfm ton NOTES 9 0 0 1 0 2 0...

Page 10: ...male pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten...

Page 11: ......

Page 12: ...ighway Tyler TX 75707 www trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specificati...

Reviews: