American Standard TMM5A0B24M21SAA Installer'S Manual Download Page 3

3

Carefully unpack the unit and inspect the contents for damage. If 

any damage is found at the time of delivery, proper notification and 

claims should be made with the carrier.

Check the rating plate to assure model number and voltage, plus 

any kits match with what you ordered. The manufacturer should be 

notified within 5 days of any discrepancy or parts shortage.

The small air handler should be centrally located and may be 

installed in a closet, alcove, utility room, basement. Minimum 

clearances must be met.

The air handler comes standard with two different options for mount-

ing, wall mount or frame mount. Both mounting options require the 

unit to be level from side to side and from front to back in order to 

allow condensate to properly drain from the unit. Failure to do this will 

result in condensate to leak out from the unit potentially causing 

structural damage to the surrounding support structures, dry wall, 

carpet, etc. around the unit. Also, both mounting structures require 

the ability to accommodate a minimum of 150 lb load. Failure to do 

this will cause damage to the support structure and potentially 

damage the unit.  

The air handler comes standard with a wall mounting bracket and air 

handler mounting bracket. Reference Figure 3-1 for more detail.

1. Remove lower wall  mounting bracket from the back of the unit by 

removing one screw which attaches the bracket to the air handler. 

Note: Discard the screw after you have removed the wall mounting 

bracket.

2. Install bracket on the wall by using 3 wood screws (not provided). 

Make sure the bracket is level in order to provided proper drainage 

from the unit. Note: Do not attach the wall mounting bracket into 

unsupported dry wall. Make sure that the wood screws are going into 

a structure that can suppport a minimum of 150 lb load.

3. Lift the air handler above the wall mounting bracket and attached 

the unit to the installed bracket. Reference Figure 3-1.

4. Install the additional bottom plate for extra support for this type 

mounting (see figure 3-1).  

Note: The additional plate is shipped in the bottom of the shipping 

carton. 

3.2.1 WALL MOUNT

 Fig. 3-2 FRAME MOUNT

WALL STRUCTURE

SUPPORTING
2˝X4˝ STRUCTURE

WOOD SCREWS

SUPPORTING
2˝X4˝ STRUCTURE

STUD ATTACHMANT
HOLES

The air handler comes with 8 clearance holes 4 on each side. These 

holes are used to mount the air handler inside of a frame structure 

(see Figure 3-2). When mounting in this fashion, make sure that the 

wood screws are mounted from within the air handler and not outside 

of the unit. Installing the screws from the outside of the unit, And 

notice don’t damage to the coil.

For ensure the proper installation for frame mount, Select the enough 

solid and level site. Ensure enough space required for installation and 

maintenance(See Figure. 3-3)

3.2.2 FRAME MOUNT

PROVIDED WALL
MOUNT BRACKET

WALLMOUNT BRACKET

WOOD SCREWS

SUPPORTING 2˝X4˝
STRUCTURE

WALL STRUTURE

WOOD SCREWS

WOOD SCREWS

PROVIDED WALL

MOUNT BRACKET

NOTE: MOUNTING WALL AND SUPPORTING 
STRUCTURE MUST BE ABLE TO SUPPORT A 
MINIMUM OF 150 LBS.

PROVIDED AIR HANDLER
MOUNTING BRACKET

 Fig. 3-1 WALL MOUNT

WOOD SCREWS

31.5˝

Section 3. Installation Instructions

3.1 Unpacking

3.2 Location

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

7)0575$16)250(5

)/)86(/,1.

)0)$102725

*1'

&20

9

9

7)05

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Green Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.

ć

FM

<**1'

1

&

/

Summary of Contents for TMM5A0B24M21SAA

Page 1: ...ed for upflow applications only 208 230 VAC OPERATION MULTI SPEED DIRECT DRIVE BLOWER CONSTANT TORQUE ECM MOTOR WITH FAN OFF TIME DELAY PROGRAMMING FACTORY INSTALLED R 410A THERMAL EXPANSION VALVE 1 2...

Page 2: ...ause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servi...

Page 3: ...bracket on the wall by using 3 wood screws not provided Make sure the bracket is level in order to provided proper drainage from the unit Note Do not attach the wall mounting bracket into unsupported...

Page 4: ...ACCA Manual 0 Design for Residential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Wa...

Page 5: ...will energize the fan on a demand for heat or cool Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other...

Page 6: ...uspension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4...

Page 7: ...onnect R To R G To G Etc See Outdoor Instruction For Details 5 To Change Speed Tap Move Blue Wire Desird Terminal 6 See Airflow Tables For Tap Usage 7 Factory Wires May Be Present DO NOT USE 2 Fig 4 2...

Page 8: ...0 1 02725 3 1 3 725 1 5281 32 5 5 1 1 1 COMPONENT ARRANGEMENT NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION 9 9...

Page 9: ...ing and electric heat operation TMM5A0B24M21SAA TMM5A0B30M21SAA TMM5A0B36M31SAA Airflow Performance Standard CFM Shaded boxes represent airflow outside the required 300 450 cfm ton NOTES 9 0 0 1 0 2 0...

Page 10: ...male pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten...

Page 11: ......

Page 12: ...ighway Tyler TX 75707 www trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specificati...

Reviews: