background image

5

3.8.4 MOTOR SPEED

•    Low voltage control connections are made to low voltage pigtails 

extending from top of air handler (see Figure 1). Connections for 

control wiring are made with wire nuts. Control wiring knockouts (7/8˝) 

are also provided on the right and left side of the unit for side connec-

tion.

•    See wiring diagrams attached to indoor and outdoor sections to be 

connected. 

•    Make sure, after installation, separation of control wiring and power 

wiring has been maintained.

3.8.3 GROUNDING

The unit must be permanently grounded. Failure to do so can 

result in electrical shock causing personal injury or death.    

•  Grounding may be accomplished by grounding metal conduit when 

installed in accordance with electrical codes to the unit cabinet or by 

attaching ground wire(s) to ground lug(s) provided in the unit wiring 

compartment. 

•  Ground lug(s) are located close to wire entrance on left side of unit 

(up-flow). Lug(s) may be moved to marked locations near wire 

entrance on right side of unit (upflow). If alternate location is more 

convenient. 

•  Use of multiple supply circuits require grounding of each circuit to 

lug(s) provided in unit. 

•   If required, install a branch circuit disconnect of adequate size,  

located within sight of, and readily accessible to the unit.  

•   

IMPORTANT

: After the Electric Heater is installed, units are 

equipped with one 60 amp. circuit breaker. These breaker(s) protect 

the internal wiring in the event of a short circuit and serve as a 

disconnect. Circuit breakers installed within the unit do not provide 

over-current protection of the supply wiring and therefore may be 

sized larger than the branch circuit protection. 

•   Supply circuit power wiring must be 75°C minimum copper 

conductors only. See Electrical Data in this section for ampacity, 

wire size and circuit protector require ment. Supply circuit protective 

devices may be either fuses or “HACR” type circuit breakers.   

•   Power wiring may be connected to either the right or left side

 

Two 7/8” dia. concentric knockouts are provided for connection of 

power wiring to unit. 

•   Power wiring is connected to the power terminal block in unit 

electric cabinet.

3.8.2 CONTROL WIRING

IMPORTANT: Class 2 low voltage control wiring should not be run in 

conduit with main power wiring and must be separated from power 

wiring, unless class 1 wire of proper voltage rating is used. 

Select a thermostat that is commonly used with HP or AC single 

stage heating/cooling with electric heat. The thermostat will energize 

the fan on a demand for heat or cool.

Install the thermostat on an inside wall, away from drafts, lights or 

other heat sources in a location that has sufficient air circulation from 

other rooms being controlled by the thermostat. The thermostat 

should be mounted 4 to 5 feet above the floor.

•   Low voltage control wiring should be 18 Awg. color-coded. For 

lengths longer than 100 ft., 16 Awg. wire should be used. 

ECM Motor Speed Taps(Model number 24

ǃ

30

ǃ

36)

Tap

Delay ---off

Time (s)

24

30

36

Tap 1

30

---

---

---

Tap 2

90

---

Default

---

Tap 3

30

---

---

---

Tap 4

90

Default

---

Default

Tap 5

30

---

---

---

Field wiring must comply with the National Electric Code (C.E.C. in 

Canada) and any applicable local ordinance.  

Disconnect all power to unit before installing or servicing.  More 

than one disconnect switch may be required to de-energize the  

equipment. Hazardous voltage can cause severe personal injury 

or death.      

3.8.1 POWER WIRING

It is important that proper electrical power is available for connection 

to the unit model being installed. See the unit nameplate, wiring 

diagram and electrical data in the installation instructions.

WARNING

WARNING

3.5 Refrigerant Piping

Refrigerant pipe connections are located on the top of the unit. 

Refrigerant piping external to the unit shall be sized in accordance 

with the instructions of the outdoor equipment. When units are 

recessed mounted in the wall, make certain that piping connections 

are pressure tested prior to the wall being closed. While brazing, be 

sure to protect the cabinet and grommets from heat damage.

3.6 Metering Device

All units are shipped and installed with an internally-checked, 

non-bleed TXV designed for air conditioning or heat pump 

operation. Pressures equalize after shut down. Some outdoor 

models may require a start assist kit. See outdoor unit for more 

information.

3.7 Blower

3.8 Wiring

3.10 Thermostat

To protect the coil, blower and other internal parts from excessive dirt 

and dust an air filter must be installed before air enters the evaporator 

coil. A filter must be installed. Consult the filter manufacturer for 

proper sizing and maximum velocity requirements.

3.9 Air Filter

This unit is supplied with a multi-speed motor with a direct drive 

blower wheel which can obtain various air flows. The unit is shipped 

with factory set cooling and heating speed taps. Airflow performance 

tables are available for additional speed taps. Disconnect all power 

to the unit before making any adjustments to the motor speed taps. 

Be sure to check the air flow and the temperature drop across the 

evaporator coil to ensure sufficient air flow.

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

Filter Sizes

Model

Filter Size In. (mm)

20x20x1 (508x508x25)

TMM5A0B24,30,36

7)0575$16)250(5

)/)86(/,1.

)0)$102725

*1'

&20

9

9

7)05

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Green Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.

ć

FM

<**1'

1

&

/

Summary of Contents for TMM5A0B24M21SAA

Page 1: ...ed for upflow applications only 208 230 VAC OPERATION MULTI SPEED DIRECT DRIVE BLOWER CONSTANT TORQUE ECM MOTOR WITH FAN OFF TIME DELAY PROGRAMMING FACTORY INSTALLED R 410A THERMAL EXPANSION VALVE 1 2...

Page 2: ...ause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servi...

Page 3: ...bracket on the wall by using 3 wood screws not provided Make sure the bracket is level in order to provided proper drainage from the unit Note Do not attach the wall mounting bracket into unsupported...

Page 4: ...ACCA Manual 0 Design for Residential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Wa...

Page 5: ...will energize the fan on a demand for heat or cool Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other...

Page 6: ...uspension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4...

Page 7: ...onnect R To R G To G Etc See Outdoor Instruction For Details 5 To Change Speed Tap Move Blue Wire Desird Terminal 6 See Airflow Tables For Tap Usage 7 Factory Wires May Be Present DO NOT USE 2 Fig 4 2...

Page 8: ...0 1 02725 3 1 3 725 1 5281 32 5 5 1 1 1 COMPONENT ARRANGEMENT NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION 9 9...

Page 9: ...ing and electric heat operation TMM5A0B24M21SAA TMM5A0B30M21SAA TMM5A0B36M31SAA Airflow Performance Standard CFM Shaded boxes represent airflow outside the required 300 450 cfm ton NOTES 9 0 0 1 0 2 0...

Page 10: ...male pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten...

Page 11: ......

Page 12: ...ighway Tyler TX 75707 www trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specificati...

Reviews: