4A-V8-SF-1G-EN
29
Alert
Code
Alert
Group
Display
Assembly
Text
Sub-
alar-
m
A/TZONE
850/950
State action on
occurrence
State action on
clearance
Alert
Description
Possible Cause
181
Initializa-
tion Error
INIT ERR
10
Err 181.10
Emergency Shutdown.
Control will clear the
fault and retry every 5
minutes.
Resume normal
operation. Control
will clear fault when
condition no longer
exists.
Internal fault with
micro and cannot
initialize
Cycle power. If error
continues call for tech
support, record
failure mode for
warranty claim before
replacing Drive.
ADC
Supply
Range
exceeded
ADC SUP EX
11
“Wait”
Emergency shutdown.
Control will clear the
fault and retry every 5
minutes.
Resume normal
operation. Control
will clear fault when
condition no longer
exists.
Internal
communication
fault
If error continues call
for tech support,
record failure mode
for warranty claim
before replacing
Drive.
ADC
Inverter
tempera-
ture range
exceeded
ADC INV T EX
12
“Wait”
Emergency shutdown.
Control will clear the
fault and retry every 5
minutes.
Resume normal
operation. Control
will clear fault when
condition no longer
exists.
Internal fault with
temperature
sensor.
If error continues call
for tech support,
record failure mode
for warranty claim
before replacing
Drive.
ADC
Rectifier
tempera-
ture range
exceeded
ADC REC T EX
13
“Wait”
Emergency shutdown.
Control will clear the
fault and retry every 5
minutes.
Resume normal
operation. Control
will clear fault when
condition no longer
exists.
Internal fault with
temperature
sensor.
If error continues call
for tech support,
record failure mode
for warranty claim
before replacing
Drive.
ADC
reference
range
exceeded
ADC REF EX
14
“Wait”
Emergency shutdown.
Control will clear the
fault and retry every 5
minutes.
Resume normal
operation. Control
will clear fault when
condition no longer
exists.
Internal fault with
micro
If error continues call
for tech support,
record failure mode
for warranty claim
before replacing
Drive.
ADC
current
range
error
ADC CUR EX
15
“Wait”
Emergency shutdown.
Control will clear the
fault and retry every 5
minutes.
Resume normal
operation. Control
will clear fault when
condition no longer
exists.
Internal fault with
current sensor
If error continues call
for tech support,
record failure mode
for warranty claim
before replacing
Drive.
182
Startup
Algorithm
Fault
STRT SOFT LO
0
“Wait”
Can’t execute start-up
algorithm Can’t start
system for at least 5
minutes. Proceed to
Normal shutdown.
Send “Wait” to
thermostat, send Alert
to CDA home screen
menu and history
Resume normal
operation
Compressor has a
failed startup
attempt.
Drive is limiting
compressor speed
due to Inverter high
temperature or high
current.
STRT HARD LO
1
Err 182.01
Shutdown. Can’t start
system without
Service being called.
Send error to
thermostat and alert
menu in CDA
Can be cleared only
on power cycle.
After power cycle,
the compressor
shall resume
normal operation.
5 startup soft
lockouts occurred
without a
successful start.
Drive is limiting
compressor speed
due to Inverter high
temperature or high
current.
183
Shutdown
Algorithm
Fault
SHTDWN CO
0
“Wait”
Control is reset
internally. Retry after 5
minutes.
Resume normal
operation after
compressor comes
to a halt.
Compressor does
not come to a
complete stop
even after the
defined time and
continues to run
even after control
is released.
Loss of internal
communication. If
error continues after
system resets, call for
tech support.
184
Protection
Algorithm
Fault
IDCF CO
0
“Wait”
Shutdown. Soft
lockout. Send “Wait” to
thermostat, send Alert
to CDA home screen
menu and history
Resume normal
operation after
suction pressure is
greater than
107psig (35°F
saturated)and
compressor cutout
time has elapsed.
Cut Out Time = 5
minutes
(In cooling mode)
Indoor coil freeze
protection is
active. Suction
pressure sensor
is <78psig (20°F
saturated) for 20
minutes.
Restricted airflow, low
charge, low ambient
operation, restriction
in refrigerant system
or metering device.
Summary of Contents for 4A6V8024A1000B
Page 12: ...12 4A V8 SF 1G EN Wiring D157619P04...
Page 41: ...4A V8 SF 1G EN 41 Communication Loss Yes Yes No Yes No No Yes No...
Page 42: ...42 4A V8 SF 1G EN Breaker Trip Procedure...
Page 43: ...4A V8 SF 1G EN 43 Start Compressor...
Page 44: ...44 4A V8 SF 1G EN Compressor Verification Parameters...
Page 45: ...4A V8 SF 1G EN 45 Run Drive Diagnostic Test e t...
Page 46: ...46 4A V8 SF 1G EN Compressor Verification Short...
Page 47: ...4A V8 SF 1G EN 47 Compressor Verification Open No Yes...
Page 48: ...48 4A V8 SF 1G EN Inverter Temperature e e...
Page 52: ...52 4A V8 SF 1G EN T Te ec ch hn ni ic ci ia an n M Mo on ni it to or r M Me en nu u...
Page 57: ...4A V8 SF 1G EN 57 T Te ec ch hn ni ic ci ia an n C Co on nt tr ro ol l M Me en nu u...
Page 58: ...58 4A V8 SF 1G EN TECH CONTROL Charge Check Charge Modes...
Page 59: ...4A V8 SF 1G EN 59 Pressure Curves Figure 20 4A6V8024A...
Page 60: ...60 4A V8 SF 1G EN Figure 21 4A6V8036A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 61: ...4A V8 SF 1G EN 61 Figure 22 4A6V8037A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 62: ...62 4A V8 SF 1G EN Figure 23 4A6V8048A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 63: ...4A V8 SF 1G EN 63 Figure 24 4A6V8049A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 64: ...64 4A V8 SF 1G EN Figure 25 4A6V8060A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 65: ...4A V8 SF 1G EN 65 Figure 26 4A7V8024A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 66: ...66 4A V8 SF 1G EN Figure 27 4A7V8036A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 68: ...68 4A V8 SF 1G EN Figure 29 4A7V8048A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 69: ...4A V8 SF 1G EN 69 Figure 30 4A7V8060A P Pr re es ss su ur re e C Cu ur rv ve es s...
Page 73: ...4A V8 SF 1G EN 73 N No ot te es s...
Page 74: ...74 4A V8 SF 1G EN N No ot te es s...