American Flame AFVK-SP Valve Kits

REV. 10-8-19 Page 5

Fig. 10

 Basic installation layout centering the grate and components inside the firebox.

Optional Valve Box Location

Valve Box Location

2” 

Min.

Burner Pan

Basket Grate

TOP VIEW

Pilot Assembly

2” 

Min.

FI

RE

PL

AC

SI

D

W

AL

L

FIR

EP

LA

CE

 SID

E W

AL

L

INSTALLATION: VALVE KIT WITH NEW LOG SET:

1.  Make sure gas is completely turned OFF to the fireplace. Make sure you have a certified and approved shut-off within 

6-feet of the fireplace, or per the local code requirements.

2.  Follow the instructions supplied with the log set to locate the burner pan. Using the fittings, orifice and gas supply line 

that came with the log set. Connect the line to the inlet gas supply.

3.  Locate a position on the back of the burner pan to mount the pilot assembly about 4” from the right or left side of the 

burner pan (See Fig. 9).

4.  Mount pilot assembly to burner pan as shown in (Fig. 9). 

Note

: This pilot bracket clips on the top edge of the burner 

pan and holds the pilot at a 45° position onto the pan, an attachment screw is recommended. Bend pilot tubing from 

pilot assembly until the bottom of the pilot bracket is resting against the pan. This will hold the pilot at the 45º position. 

(Use caution when bending pilot tubing not to kink the tubing and when locating the igniter and flame sensor wires not 

to locate the wires and the tubing in or over the burner pan.) Locate the valve kit in the right or left front corner of the 

firebox as far forward as possible (See Fig. 10)

5.  Bend inlet gas supply line and connect to the 3/8” flare fitting to 3/8” inlet connector on the valve kit (Use caution not 

to kink the aluminum inlet line when bending to fit to the valve).

6.  Bend 12” stainless flex line and connect to valve outlet. Connect other end to 3/8” flare fitting on burner pan.         

Caution:

 Ensure no gas line, inlet or outlet, are placed over top of the burner pan.

7.  Turn ON gas supply and check all connections for leaks using soapy water solution.

8.  Follow valve lighting instructions. After pilot is operating check pilot fittings for leaks.

9.  Follow the instructions supplied with the log set to install ember material, basket grate and logs.

10. Install Damper clamp (supplied with valve kit) which allows damper to remain slightly open to allow the pilot gases to 

vent).  

 

NOTE: For any PROPANE installations see conversion kit instructions.

Summary of Contents for AFVK-SP

Page 1: ...tice Please leave these instructions for the consumer Retain for future reference Models AFVK SP AFVK SP HL AFVK SP MHL Electronic Safety Pilot System for Vented Gas Logs IF YOU CANNOT READ OR UNDERST...

Page 2: ...Set Page 5 Reference Section Wiring Diagram Page 6 Battery Pack Preparation Page 7 Gas Conversion Page 8 Operation of System Page 9 10 Troubleshooting Page11 Replacement Parts Page 12 Warranty Page12...

Page 3: ...Solenoid ON Remote Switch Continious Pilot On Off Switch AFVK SP HL Side View inside box Fig 4 AFVK SP HL Hi Lo Solenoid SP1001HL trans mitter damper clamp flex line adapter fitting includes battery p...

Page 4: ...et gas supply 9 Bend 12 stainless flex line and connect it to the valve outlet then connect other end to 3 8 flare fitting to existing burner pan Caution Ensure no gas line inlet or outlet are placed...

Page 5: ...ilot tubing from pilot assembly until the bottom of the pilot bracket is resting against the pan This will hold the pilot at the 45 position Use caution when bending pilot tubing not to kink the tubin...

Page 6: ...itor Wires Fig 11 Module Identification IN PILOT OUT PILOT ADJ MAIN MAIN 2 Pin Connector Green White Wires PILOT 2 Pin Connector Orange White Wires Pilot Ass y Fig 12 Gas Valve Identification OUT PILO...

Page 7: ...r on the battery pack comes pre installed to the 4 pin female connector located on the battery pack and module Note Figs 14 16 for reference 2 The AFVK SP HL AFVK SP MHL also has 2 18 wires Red Black...

Page 8: ...ROPANE it will be necessary to use the LPK 18 or LPK 24 1 The AFVK SP AFVK SP HL or AFVK SP MHL electronic control valves are convertible from Natural gas to Propane gas by simply turning the stem kno...

Page 9: ...OFF OFF REMOTE ON OFF CONTINUOUS PILOT Fig 20 Valve box switches Fig 21 Remote control Continuous button 2 REMOTE CONTROL FEATURE The AFVK SP AFVK SP HL or AFVK SP MHL comes with a remote control tra...

Page 10: ...ilot is lit 2 seconds the main burner will light 3 Adjust the main flame from HI to LO with the manual HI LO knob on front of valve kit Note Move the OFF REMOTE slide switch on the face plate of valve...

Page 11: ...e continuous pilot switch to the OFF position MAIN BURNER DOES NOT COME ON WHEN THE MANUAL ROCKER SWITCH OR REMOTE CONTROL IS TURNED ON 1 Confirm that the pilot sparks and lights 2 Check the 2 pin pla...

Page 12: ...tinuous Pilot Off On AUX OUT PILOT ADJ IN MAIN PILOT 10 11 LIMITED WARRANTY American Flame warrants the AFVK SP AFVK SP HL or AFVK SP MHL Valve Kit for 12 months from the date of purchase or installat...

Reviews: