113247 - 3
www.amdry.com
21
Electrical Information _________________
Electrical Requirements
All electrical connections must be made by a properly licensed
and competent electrician. This is to ensure that the electrical
installation is adequate and conforms to local and state
regulations or codes. In the absence of such codes, all
electrical connections, materials, and workmanship must
conform to the applicable requirements of the National
Electrical Code ANSI/NFPA NO. 70-LATEST EDITION or in
Canada, the Canadian Electrical Codes Parts 1 & 2 CSA
C22.1-1990 or LATEST EDITION.
Important
Failure to comply with these codes or ordinances,
and/or the requirements stipulated in this manual
can result in personal injury or component failure.
Note
Component failure due to improper installation will
void the warranty.
Each dryer should be connected to an independently protected
branch circuit. The dryer must be connected with copper
wire only. Do not use aluminum wire, which could cause a
fire hazard. The copper conductor wire/cable must be of proper
ampacity and insulation in accordance with electric codes
for making all service connections.
Note
The use of aluminum wire will void the warranty.
An individual ground circuit must be provided to
each dryer, do not daisy chain.
Component failure due to improper voltage application will
void the warranty.
The manufacturer reserves the right to make changes in
specifications at any time without notice or obligation.
Important
A separate protected circuit must be provided to
each dryer.
The dryer must be connected to the electric supply shown
on the data label. In the case of 208 VAC or 240 VAC, the
supply voltage must match the electric service
specifications of the data label exactly.
The wire size must be properly sized to handle the related
current.
Warning
208 VAC and 240 VAC are not the same. Any
damage done to dryer components due to
improper voltage connections will automatically void the
warranty.
Electrical Service Specifications
Important
Figures shown are for reversing models only. For
non-reversing models contact the factory.
ADSH-75 Steam Models Only
Not available at time of printing. Contact the factory.
ADSH-120 Steam Models Only
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
3ø
3
14.5
—
20
240
3ø
3
14.6
—
20
230
3ø
3
—
17.4
25
380
3ø
3
8.5
—
15
380-400
3ø
4*
—
8.7
15
416
3ø
4*
—
9.0
15
440
3ø
3
8.7
—
15
460/480
3ø
3
7.8
—
15
575
3ø
3
5.8
—
15
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When
ordering, specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
3ø
3
28.3
—
50
240
3ø
3
26.7
—
45
230
3ø
3
—
31.9
50
380
3ø
3
16.2
—
25
380/400
3ø
4*
—
16.1
25
416
3ø
4*
—
16.0
25
440
3ø
3
14.4
—
20
460/480
3ø
3
13.9
—
20
575
3ø
3
11.4
—
20
!
!
!
!
!
!
* Customer must contact factory to special order 3-wire system.
8/15/07
* Customer must contact factory to special order 3-wire system.
8/15/07
ADSH-170 Steam Models Only