D. ELECTRICAL REQUIREMENTS
It is your responsibility to have
ALL
electrical connections made by a properly licensed and competent electrician
to assure that the electrical installation is adequate and conforms to local and state regulations or codes. In the
absence of such codes,
ALL
electrical connections, materials, and workmanship
must conform
to the applicable
requirements of the National Electrical Code ANSI/NFPA NO. 70-LATEST EDITION or in Canada, the Canadian
Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.
IMPORTANT:
Failure to comply with these codes or ordinances, and/or the requirements
stipulated in this manual can result in personal injury or component failure.
NOTE:
Component failure due to improper installation will VOID THE WARRANTY.
It is required that a separate circuit servicing each basket (tumbler) be provided. The dryer
must be
connected
with copper wire only.
DO NOT use aluminum wire, which could cause a fire hazard
.
NOTE:
The use of aluminum wire will VOID THE WARRANTY.
1. Electrical Service Specifications
IMPORTANT: THE DRYER
MUST BE
CONNECTED TO THE ELECTRIC SUPPLY
SHOWN ON THE DATA LABEL THAT IS AFFIXED TO THE LEFT
SIDE OF THE MAIN ELECTRICAL CABINET LOCATED IN THE
RIGHT HAND ELECTRICAL ENCLOSURE.
GAS
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC
ARE NOT THE SAME. When ordering,
specify
exact voltage
.
When fuses are used they
must be
dual element, time delay, current
limiting, class RK1 or RK5
ONLY
. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY
. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers
must be
3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
3ø
3 / 4
118.1
—
150
230
3ø
3
108.7
—
150
230
3ø
3
—
—
—
380
3ø
3 / 4
—
66.8
90
400
3ø
3 / 4
—
67.4
90
416
3ø
3 / 4
—
65.4
90
460
3ø
3
58.9
—
90
480
3ø
3
59.3
—
90