8

American Dryer Corp.

113576 - 1

Multiple Dryer Venting – Through Roof or Rear Wall (5x 90° Turns)

Electrical Information (50Hz) ___

Electric installation must be performed by qualified
personnel in accordance with national and local
safety regulations.

The dryer must be electrically earthed (grounded) in accordance
with national and local codes.

Individual earth circuit must be provided to each dryer.

Failure to properly earth the dryer will void the warranty.

An external means of power removal (disconnect device) must
be provided.

Each dryer should be connected to a properly sized, and
independently protected, branch circuit.

The electric supply must match exactly what is specified on
the dryer’s rating plate (data badge).

Electrical Connections

The electrical input connections are made into the rear of the
dryer (refer to the Technical Specifications page).

A strain relief must be used where wires enter the dryer.

Gas and Steam Heated Dryers

Single-Phase Connection

Summary of Contents for AD-35i

Page 1: ...76 1 American Dryer Corporation 88 Currant Road Fall River MA 02720 4781 USA Telephone 1 508 678 9000 Fax 1 508 678 9447 e mail techsupport amdry com www adclaundry com To avoid errors and damage to the dryer please read these instructions carefully before attempting to install or operate ...

Page 2: ...erosene oil paint or wax Items that have been spotted or soaked with vegetable or cooking oil constitute a fire hazard and should not be dried Do not dry mop heads Contaminations from wax or flammable solvents are a fire hazard Do not store or use gasoline or other flammable liquids or vapors in the vicinity of this appliance Aqualified technician must be called if any high limit thermostat trips ...

Page 3: ...113576 1 www adclaundry com 3 This Page Is Intentionally Left Blank ...

Page 4: ... 22 9 24 9 Heat Rate Gas kW 20 5 36 6 39 6 Heat Rate Steam Normal Load Bhp 2 7 3 6 Steam Consumption kg hr 47 6 63 5 Electric Oven Size kW 6 7 13 5 18 5 20 4 22 0 18 5 20 4 22 0 Airborne Sound Level dB A 63 64 64 Tumbler Drive Motor kW 0 75 0 75 0 75 Blower Fan Motor kW 0 37 0 56 0 56 Net Weight Approximate kg 250 300 318 Shipping Weight Approximate kg 265 330 327 Cabinet Width A cm 81 0 87 6 99 1...

Page 5: ...113576 1 www adclaundry com 5 ...

Page 6: ... 50i 91 cm AD 80i 102 cm G 2 5 cm To allow control door to open H 2 5 cm I 1 5 mm J 1 5 mm Fresh Make Up Air Supply Requirements The dryer draws in air heats it passes it through the tumbler and exhausts it outside Adequate ventilation has to be provided to avoid the back flow of gases into the room from appliances burning fuels including open fires Insufficient fresh air supply could diminish dry...

Page 7: ...45 in the direction of airflow The main duct diameter should increase before each individual duct is added Multiple Dryer Venting Through End Wall 3x 90 Turns AD 35i AD 50i AD 80i A m 15 80 12 10 B mm 152 203 203 203 Multiple Dryer Venting AD 35i AD 50i AD 80i A mm 152 203 203 B mm 810 876 991 Multiple Dryer Venting Through an End Wall C mm 203 254 254 D mm 254 356 356 E mm 305 406 406 F mm 356 45...

Page 8: ...d to each dryer Failure to properly earth the dryer will void the warranty An external means of power removal disconnect device must be provided Each dryer should be connected to a properly sized and independently protected branch circuit The electric supply must match exactly what is specified on the dryer s rating plate data badge Electrical Connections The electrical input connections are made ...

Page 9: ... 21 32 416V 3 13 5 22 32 AD 50i AD 80i Oven kW Amps 220V 1 18 5 89 0 125 230V 1 20 4 93 6 125 240V 1 22 0 96 6 125 220V 3 18 5 53 4 80 230V 3 20 4 56 1 80 240V 3 22 0 57 8 80 380V 3 18 5 34 7 50 400V 3 20 4 36 1 50 416V 3 22 0 37 2 50 NOTES ______________________________________________________ _____________________________________________________________ __________________________________________...

Page 10: ... top of the dryer for this purpose The length and design of the restraint should be suitable to prevent strain on the gas line if the dryer is moved If the dryer is to be moved then the following steps must be taken Disconnect electrical power to the dryer Close all external gas supply shutoff valves Disconnect the gas supply line Remove the restraint from the dryer CE Approved Gas Types 2nd Famil...

Page 11: ...Consult factory for elevations over 610m for correct burner injector size s 7 Instructions on how to convert the gas valve is included with the gas valve conversion kit see chart 8 Reverse step 4 to install the gas valve B with manifold D assembly 9 Open shutoff valve in the dryer s gas supply line 10 Test all connections for leaks 11 Connect gas valve wires 12 Continue electric power 13 Provide p...

Page 12: ...supply connection into the main supply line must be made with a minimum 25 cm riser This will prevent any condensate from draining towards the dryer The steam supply line to the dryer must include a 30 cm riser along with a drip trap and check valve This will prevent any condensate from entering the steam coil Flexible hoses or couplings must be used The dryer vibrates slightly when operating whic...

Page 13: ... 50i AD 80i 1 Steam Coil 2 Vacuum Breaker 3 Solenoid Valve 4 Flexible Hose or Coupling 5 Riser 6 Strainer 7 Manual Shutoff Valve 8 Drop 9 Dirt Leg 10 Drip Trap 11 Check Valve 12 Inverted Bucket Steam Trap 13 Return Main 14 Supply Main ...

Page 14: ... with water and mild detergent solution non flammable Alternatively tumble a load of old garments that are wetted with water and mild detergent solution non flammable Preoperational Test A performance check is needed after the dryer is fully installed and before the dryer is ready for use Start the dryer refer to the Operating Instructions below Gas Dryers Check for flame ignition may need more th...

Page 15: ...s from the factory you can FAX your order to ADC at 1 508 678 9447 or telephone our Parts Department at 1 508 678 9000 Please be prepared to provide the dryer model number serial number description of the part and the part number if known This dryer is equipped with two manually resettable high limit thermostats The burner high limit is located in the top center of the dryer behind the control doo...

Page 16: ...orted LOW VOLTAGE FAULT Volt dropped below the operating value EE PROM FAULT Error in memory location Fault correction Enter the program mode by pressing the UP and STOP keys Press 4 and ENTER keys in password FAA Press UP ARROW Press enter to confirm reset of EE PROM Inputs Red L E D s All indications are with L E D lit ESTOP Indicates E STOP has been pressed GAS_V Indicates the gas valve is open...

Page 17: ...g credit coin mode remaining time free mode MED Temps Exhaust left S A F E right Axial middle Axial dryer LO Tumbler RPM S A F E TEST Switch to program mode Press and hold the Pause key until prompted to press MED to open the water L C D Operating Messages When Display Reads Out of Order Pressing LO displays one of the causes listed below MODEL FAULT Wrong model selected at PL01 3rd position SAIL ...

Page 18: ... shipments will be refused You will be notified if your warranty claim cannot be processed due to insufficient or missing information We must receive this information within 30 days otherwise the claim will be rejected and the part will be discarded For your convenience log the following information Date of Purchase ________________________________ Model Number __________________________________ R...

Reviews: