15
MULTIPLE DRYER (Common) VENTING
H
ORIZONTAL
V
ENTING
If it is not feasible to provide separate exhaust ducts for each dryer, ducts for individual dryers may be channeled
into a common main duct. Each dryer is provided with a back draft damper. The individual ducts should enter the
bottom or side of the main duct at an angle not more than 45° in the direction of the airflow. No more than four
(4) dryers
should be
connected to one (1) main common duct run.
The main common duct may be any shape so long as the minimum cross-sectional area is provided. The main
duct should be tapered with the diameter increasing before each individual 10-inch duct is added (refer to
Illus.
C
and Illus. D
).
Illus. C
Horizontal venting
must not
exceed 20 feet - this calculation compensates for the use of a maximum of only
one (1) elbow which is the outside outlet protection.
NOTE
: Distance between dryer single ducts being connected to the main common duct
must be
a
minimum of 31-3/8" (dryer width).
Duct work
should be
laid out in such a manner where allowances are made at rear area of the
dryer for removal of rear service panels or guards.