Assembled Moves (continued)
Blend Move (continued)
1) You do not have to preset the position or home the machine before you can use a Blend Move.
Because the Blend Move is based on Relative Moves, it can be run from any location.
2) The Blend Move is stored in the internal memory of the SMD17K and can be run multiple
times once it is written to the unit. The Blend Move data stays in memory until power is
removed, the unit is sent new Configuration Data, or a new Blend or Dwell Move is written to
the unit. As described in
Saving an Assembled Move in Flash
on page 36, it is also possible
to save a Blend Move to flash memory. This move is restored on power up and can be run as
soon as you configure the SMD17K and enter Command Mode.
3) There are two control bits used to specify which direction the Blend Move is run in. This
gives you the ability to run the Blend Move in either direction.
Controlled Stop Conditions
The move completes without error.
You issue a Hold Move command through the Network Output Data. When this occurs, the SMD17K
decelerates the move at the deceleration rate of the present segment to the Starting Speed and ends the
move. Note that your final position will most likely not be the one you commanded. A Blend Move that
is brought to a controlled stop with the Hold Move command cannot be restarted. The use of the Hold
Move command is explained in the
Immediate Stop Conditions
You issue an Immediate Stop command through the Network Output Data.
A positive transition on an input configured as an E-Stop Input.
A CW or CWW Limit Switch is reached. If the limit that is reached is the same as the direction of
travel, for example, hitting the CW limit while running a CW move, a
Reset Errors
command must be
issued before moves are allowed in that direction again. If the limit that is reached is opposite the direc-
tion of travel, a
Reset Errors
command does not have to be issued.
Dwell Move
A Dwell Move gives you the ability to string multiple relative moves together and run all of them sequentially
with a single start condition. Like a Blend Move, a Dwell Move is programmed into an SMD17K as a series of
relative moves before the move is started.
Unlike a Blend Move, the motor is stopped between each segment of the Dwell Move for a programed
Dwell
Time
. The Dwell Time is programmed as part of the command that starts the move. The Dwell Time is the same
for all segments. Because the motor is stopped between segments, the motor direction can be reversed during
the move. The sign of the target position for the segment determines the direction of motion for that segment.
Positive segments will result in clockwise shaft rotation while a negative segment will result in a counter-clock-
wise shaft rotation.
Summary of Contents for SMD17K
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S292...
Page 6: ...TABLE OF CONTENTS SMD17K User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Page 48: ...CALCULATING MOVE PROFILES SMD17K User Manual ADVANCED MICRO CONTROLS INC 48 Notes...
Page 76: ...COMMAND DATA FORMAT SMD17K User Manual ADVANCED MICRO CONTROLS INC 76 Notes...
Page 94: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...
Page 96: ...DISTRIBUTED CLOCK SYNC0 SETUP SMD17K User Manual ADVANCED MICRO CONTROLS INC 96...
Page 98: ...DISTRIBUTED CLOCK SYNC0 SETUP SMD17K User Manual ADVANCED MICRO CONTROLS INC 98...