background image

20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254  Fax: (860) 584-1973  http://www.amci.com

13

TROUBLESHOOTING

Indexer Problems

Driver Problems

Symptom

Solution

My indexer/PLC reports a fault 
from the SD17040C when every-
thing seems fine.

Your logic may be reversed.  On the SD17040C, the Fault Output is on (con-
ducts current) when the driver is working correctly and turns off (stops cur-
rent flow) when there is a fault with the driver.  Therefore, losing power to the 
driver appears as a fault.  If you’re expecting the fault output to turn on and 
conduct current when there is a fault, then your logic is reversed.

The motor is running faster/slower 
than expected and/or the distance 
traveled is farther/shorter than 
expected.

Most likely a problem with the SD17040C’s Step Resolution setting or the 
indexer’s programming.  If the motor is running too fast, the Step Resolu-
tion on the SD17040C is set lower than the indexer’s programmer 
assumed it would.  If the motor is running slow, the Step Resolution is set 
higher than the indexer programmer assumed it would be.

Symptom

Solution

Both LED’s are off, and the Fault 
Output is active. (Not conducting)  
Power is applied to the driver.

1) The AC line voltage may be too low.  It must be greater than 85Vac 

for the SD17040C to operate properly.

2) One or both of the 10A fuses may be blown.  These fuses will not 

blow under normal circumstances, so call AMCI for assistance.  
Blown fuses may be a sign of serious installation problems.

Both LEDs are green, the Fault 
Output is inactive, (conducting) but 
the motor is not powered.

1) The ±Disable input may be active.  The active state, (power applied 

or power removed), is set by DIP switch SB1-4.  This switch may be 
set incorrectly.

2) The Idle Current Reduction may be set to its To 0% setting.  With this 

setting, current is removed from the motor if a directional pulse is not 
received for one second.

The 

STEP/FAULT

 LED does not 

blink when the indexer sends 
pulses to the driver.  The motor 
does not turn.

1) Verify that your two directional inputs on the Indexer Connector are 

not swapped or cross-wired.

2) If the inputs are wired as a sinking or sourcing instead of differential, 

verify that they are wired correctly.  If your indexer has sourcing out-
puts, then the inputs of the SD17040C must be wired as sinking 
inputs and vice versa. 

The 

STEP/FAULT

 LED is red.

The driver is experiencing a fault condition.  All faults are latched, so 
power must be cycled to the driver or the Disable Input must be toggled 
before the fault will clear.

1) Over Temp Fault.  Is the driver very hot?  It shuts down when its 

internal temperature exceeds 90°C (195°F).

2) Interlock Fault.  The motor is not plugged into the driver or a wire 

jumper was not installed between the two Interlock pins on the Motor 
Connector.

3) Short in Motor.  Shut off the SD17040C and disconnect the motor.  

Pull back the rubber boot and verify the following with an ohmmeter.
a) Open circuit from “A+” to “B+” pins.  (Tests for short between 

phases.)

b) Open circuit from “A+” to “Earth Ground” and “B+” to “Earth 

Ground”. (Tests for short between phase and case.)

If any of these readings is not an open circuit, then check your wiring.  
The most common cause of a short between phases is cross-wiring 
the phases when wiring the connector.  If you see a phase-to-case 
short, make sure you don’t have a stray wire from the “B+” or “A-” ter-
minals hitting the Earth Ground terminal on the connector.

Summary of Contents for SD17040C

Page 1: ...s e r M anual Manual 940 0S110 Table of Contents General Information 2 Introducing the SD17040C 3 Specifications 4 Mounting the SD17040C 5 Switch Settings 6 Connecting Your Controller 7 Connecting You...

Page 2: ...at its option repair or replace free of charge any equipment covered by this warranty which is returned shipping charges prepaid within eighteen months from date of invoice and which upon examination...

Page 3: ...uitry Back EMF Protection Circuity Programmable Step Resolution from 200 to 50 800 steps per turn Programmable Idle Current Reduction Programmable Current Loop Gain Programmable Pulse Train Input Step...

Page 4: ...Motor Current Switch selectable from 1 0 to 4 0ARMS in 0 1 Amp steps Idle Current Reduction Switch selectable to Not reduced To 69 To 50 or To 0 Motor current is reduced to selected level if a step p...

Page 5: ...so take steps to ensure that the two are electrically bonded together If necessary remove paint for the bolt mounting surfaces of the panel to ensure adequate electrical bonding Airflow and Wiring Spa...

Page 6: ...0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 1 1 0 0 0 0 0 0 1 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 0...

Page 7: ...lses The active state of the Disable Input is set by switch SB1 4 RLD An additional load resistor may be required on some PLC outputs to improve switching time A symptom of this problem is that the mo...

Page 8: ...e and is not ready to accept pulses Both ends of the output are uncommitted so it can be wired as a sourcing or sinking output The figure shows a typical connection as a sourcing output RLIMIT A resis...

Page 9: ...TAP B B EARTH GND A CTAP INTERLOCK A A 8 LEAD MOTOR Eight Lead Series Connected Motor Case INTERLOCK B CTAP B B EARTH GND A CTAP INTERLOCK A A 8 LEAD MOTOR Eight Lead Parallel Connected Motor Case INT...

Page 10: ...r itself B Phase Ground Short One of the motor s windings is shorted to earth ground The EARTH GND terminal of the Motor Connector is used as the reference point The fault can be in the motor cable or...

Page 11: ...for your system Turn off all of the switches in switch bank 2 and then verify that the motor current is set correctly and the motor is attached to the driver Cycle power to the driver The STEP FAULT...

Page 12: ...ne turn While the turn is in progress the STEP LED should blink Verify that the motor rotated in the correct direction for one complete turn If you are using an optical encoder or other position feedb...

Page 13: ...be active The active state power applied or power removed is set by DIP switch SB1 4 This switch may be set incorrectly 2 The Idle Current Reduction may be set to its To 0 setting With this setting cu...

Page 14: ...he driver is config ured for the Step Direction format the motor will rotate counter clock wise when the driver receives CW pulses and it will not rotate at all when the driver receives CCW pulses If...

Page 15: ......

Page 16: ...VANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ADVANCED MICRO CONTROLS INC ADVANCED MICRO CONTROLS INC ADVANCED MICRO CONTROLS INC 20 GEAR DRIVE TERRYVILLE CT 06786 T 860 585 1254 F 860 584 1973...

Reviews: