12
4.1.2 120VAC POWER SUPPLY WITH BUZZER
TRANSMITTER
AMC VersaTox
1-800-465-5777
www.armstrongmonitoring.com
3156502A
SENSOR
3.62"
4.125"
CABLE 6 FT
Figure 4-2 120VAC Power Supply with Buzzer Mounting
4.1.3 DUCT MOUNTING (OPTIONAL)
NOTE: The duct mount version is available for CO gas detection only.
The duct mount option is used to divert a portion of the duct airflow through the AMC-VersaTox.
The difference between the total pressure in the duct and outside the duct propels the sample
stream. The duct mount option can only be used in positive pressure ducts and is designed to
be directly mounted to the outside of the duct. The sampling tube is attached to the AMC-
VersaTox housing and inserted into the duct. The duct mount is assembled assuming the duct
air flow direction from left to right. If the opposite direction is required, remove the duct mounting
nut inside the housing, rotate the sampling tube 180º and reinstall the nut. Mount the
sensor/transmitter in a straight section of duct where the airflow is unrestricted and does not
interfere with any internal duct components. It is necessary to seal the conduit entry with
Ducseal or with another sealant.