Adjust heat < > vent differential (8)

Press the        to set the desired
temperature differential (dead band)
between heat and vent when in the Auto
mode.

Adjust GM 44 differential (9)

Press the        to set the number of degrees
that the 0 - 5VDC proportional band is to
vary over.

Adjust AmbiTec Plus type (10)

Press the         to set the control panel to
the type of unit required.  If the control
panel is to be used to control an individual
heater then set the display to read, ‘Adjust
Energy mizor 00’.  If more than one control
panel is to be used to control the heaters in
a Master/Slave configuration the use the       

to set the unit to be designated as the

Master to read ‘Adjust Master 00’.   If a unit
is to be designated as a slave panel then use
the         to set each slave to read ‘Adjust
Slave XX’.  XX is to be interpreted to be any
number from 01 - 31.  No two-slave panels
are allowed to have the same number
assigned.  Only one Master panel is allowed
on any one system.

Adjust reset (11)

Use the         to set the AmbiTec Plus to the
type of reset required.  Type 01 is all relays
off and is used for those heaters with
automatic ignition where power to the
burner must be interrupted to cause burner
reset in case of burner lock out.  Type 02 is
for use where a live or neutral is required to
be switched back to the heater unit to cause
burner reset.

Adjust V3 (12)

Use the        to change operation from
manual ‘Vent’ mode to V1 auto temperature
sensitive mode.

Adjust high fire time (13)

Use the        to set the time required for the
burner to be on high fire during light up for
proper ignition of the burner.  The setting
may be from 00 - 99 seconds.

Adjust preheat mode (14)

Press the         to select 01 if the preheat is
to remain fixed at the time set in the adjust
preheat screen.  Select 02 to allow the
controller to hold off the preheat to take
into account the actual ambient
temperature.

Adjust pre heat (15)

Use the        to set the required preheat
time from 0 hours to 4 hours in 30 minute
steps.  Ideally this should be set to the time
it takes to raise the room temperature to
20˚C.  Every on time will be advanced by
this preheat time.

Adjust day temperature band (16)

Use the        to select ‘From’ reading.  Use
the        to set these to the lower end of the
range over which the day temperature may
be set in the normal display adjust screen.
Use the         to select To reading.  Use the 

to set the upper end of the range over

which the day temperature may be set in
the normal display adjust screen.  The From
is adjustable from 00˚C to 50˚C and the To
is adjustable from 00˚C to 50˚C.  However
the To reading can never be set lower than
the From reading.

Night temperature band (17)

Use the        to select From reading.  Use
the        to set these to set the lower end of
the range over which the day temperature
may be set in the normal display adjust
screen.  Use the         to select To reading.
Use the        to set the upper end of the
range over which the day temperature may
be set in the normal display adjust screen.
The From is adjustable from 00˚C to 40˚C
and the To is adjustable from 00˚C to 50˚C.
However to To reading can never be set
lower than the From reading.

FWD clock 1 hour at 01:00 (18)

Use the        to move to the month position
and the        to select the month.  Use the

to select the date position and the     

to set the correct date for automatic clock
forward time.

RTD clock 1 hour at 01:00 (19)

Use the         to move to the month position
and the        to select the month.  Use the   

to select the date position and the    

to set the correct date for automatic

clock retard time.

Holiday (Covered only for frost
protection no night set back) (20)

Use the        to select the From date
position for the holiday period to start and
the        to set the date.  Use the         to
select the From month position and the
to set the month.  Use the        to select the
To date position for the holiday period to
end and the        to set the date.  Use the 

to select the To month position and the   
to set the month.

Note  If set the will turn off on the last OFF of
the From date and will turn back on again on
the first On of the To date.

Holiday 2 (21)

If required set a second holiday period as in
holiday 1.

Holiday 3 (22)

If required set a third holiday period as in
holiday 1.

Holiday 4 (23)

If required set a fourth holiday period as in
holiday 1.

Adjust Hand (24)

Use the        to adjust from 30 min. to 2
hours in 30 min steps.

AMBITEC

PLUS

ENERGY SAVING ELECTRONIC CONTROL PANEL

Summary of Contents for AMBITEC PLUS

Page 1: ...AMBITEC PLUS ENERGY SAVING ELECTRONIC CONTROL PANEL...

Page 2: ...neral setting instructions Display windows brief guide Display windows detailed Setting passwords Master slave operation Relay switching Technical support common problems Interconnect terminal layout...

Page 3: ...er Alphanumeric display system operation Optional Optimum Start Facility with automatic preheat adjustment LED s indicate frost protection and burner failure for automatic ignition burner systems Thre...

Page 4: ...ndard display It will then be necessary to press the Select button to get to any other screens that required adjustments in their settings Clock on times should be set to the normal occupancy times re...

Page 5: ...ock is OFF indicating which set point it is trying to achieve Advance ON OFF 3 With the normal display shown pressing the Select button twice will take you to the clock override screen The display wil...

Page 6: ...be advanced by this preheat time Adjust day temperature band 16 Use the to select From reading Use the to set these to the lower end of the range over which the day temperature may be set in the norm...

Page 7: ...date at the master will be sent to the slaves The master checks each slave on the system for a burner failure Should a failure occur this would appear not only on the slave controller but also on the...

Page 8: ...m temperature is daytime temperature setting V1 OFF V2 OFF V3 OFF 0 5VDC output ON if H1 is ON Vent mode CRF ON H2 OFF H1 OFF V1 ON if room temperature than day setting temperature dead band setting V...

Page 9: ...is blank and the connections are correct the AmbiTec Plus could need resetting this is detailed below under clearing all settings Note The AmbiTec Plus control panel is fully compatible with the MK2 E...

Page 10: ...as a starting point for all interlinks to liven up the relays except V3 relay connections 230V Flame fail V3 Summer Vent relay V2 Second stage Vent relay V1 First stage vent relay H1 First stage heat...

Page 11: ...s the right to change product specification without due notice Document reference number GB WA 032 0201 Ambi Rad Limited Fens Pool Avenue Brierley Hill West Midlands DY5 1QA United Kingdom Telephone 0...

Reviews: