7. Select CHARGE MODE.
8. Select ON. Press DONE to initiate CHARGE mode.
(System will then run for 1 hour and either return to
cooling mode if the thermostat is set for COOL mode,
or stop if the thermostat is set for FAN or HEAT mode.)
If charging is not complete after 1 hour, repeat
7. and 8.
Refer to “Adjust Refrigerant Level” and “Measure
Subcooling to Verify Proper Charge” for refrigerant
charge level adjustment.
9. To terminate CHARGE MODE, select CHARGE
mode screen again. Press OFF. Press DONE to
terminate CHARGE MODE.
10. Once CHARGE MODE is complete and has been
terminated, navigate to HOME screen. Enter
normal operation with temperature offset or thermostat
schedule, as desired.