10
System Wiring
Step 1. Calculate Refrigerant Charge Based on
Line Set Length
The condenser unit is shipped with a predetermined factory
charge level as shown below. For longer line sets greater
than 15 feet, add 0.6 ounces of refrigerant per foot. Refer
to the following page for the equivalent length of the elbow
fittings.
NOTICE
T
OTAL
R
EFRIGERANT
=
F
ACTORY
C
HARGE
+ (0.6
OZ
./
FT
. * A
DDITIONAL
F
EET
OF
A
CTUAL
L
INE
S
ET
)
.
The following table shows refrigerant amounts for every 5
feet of line.
2-Ton 3-Ton 4-Ton 5-Ton
15 (Factory Charge) 152
154
246
246
20
155
157
249
249
25
158
160
252
252
30
161
163
255
255
35
164
166
258
258
40
167
169
261
261
45
170
172
264
264
50
173
175
267
267
55
176
178
270
270
60
179
181
273
273
65
182
184
276
276
70
185
187
279
279
75
188
190
282
282
80
191
193
285
285
85
194
196
288
288
90
197
199
291
291
95
200
202
294
294
100
203
205
297
297
105
206
208
300
300
110
209
211
303
303
115
212
214
306
306
120
215
217
309
309
125
218
220
312
312
130
221
223
315
315
135
224
226
318
318
140
227
229
321
321
145
230
232
324
324
150
233
235
327
327
155
236
238
330
330
160
239
241
333
333
165
242
244
336
336
170
245
247
339
339
175
248
250
342
342
180
251
253
345
345
185
254
256
348
348
190
257
259
351
351
195
260
262
354
354
200
263
265
357
357
Actual Line Set
Length (ft.)
Unit Tonnage
Total Refrigerant (oz.)
Step 2. Connect Air Conditioner Unit to System
CAUTION
OPEN THE LIQUID VALVE FIRST! IF THE SUCTION SERVICE VALVE IS OPENED
FIRST, OIL FROM THE COMPRESSOR MAY BE DRAWN INTO THE INDOOR
COIL TXV RESTRICTING
REFRIGERANT FLOW AND AFFECTING OPERATION OF THE SYSTEM.
Summary of Contents for VXC20 Series
Page 6: ...6...
Page 26: ...26 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...
Page 27: ...27 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...
Page 29: ...29 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...
Page 39: ...39...
Page 40: ...40...
Page 41: ...41...
Page 57: ...57...
Page 58: ...58...