Amana PHB**C Installation Instructions Manual Download Page 5

5

To prevent improper and dangerous
operation due to wiring errors, label all
wires prior to disconnection when
servicing controls. Verify proper
operation after servicing.

The best protection for the wiring is the lowest rated fuse
or circuit breaker which will supply power to the unit during
normal operation without nuisance trips. Such a device
will provide maximum circuit protection. DO NOT EX-
CEED THE MAXIMUM OVERCURRENT DEVICE SIZE
SHOWN ON UNIT DATA PLATE.

All line voltage connections must be made through weath-
erproof fittings.  All exterior power supply and ground
wiring must be in approved weatherproof conduit. Low
voltage wiring from the unit control panel to the thermostat
requires coded cable.

Flexible Set-Up For Wiring On The Left Or Right
Side
Line voltage and low voltage wiring can enter the unit
either by:

• Line voltage, electrical heater wiring, and low voltage

on the right side or

• Line voltage and low voltage wiring on the left side

with electrical heater wiring on the right side or

• Line voltage and electrical heater wiring on the right

side with low voltage wiring on the left side or

• Low voltage wiring on the left side and line voltage

and electric heater wiring on the right side.

For knockout locations, see dimension drawing on the
Specification Sheet .  Use the Single Point wiring kit to add
further flexibility to the installation wiring.

Unit Voltage

The unit transformer is factory connected for 230V opera-
tion. If the unit is to operate on 208V, reconnect the
transformer primary lead as shown on the unit wiring
diagram.

Vl. Circulating Air and Filters

Airflow Conversion

Units can easily be converted from horizontal to vertical
airflow delivery.

Units are shipped from the factory ready for horizontal
airflow. If conversion to vertical airflow is necessary,
proceed as follows:

1. Cut insulation around bottom openings and remove

panels from the bottom of the unit, saving the screws
holding the panels in place.

2. From the rear of the unit, remove the four screws

securing the blower assembly in place and loosen the
two screws directly below the duct opening (Figure 4).

Remove

Loosen

Figure 4

Duct Removal

3. Remove the clamp securing the blower assembly to

the bottom of the unit. The clamp and screws may be
discarded (Figure 5).

Airflow

Remove

Figure 5

Clamp Removal

4. Rotate the blower assembly 90° clockwise, setting

the blower assembly outlet on the bottom of the unit
and secure with two screws removed in step 2 (Figure
6) .

5. Tighten the two screws below the duct opening that

were loosened in step 2.

Figure 6

Vertical Blower Assembly

CAUTION

Airflow

Install

Screws

Removed

From

Back 

Panel

Summary of Contents for PHB**C

Page 1: ...n manual adjacent to the unit RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION Remember itisyourresponsibilitytoinstalltheproduct safely and to know it well enough to be able to instruct a customer in its...

Page 2: ...efects or other reproductive harm Locating The Unit WARNING Topreventdeath personalinjury property damage or equipment damage the following points must be observed when installing the unit All Install...

Page 3: ...pection report issued by carrier representative at the time damage is reported to the carrier The carrier is responsible for making prompt inspection of damage and for a thorough investigationofeachcl...

Page 4: ...de at the heater accessory box If no heater is installed the thermostat wiring will bemade to the low voltage control board See the unit wiring diagram for electrical connections O R W Y G O R W Y G F...

Page 5: ...de For knockout locations see dimension drawing on the SpecificationSheet UsetheSinglePointwiringkittoadd further flexibility to the installation wiring Unit Voltage The unit transformer is factory co...

Page 6: ...duct from the unit through a wall fabricated of combustible material may be installed with out clearance However minimum clearances for the unit must be observed as shown in Specification Sheet The o...

Page 7: ...WARNING To avoid death or personal injury due to electrical shock do not remove any internal compartment covers or attempt any adjustment CAUTION Verify proper operation after servicing VIII Sequence...

Page 8: ...cludes its own separate instructions Replacement Parts Refer to the description in the Parts Catalog when order ing any part Be sure to provide the unit model manufac turing and serial numbers with th...

Reviews: