28
Outdoor
Indoor
PGC42
PGC48
PGC60 and PGB58
Air Temp.
at
Air
Temp.
Indoor
Air Temp.
Pressure @ Unit
Gauge Fittings
Amps
Indoor
Air Temp.
Pressure @ Unit
Gauge Fittings
Amps
Indoor
Air Temp.
Pressure @ Unit
Gauge Fittings
Amps
Condenser
Inlet
(Dry Bulb)
at Evap.
Inlet
(Wet Bulb)
Difference
Between
Coil Inlet
and Outlet
Low
Side
High
Side
Total to
Unit
Difference
Between
Coil Inlet
and Outlet
Low
Side
High
Side
Total to
Unit
Difference
Between
Coil Inlet
and Outlet
Low
Side
High
Side
Total to
Unit
A
B
C
D
E
B
C
D
E
B
C
D
E
° F.
° F.
° F.
PSIG
PSIG
Amps
° F.
PSIG
PSIG
Amps
° F.
PSIG
PSIG
Amps
77
7
86
332
23.1
8
88
327
23.8
9
83
343
34.9
115
72
12
85
331
23.1
13
88
327
23.8
15
83
342
34.8
67
18
85
332
23.1
18
88
327
23.8
21
82
342
34.7
62
23
84
332
23.2
24
87
326
23.7
26
81
341
34.6
77
8
85
313
22.2
8
88
308
23.2
10
82
323
33.3
110
72
13
85
313
22.2
13
87
308
23.2
15
82
322
33.2
67
18
84
312
22.1
18
87
308
23.1
21
81
322
33.2
62
23
83
311
22.1
24
86
307
23.1
27
80
321
33.1
77
8
84
294
21.3
8
87
291
22.5
10
82
303
31.8
105
72
13
84
293
21.2
13
86
290
22.5
15
81
303
31.8
67
18
83
294
21.3
18
86
290
22.5
21
80
303
31.8
62
23
82
293
21.2
24
85
290
22.4
27
80
302
31.7
77
8
84
277
20.4
8
86
274
21.9
10
81
285
30.5
100
72
13
83
276
20.4
13
86
273
21.9
15
80
285
30.4
67
18
83
275
20.4
19
85
273
21.8
21
80
285
30.5
62
24
82
274
20.3
24
84
272
21.8
27
79
284
30.4
77
8
83
259
19.6
8
85
256
21.3
10
80
268
29.2
95
72
13
82
258
19.6
13
85
257
21.2
16
80
267
29.2
67
18
82
257
19.5
19
84
256
21.2
22
79
267
29.2
62
24
81
256
19.5
25
84
255
21.1
28
78
266
29.1
77
8
82
241
18.8
8
84
240
20.6
10
79
251
28.1
90
72
13
82
241
18.8
14
84
240
20.6
16
79
250
28.0
67
19
81
240
18.8
19
83
240
20.6
22
78
250
28.0
62
24
80
240
18.8
25
83
239
20.5
28
77
249
27.9
77
8
82
226
18.1
9
84
225
20.0
11
79
234
27.0
85
72
13
81
224
18.1
14
83
225
20.0
16
78
234
26.9
67
19
81
225
18.1
19
83
224
20.0
22
78
233
26.9
62
24
80
223
18.0
25
82
224
19.9
28
77
232
26.8
77
8
81
211
17.5
9
83
200
19.4
11
78
218
25.9
80
72
13
81
210
17.5
14
82
210
19.4
16
78
218
25.9
67
19
80
211
17.5
20
82
209
19.4
22
77
218
25.9
62
24
79
208
17.4
25
81
209
19.3
28
76
217
25.8
77
9
80
196
16.9
9
82
196
18.8
11
78
204
25.0
75
72
14
80
196
16.9
14
82
196
18.8
16
77
203
24.9
67
19
79
194
16.8
20
81
195
18.8
22
76
203
24.9
62
25
79
194
16.8
25
80
195
18.8
28
76
202
24.8
Table 8B
A Columns - All data based on indoor dry bulb of 80° F and rated air flow. As indoor dry bulb temperature increases, a slight increase will occur in indoor air temperature differential
between inlet and outlet. Low and high side pressures and power will not change.
B Columns - A properly operating unit should be within ±3° F of the typical (dry bulb) value shown.
C Columns - A properly operating unit should be within ±3 PSIG of the typical value shown.
D Columns - A properly operating unit should be within ±7 PSIG of the typical value shown.
E Columns - A properly operating unit should be within ±2 amps of the typical value shown.