CONDENSING UNIT SPECIFICATIONS
8
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/
circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuses or HACR type Circuit Breaker of the same size as noted.
ASX140181D*
/ ASX140421D*
ASX140181D*
ASX140421D*
Cooling Capacity, BTUH
18,000
40,000
Compressor
R.L. Amps
9.00
16.7
L.R. Amps
48.0
79.0
Low Pressure Switch
Open
Close
N/A
N/A
22 PSIG
50 PSIG
High Pressure Switch
Open
Close
610 PSIG
420 PSIG
610 PSIG
420 PSIG
Condenser Fan Motor
Horsepower
1/8
1/6
F.L. Amps
0.7
0.9
Liquid Line, Inches O.D.*
3/8"
3/8"
Suction Line, Inches O.D.*
3/4"
7/8"
Refrigerant Charge
73.0
140.0
Power Supply
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity
(1)
12
21.8
Maximum Overcurrent Device
(2)
20
35
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
146
184