39
PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and
high side pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 2
degrees
of the subcooling value shown in the installation
instructions.
A properly operating unit should be within plus or minus
3 degrees
of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus
10 PSIG
of the
HI PR
shown.
A properly operating unit should be within plus or minus
5 PSIG
of the
LO PR
shown.
A properly operating unit should be within plus or minus
3 Amps
of the typical value shown.
NOTE: Pressures are measures at the liquid and suction service valve ports.
ASX140421[C/D]* - ASX140481C*
Outdoor
Temp. ° F.
Total
Btuh
Sensible
Btuh
Latent
Btuh
Total
Watts
75°
48,300
34,776
13,524
3,260
80°
47,750
34,858
12,893
3,365
85°
47,200
34,928
12,272
3,470
90°
46,600
34,950
11,650
3,560
95°
46,000
34,960
11,040
3,650
100°
44,850
34,759
10,091
3,725
105°
43,700
34,523
9,177
3,800
110°
42,100
33,470
8,631
3,865
115°
40,500
32,400
8,100
3,930
95°
43,552
35,549
8,003
3,618
TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB
ASX140481C* / CA*F4860*6D* W/.078 Orfice
Conditions: 80°F IDB, 67°F IWB @ 1550 CFM
Outdoor
Temp. ° F.
Total
Btuh
Sensible
Btuh
Latent
Btuh
Total
Watts
75°
42,116
29,985
12,131
2,950
80°
41,614
30,004
11,610
3,040
85°
41,113
30,015
11,098
3,130
90°
40,611
30,127
10,485
3,205
95°
40,110
30,227
9,883
3,280
100°
39,107
30,029
9,078
3,350
105°
38,105
29,803
8,301
3,420
110°
36,701
28,826
7,875
3,475
115°
35,297
27,839
7,458
3,530
95°
37,200
30,132
7,068
3,160
TVA Conditions @ 95° OD DB, 75° ID DB 63° ID WB
MODEL: ASX 140421[C*/D* ] / CA*F4860*6B* W /.070 Ori fice,
Conditions: 80°F IDB, 67°F IWB @ 1450 CFM