Amana ASC13018 Service Instructions Manual Download Page 38

SERVICING

38

AR*F & MBR

WITH SINGLE STAGE

 

HEAT PUMPS

3.0 Cooling Operation

On heat pump units, when the room thermostat set to the
cooling mode, 24Vac is supplied to “O” which energizes the
reversing valve.  As long as the thermostat is set for cooling,
the reversing valve will be in the energized position for cooling.

3.1

 On a demand for cooling, the room thermostat energizes

“G” and “Y” and 24Vac is supplied to “Y” at the heat pump
and the “G” terminal on the EBTDR board.

3.2

 The heat pump turned on in the cooling mode and after a

7 second on delay, the relay on the EBTDR board is
energized and the blower motor starts.

3.3

 When the cooling demand is satisfied, the room thermo-

stat removes the 24Vac from “G” and “Y”.

3.4

 The heat pump is turned off and after a 65 second delay

off, the relay on the EBTDR board is de-energized and the
blower motor is turned off.

4.0 Heating Operation

On heat pump units, when the room thermostat set to the
heating mode, the reversing valve is not energized.  As long
as the thermostat is set for heating, the reversing valve will be
in the de-energized position for heating except during a
defrost cycle.  Some installations may use one or more
outdoor thermostats to restrict the amount of electric heat
that is available above a preset ambient temperature.  Use of
optional controls such as these can change the operation of
the electric heaters during the heating mode.  This sequence
of operation does not cover those applications.

4.1

 On a demand for first stage heat with heat pump units, the

room thermostat energizes “G” and “Y” and 24Vac is
supplied to “Y” at the heat pump unit and the “G” terminal
on the EBTDR board.  The heat pump is turned on in the
heating mode and the blower motor starts after a 7 second
on delay.

4.2

 If the first stage heat demand cannot be satisfied by the

heat pump, the temperature indoors will continue to drop.
The room thermostat will then energize terminal “W2’ for
second stage heat and 24Vac will be supplied to heat
sequencer HR1 on the heater assembly.

4.3

 HR1 contacts M1 and M2 will close will close within 10

to 20 seconds and turn on heater element #1.  At the
same time, if the heater assembly contains a second
heater element, HR1 will contain a second set of con-
tacts, M3 and M4, which will close and turn on heater
element #2.  The blower motor is already on as a result
of terminal “G” on the EBTDR board being energized for
the first stage heat demand.

Note:

 If more than two heater elements are on the heater

assembly, it will contain a second heat sequencer, HR2,
which will control the 3

rd

 and 4

th

 heater elements if available.

If the second stage heat demand, “W2” cannot be satisfied
by the heat pump, the temperature indoors will continue to
drop.  The room thermostat will then energize “W3” and
24Vac will be supplied to HR2 on the heater assembly.  When
the “W3” demand is satisfied, the room thermostat will
remove the 24Vac from HR2.  The contacts on HR2 will open
between 30 to 70 seconds and heater elements #3 and #4 will
be turned off.  

On most digital/electronic thermostats,

“W3” will remain energized until the first stage heat
demand “Y” is satisfied and then the “G”, “Y”, “W2”
and “W3” demands will be removed.

4.4

 As the temperature indoors increase, it will reach a point

where the second stage heat demand, “W2”, is satisfied.
When this happens, the room thermostat will remove the
24Vac from the coil of HR1.  The contacts on HR1 will
open between 30 to 70 seconds and turn off both heater
element(s).  The heat pump remains on along with the
blower motor because the “Y” demand for first stage heat
will still be present.

4.5 

When the first stage heat demand “Y” is satisfied, the

room thermostat will remove the 24Vac from “G” and “Y”.
The heat pump is turned off and the blower motor turns off
after a 65 second off delay.

5.0 Defrost Operation

On heat pump units, when the room thermostat is set to the
heating mode, the reversing valve is not energized.  As long
as the thermostat is set for heating, the reversing valve will be
in the de-energized position for heating except during a
defrost cycle.

5.1

 The heat pump will be on and operating in the heating

mode as described the Heating Operation in section 4.

 5.2 The defrost control in the heat pump unit checks to see

if a defrost is needed every 30, 60 or 90 minutes of heat
pump operation depending on the selectable setting by
monitoring the state of the defrost thermostat attached to
the outdoor coil.

5.3 If the temperature of the outdoor coil is low enough to

cause the defrost thermostat to be closed when the
defrost board checks it, the board will initiate a defrost
cycle.

5.4 When a defrost cycle is initiated, the contacts of the

HVDR relay on the defrost board open and turns off the
outdoor fan.  The contacts of the LVDR relay on the
defrost board closes and supplies 24Vac to “O” and “W2”.
The reversing valve is energized and the contacts on HR1
close and turns on the electric heater(s).  The unit will
continue to run in this mode until the defrost cycle is
completed.

Summary of Contents for ASC13018

Page 1: ...ps with R 22 Refrigerant Blowers Coils Accessories This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or...

Page 2: ...you assume responsibility for any personal injury or property damage which may result WARNING This unit should not be connected to or used in conjunction with any devices that are not design certifie...

Page 3: ...s Ensure the pressure rating meets or exceeds 400 lbs When in doubt do not use cylinder WARNING In either of these instances an electrical short between the terminal and the compressor housing may res...

Page 4: ...ons G S C 13 036 1 A A Brand Name G Goodman Brand Amana Brand Distinctions S Goodman Brand High Feature Set Models A Amana Brand Product Category S Split System Unit Type C Condenser R 22 H Heat Pump...

Page 5: ...5 tons 024 2 tons 030 2 5 tons 036 3 tons 042 3 5 tons 048 4 tons 060 5 tons 070 5 tons 090 7 5 tons 120 10 tons C KL 036 2 A Electrical Supply Unit Type E CommercialAirConditioner K AirConditioner P...

Page 6: ...ner K AirConditioner P Heat Pump Product Category C Split System 1 208 230V 60Hz 1ph 2 220 240V 50Hz 1ph 3 208 230V 60Hz 3ph 4 308 415V 50Hz 3ph Revision NominalCapacity 018 1 5 tons 024 2 tons 030 2...

Page 7: ...n A Initial Release THIS NOMENCLATURE IS TO BE USED AFTER JULY 2006 THIS NOMENCLATURE IS TO BE USED TRHOUGH JULY 2006 A W U F 3642 1 6 A A Electrical Supply Expansion Device Application C Ceiling Moun...

Page 8: ...21 Furnace Cabinet D Fits 24 1 2 Furnace Cabinet N Does Not Apply Horizontal Slab Coils Expansion Device F Flowrator Revision A Initial Release Nominal Capacity Range 13 SEER 1824 1 1 2 2 tons 3030 2...

Page 9: ...X X X X X CSR U 1 Hard Start Kit X X X X CSR U 2 Hard Start Kit X X X X CSR U 3 Hard Start Kit X X Model Description ASC13018 ASC13024 ASC13030 ASC13036 ASC13042 ASC13048 ASC13060 OT18 60A Outdoor The...

Page 10: ...Kit x x OT18 60A Outdoor Lockout Stat OT EHR18 60 Emergency Heat relay kit CSR U 1 Hard Start Kit x x CSR U 2 Hard Start Kit x x x CSR U 3 Hard Start Kit x x Model Description CKL18 CKL24 CKL30 CKL36...

Page 11: ...ORATOR COIL 1 4 FLARE CONNECTION BULB SUCTION LINE EXPANSION VALVE REMOVE BEFORE INSTALLING EXPANSION VALVE SEAL SUPPLIED W KIT SEAL SUPPLIED W KIT BULB TO BE LOCATED AT 10 OR 2 O CLOCK TAILPIECE 3 8...

Page 12: ...HERMOSTAT WIRE SHORT CYCLE PROTECTOR YELLOW 1 BLACK 1 Y1 Y2 R1 R2 Y C UNIT TERMINAL BOARD CONTACTOR ASC01A ANTI SHORT CYCLECONTROLKIT Install Line Thermostat Here Install Line Thermostat Here Wire Nut...

Page 13: ...X X CHPF30306 X X CHPF36426 X X CSCF1824N6 X X CSCF303N6 X X CSCF3642N6 X X X NO HEAT KIT HKR 03 HKR05 C HKR 06 HKR 08 C HKR 10 C HKR 15C HKR 20C HKR 21C HKR3 15 HKR3 20 MBR0800AA 1AA X X X X X MBR12...

Page 14: ...t the compressorcenter COILS AND BLOWER COILS MBR MBEblowercabinetsaredesignedtobeusedasatwo piece blower and coil combination MBR MBE blower sec tions can be attached to cased evaporator coil This tw...

Page 15: ...d itcontinuestogiveup heat which subcools the liquid and it is ready to repeat the cycle HEATING The heating portion of the refrigeration cycle is similar to the coolingcycle Byenergizingthereversingv...

Page 16: ...door Coil Accumulator Bi Flow Filter Dryer Outdoor Coil Thermostatic Expansion Valve Check Valve Reversing Valve De Energized Indoor Coil Accumulator Bi Flow Filter Dryer Outdoor Coil Thermostatic Exp...

Page 17: ...ng mode the orifice moves back off its seat allowingrefrigeranttoflowunmeteredaround the outside of the orifice EXPANSIONVALVE CHECKVALVEASSEMBLY INCOOLINGOPERATION EXPANSIONVALVE CHECKVALVEASSEMBLY I...

Page 18: ...ndoor Coil Outdoor Coil Thermostatic Expansion Valve COOLING CYCLE CONDENSING UNIT In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the c...

Page 19: ...elow a specific ambient temperature setting i e break even temperature during heating When used in this manner the Y heat demand is switched to the W1 input to the furnace by the outdoor thermostat an...

Page 20: ...est Motor Windings S 16 Improper Cooling Anticipator Check Resistance of Anticipator S 3B Shortage of Refrigerant Test For Leaks Add Refrigerant S 101 103 Restricted Liquid Line Remove Restriction Rep...

Page 21: ...CM Motor Windings 33 S 16D ECM CFM Adjustments 33 S 16E Checking GE X13 Motors 34 S 17 CheckingCompressorWindings 35 S 17A Resistance Test 35 S 17B GroundTest 35 S 17D OperationTest 36 S 18 Testing Cr...

Page 22: ...nsofundersized wirecancauselowvoltage Ifwiresizeisadequate notify the local power company in regard to either low or high voltage REMOTE CONDENSING UNITS BLOWER COILS VOLTAGE MIN MAX 208 230 198 253 1...

Page 23: ...TS OPTIONS Troubleshooting Encoded Two Stage Cooling Thermostats Options TEST FUNCTION SIGNAL OUT SIGNAL FAN S T E T S1 S1 S1 S2 S2 S2 S3 S3 S3 R COM LOW SPEED COOL LO SPEED COOL HI SPEED COOL LO SPEE...

Page 24: ...pproximatelythree minutes before resetting 1 Remove wire from Y1 terminal 2 Wait for approximately four 4 minutes if machine was running With power ON WARNING Line Voltage nowpresent 1 Apply 24 VAC to...

Page 25: ...relay or contactor S 8 CHECKING CONTACTOR CONTACTS DISCONNECTELECTRICALPOWERSUPPLY WARNING Disconnect Electrical Power Supply 1 Disconnectthewireleadsfromtheterminal T sideofthe contactor 2 With powe...

Page 26: ...electrical box of any residential condensing unit that has a Copeland Scroll compressor inside Once attached Comfort Alert provides around the clock monitoring for common electrical problems compress...

Page 27: ...formation Yellow ALERT Locked Rotor 1 Run capacitor has failed Flash Code 4 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Page 28: ...ight dimming within the home Only hard start kits approved by Amana brand or Copeland should be used Kick Start and or Super Boost kits are not approved start assist devices Thedischargecheckvalveclos...

Page 29: ...o and slowly returnstoinfinity Startcapacitorwithbleedresistorwill not return to infinity It will still read the resistance of the resistor B Shorted indicator swings to zero and stops there replace C...

Page 30: ...5 at the power connector If no voltage is present 3 Check the unit for incoming power See section S 1 4 Check the control board See section S 40 5 Iflinevoltageispresent reinsertthe5 pinconnectorand...

Page 31: ...R G Turn power OFF prior to repair Wait 5 minutes after disconnecting power before opening motor Handle electronic motor control with care Motor rocks but won t start Loose motor mount Blower wheel n...

Page 32: ...wer OFF prior to repair Wait 5 minutes after disconnecting power before opening motor Handle electronic motor control with care Blower won t shut off Current leakage from controls into G Y or W Check...

Page 33: ...E product uses a General Electric ECMTM motor This motor provides many features not available on the traditional PSC motor These features include ImprovedEfficiency Constant CFM Soft Start and Stop Im...

Page 34: ...ged electric heat cut jumper PJ4 on the control board S 16E CHECKING GE X13TM MOTORS The GE X13TM Motor is a one piece fully encapsulated 3 phasebrushlessDC singlephaseACinput motorwithball bearing co...

Page 35: ...otoramperage andwindingtemperature Highmotortemperatureoramper age heats the disc causing it to open breaking the common circuit within the compressor on single phase units Heat generated within the c...

Page 36: ...thecause for failure is somewhere else in the system B If the compressor fails to start replace COPELAND COMPRESSOR 03 A 12345 L YEAR MONTH SERIAL NUMBER PLANT S 18 TESTING CRANKCASE HEATER OPTIONAL I...

Page 37: ...he EBTDR board These terminals are used to connect the unused leadsfromtheblowermotorandhavenoaffectontheboard s operation SEQUENCE OF OPERATION This document covers the basic sequence of operation fo...

Page 38: ...r the first stage heat demand Note If more than two heater elements are on the heater assembly it will contain a second heat sequencer HR2 which will control the 3rd and 4th heater elements if availab...

Page 39: ...tion 2 1 On a demand for heat the room thermostat energizes W1 and 24Vac is supplied to terminal E W1 of the VSTBinsidetheMBEandAEP units TheVSTBwillturn on the blower motor and the motor will ramp up...

Page 40: ...contains a second heater element HR1 will contain a second set of contacts M3 and M4 which will close to turn on heater element 2 Note If more than two heater elements are on the heater assembly it w...

Page 41: ...ion manual suppliedwiththeblowercoil ortheblowerperformancetable in the service manual shows the CFM for the static mea sured Alternately the system CFM can be determined by operat ingtheelectricheate...

Page 42: ...er test the element for continuity no reading indicates the element is open Replace as necessary S 100 REFRIGERATION REPAIR PRACTICE DANGER Always remove the refrigerant charge in a proper manner befo...

Page 43: ...e s with the compressor open with the suction line of the comprssor closed or severely restricted WARNING 1 Connect the vacuum pump vacuum tight manifold set with high vacuum hoses thermocouple vacuum...

Page 44: ...suction valve core remove hose and reinstall both valve core caps 6 Check system for leaks NOTE Thischargingprocedurecanonlybedoneinthe cooling mode of operation Early production a mod els only All mo...

Page 45: ...needforanexternalcheckvalveandbypassloop Thethreeforceswhichgoverntheoperationofthevalveare 1 the pressure created in the power assembly by the feeler bulb 2 evaporatorpressure and 3 theequivalentpres...

Page 46: ...le superheat SUPERHEAT ADJUSTMENT The expansion valves used on Amana brand coils are factory set and are not field adjustable If the superheat setting becomes disturbed replace the valve On systems us...

Page 47: ...flow into an evaporator coil The amount of refrigerant that flows through the capillary tube restrictororificeisregulatedbythepressuredifference between the high and low sides of the system In the coo...

Page 48: ...OTICE Violation of EPA regulations may result in fines or other penalties Now determine if a burn out has actually occurred Confirm byanalyzinganoilsampleusingaSporlanAcidTestKit AK 3 or its equivalen...

Page 49: ...line size to 3 8 is critical since an increased refrigerant charge level from having a larger liquidlinecouldpossiblyshortenacompressor slifespan 3 Single Stage Condensing Unit The maximum length of...

Page 50: ...le 9 Installation Requirements 1 In a completely horizontal installation with a long line set wheretheevaporatorisatthesamealtitudeas orslightly below the condenser the line set should be sloped towar...

Page 51: ...0 F at any time Wrap the reversing valve with a large rag saturated with water Re wet the rag and thoroughly cool the valve after eachbrazingoperationofthefourjointsinvolved Thewetrag around the rever...

Page 52: ...oilandthenegativeprobe above the coil 2 A direct reading can be taken of the static pressure drop across the coil 3 Consult proper table for quantity of air STATIC PRESSURE DROP Ifthetotalexternalstat...

Page 53: ...P2 4 K1 OT NO Y P2 9 CALL FOR 2ND STAGE COMPRESSOR Y2 1 0K G FURN P2 1 C OT C C SECOND STAGE COMPRESSOR OUTPUT G CALL FOR EMERGENCY HEAT W1 FURN W2 HP F1 3A OT NC 24VAC 2ND STAGE COMPRESSOR DEMAND OUT...

Page 54: ...age Electric Heat RED EMERGENCY HEAT RELAY 1 4 2 BLUE WHITE BLACK BROWN THERMOSTAT OT EHR18 60 2 1 From Air Handler C G W2 R C R W2 O Y From Outdoor Unit C G W2 E R O Y Indoor Thermostat W3 B L U E G...

Page 55: ...or Unit C G W2 E R O Y Indoor Thermostat W3 W3 B L U E G R E E N W H I T E R E D B R O W N B L U E R E D W H I T E O R A N G E Y E L L O W 15kw and Above with Two OT EHR18 60 s Two Stage Electric Heat...

Page 56: ...ATOR MOTOR ELECTRONIC BLOWER TIME RUN CAPACITOR SR EM EBTDR RC BK RD BL YL BLUE BLACK RED YELLOW COMPONENT CODE BROWN PURPLE GREEN PU BR GR FEMALE PLUG CONNECTOR MALE PLUG CONNECTOR NOTE 2 TRANSFORMER...

Page 57: ...G NO K1 USE COPPER OR ALUMINUM WIRE EQUIPMENT GROUND 3 5 2 1 4 TR PC PU L1 L2 BL W BR SR PK G W BR BL PU R BK R R R BK BL BL R 208 240 24V BL R M6 M5 RS2 W BR BL BL L1 L2 BK BK R R Y Y Y M8 M7 BL BL B...

Page 58: ...ATIONS CONNECT THERMOSTAT TO Y Y2 ONLY TAPE OR REMOVE Y1 CONNECTION CONNECT CONDENSING UNIT TO YCON C 6 RED WIRES TO BE ON TRANSFORMER TERMINAL 3 FOR 240 VOLTS AND ON TERMINAL 2 FOR 208 VOLTS 1 FOR HE...

Page 59: ...DENSER COM W2 O ED W1 OUTDOOR HEATPUMP W W2 R W BL OTC OT1 C OT2 O E W1 BR BL Y BL Y YCON TO CONDENSER C PL2 3 1 2 BR Y W BL BR R PK G Y1 C W2 R TO Y Y2 G EM BK R G BL 4 5 6 7 8 9 W R R BL COM BL 5 TR...

Page 60: ...r 240 volts and on terminal 2 for 208 volts 2 See composite wiring diagrams in installationinstructions for proper low voltage wiring connections Notes DELAY RELAY RELAY EVAPORATOR MOTOR ELECTRONIC BL...

Reviews: