Component Specifications
RT1300057 Rev. 2
2
November 2000
Illustration
Component
Test Procedure
A3079001
Bulb, tubular
Volt
Watt
115 VAC
40 watts
A0282807
Bulb, globular
Volt
Watt
120/125 VAC
60 watts
C8931608
Capacitor, compressor run
Volt
Capacitance
210 VAC(Panasonic), 220 VAC (ASC
AMN04 or NSK85212)
15 Mfd +10%
-5%
R9900020
Compressor
Type
BTUH
Volt
Watt
Current
Lock rotor
Full load
Resistance
Run Windings
Start Windings
Fan Cooled, R134a refrigerant
970 BTUH
115 VAC, 60 Hz
170 watts
21.3 amps
1.6 amps
2.60 ohms
4.35 ohms
R9900109
Control, damper
Settings
#1
#4
#7
Closing temperatures
47
F
40
F
30
F
R0161092
Control, freezer temperature
Settings
#1
²
in
#1
²
out
#4
²
in
#4
²
out
#7
²
in
#7
²
out
Temperatures
21.0
F
4.5
F
13.3
F
-5.9
F
9.8
F
-11.0
F
B2150504
Drier
Drier must be changed every time the system is opened for testing or
compressor replacement.
Desiccant (20) 8 x 12 4AXH - 7 M>S> -Grams
12049801
Heater, evaporator
Volt
Wattage
Resistance
115 VAC
450
5% watts
29
5% ohms
!
WARNING
To avoid risk of electrical shock that can cause death or severe personal injury, disconnect unit from power before
servicing unless tests require power. Discharge capacitors through a 10,000-ohm resistor before handling. Wires
removed during disassembly must be replaced on correct terminals to ensure proper grounding and polarization.