SERVICING
95
Underfeeding
Underfeeding by the expansion valve results in low system
capacity and low suction pressures.
If these symptoms are observed:
1. Check for a restricted liquid line or drier. A restriction will
be indicated by a temperature drop across the drier.
2. Check the operation of the power element of the valve as
described in Checking Expansion Valve Operation.
Checking Superheat
Superheat on Fixed Orifice or TXV
1. Purge gauge lines. Connect service gauge manifold to
base-valve service ports. Run system at least 10 minutes
to allow pressure to stabilize.
2. Temporarily install a thermometer 4-6” from the compressor
on the suction line. Ensure the thermometer makes
adequate contact and is insulated for best possible
readings. Use vapor temperature to determine superheat.
3. Refer to the superheat table provided for proper system
superheat. Add charge to lower superheat or recover
charge to raise superheat.
4. Disconnect manifold set, installation is complete.
Superheat Formula = Suct. Line Temp. - Sat. Suct.
Temp.
Model
Cur. Rev Piston Prev. Rev Piston
G/VSZ140181
LA
.032
KF
.039
G/VSZ140241
LA
.047
KH
.047
G/VSZ140301
KG
.052
KF
.052
G/VSZ140361
KE
.059
LA
.059
G/VSZ140421
KE
.061
KD
.061
G/VSZ140481
KF
.065
KE
.065
G/VSZ140491
KE
.065
KD
.065
G/VSZ140601
KE
.065
KD
.065
Model
Cur. Rev Piston Prev. Rev Piston
ASZ140181
KE
.039
KD
.039
ASZ140241
KD
.047
KC
.047
ASZ140301
KD
.052
KC
.052
ASZ140361
KD
.059
KC
.059
ASZ140381
AC
.059
n/a
.059
ASZ140421
KD
.061
KC
.061
ASZ140481
KD
.065
KC
.065
ASZ140491
KD
.065
KC
.065
ASZ140601
KC
.065
KB
.065
Model
Cur. Rev Piston Prev. Rev Piston
ANZ140181
AE
.039
AD
.039
ANZ140241
AD
.047
AA
.047
ANZ140301
AE
.052
AD
.052
ANZ140361
AD
.059
AC
.059
ANZ140421
AD
.061
AC
.061
ANZ140481
AD
.065
AC
.065
ANZ140491
AD
.065
AC
.065
ANZ140601
AC
.065
AB
.065
Pistons Used in Outdoor Heat Pump Coils
Goodman 14 SEER Heat Pumps
Amana 14 SEER Heat Pumps
Amana 14 SEER Heat Pumps
CAUTION
To prevent personal injury, carefully connect
and disconnect manifold gauge hoses. Escaping
liquid refrigerant can cause burns. Do not vent
refrigerant to atmosphere. Recover during
system repair or final unit disposal.
1. Run system at least 10 minutes to allow pressure to
stabilize.
2. For best results, temporarily install a thermometer on the
liquid line at the liquid line service valve and 4-6” from the
compressor on the suction line. Ensure the thermometer
makes adequate contact and is insulated for best possible
readings. Use liquid line temperature to determine sub-
cooling and vapor temperature to determine superheat.