4
www.amana-hac.com
SS-ACVC96
SS-ACVC96
www.amana-hac.com
5
Airflow Data
ACVC960403BNA
Cooling Speeds
( @ .1" - .8" w.c. ESP)
ACVC960403BNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 20 - 50°F)
Tap
Adjust
High-Stage
CFM
Low-Stage
CFM
Tap
Adjust
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10%
590
404
A
Minus 10%
861
614
41
Minus 5%
622
427
Minus 5%
909
648
39
Normal
655
449
Normal
957
682
37
Plus 5%
688
471
Plus 5%
1,005
716
35
Plus 10%
721
494
Plus 10%
1,053
750
34
B
Minus 10%
726
512
B
Minus 10%
953
675
37
Minus 5%
767
541
Minus 5%
1,006
713
35
Normal
807
569
Normal
1,059
750
34
Plus 5%
847
597
Plus 5%
1,112
788
32
Plus 10%
888
626
Plus 10%
1,165
825
31
C
Minus 10%
898
644
C
Minus 10%
1,040
738
34
Minus 5%
948
680
Minus 5%
1,097
779
32
Normal
998
716
Normal
1,155
820
31
Plus 5%
1,048
752
Plus 5%
1,213
861
29
Plus 10%
1,098
788
Plus 10%
1,271
902
28
D
Minus 10%
1,086
769
D
Minus 10%
1,126
799
32
Minus 5%
1,147
811
Minus 5%
1,188
844
30
Normal
1,207
854
Normal
1,251
888
28
Plus 5%
1,267
897
Plus 5%
1,314
932
27
Plus 10%
1,328
939
Plus 10%
1,376
977
26
ACVC960603BNA
Cooling Speeds
( @ .1" - .8" w.c. ESP)
ACVC960603BNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
Tap
Adjust
High-Stage
CFM
Low-Stage
CFM
Tap
Adjust
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10%
590
390
A
Minus 10%
844
618
63
Minus 5%
623
411
Minus 5%
891
653
60
Normal
656
433
Normal
938
687
57
Plus 5%
689
455
Plus 5%
985
721
54
Plus 10%
722
476
Plus 10%
1,032
756
52
B
Minus 10%
711
487
B
Minus 10%
855
676
62
Minus 5%
751
514
Minus 5%
903
713
59
Normal
790
541
Normal
950
751
56
Plus 5%
830
568
Plus 5%
998
789
53
Plus 10%
869
595
Plus 10%
1,045
826
51
C
Minus 10%
875
617
C
Minus 10%
887
733
60
Minus 5%
923
652
Minus 5%
937
773
57
Normal
972
686
Normal
986
814
54
Plus 5%
1,021
720
Plus 5%
1,035
855
52
Plus 10%
1,069
755
Plus 10%
1,085
895
49
D
Minus 10%
1,076
725
D
Minus 10%
893
787
60
Minus 5%
1,135
766
Minus 5%
942
830
57
Normal
1,195
806
Normal
992
874
54
Plus 5%
1,255
846
Plus 5%
1,042
918
51
Plus 10%
1,315
887
Plus 10%
1,091
961
49
Notes
•
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
•
For most jobs, about 400 CFM per ton when cooling is desirable.
•
Installation is to be adjusted to obtain temperature rise within the range specified on the rating plate.