9.  The unit must be connected to the building piping by

one of the following methods:

Rigid metallic pipe and fittings

Semirigid metallic tubing and metallic fittings (Alumi-

num alloy tubing must not be used in exterior loca-

tions)

Listed gas appliance connectors used in accor-

dance with the terms of their listing that are com-

pletely in the same room as the equipment

Protect connectors and semirigid tubing against

physical and thermal damage when installed.  En-

sure aluminum-alloy tubing and connectors are

coated to protect against external corrosion when in

contact with masonry, plaster, or insulation, or sub-

jected to repeated wetting by liquids such as water

(except rain water), detergents, or sewage.

Inlet Piping

When the gas piping enters through the right side of the
furnace

, the installer must supply the following fittings

(starting from the gas valve):

• 90 degree elbows (2).
• Close nipple.
• Straight pipe to reach the exterior of the furnace.

A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from
1/2" to another pipe size.
When the gas piping enters through the left side of the
furnace, the installer must supply the following fittings
(starting from the gas valve):

Straight pipe to reach the exterior of the furnace.

A ground joint union, drip leg, and manual shutoff valve

must also be supplied by the installer. In some cases,

the installer may also need to supply a transition piece

from 1/2 inch to another pipe size.

Gas Inlet Through Furnace Right Side

Gas Supply and Piping

Gas Inlet Through Furnace Left Side

 Gas Inlet Through Furnace Bottom Side

Gas Inlet Through Furnace Top Side

Summary of Contents for 10759833

Page 1: ...ied in The American National Standard National Standard of Canada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces DESIGN C ERTIFIE D C E R T I F I E D February 2003 Part No 10759833 Printed...

Page 2: ...al circumstances beyond our control such as power outages gas service interruptions product installation or component failures could result in heating system operational problems Table of Contents Saf...

Page 3: ...iary Limit 29 High or Primary Limit 30 Safety Circuit Description 31 Integrated Ignition Control 31 Primary Limit 31 Auxiliary Limit 31 Rollout Limit 31 Pressure Switches 31 Flame Sensor 31 Burner Box...

Page 4: ...ce must be performed by a qualified installer service agency or the gas supplier WARNING Should overheating occur or the gas supply fail to shut off turn off the manual gas shut off valve external to...

Page 5: ...micalorchemicalswhichmaycauseseriousillness ordeathandwhichareknowntotheStateofCaliforniatocausecancer birthdefectsorother reproductive harm WARNING To prevent possible death personal injury or proper...

Page 6: ...er The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim The distributor or manufacturer will not accept claims from dealers for transportati...

Page 7: ...lation Codes local plumbing or waste water codes and other applicable codes A copy of the National Fuel Gas Code NFPA 54 ANSI Z223 1 can be obtained from any of the following American National Standar...

Page 8: ...ated problems Do not install the furnace where the combustion air is ex posed to the following substances chlorinated waxes or cleaners chlorine based swimming pool chemicals water softening chemicals...

Page 9: ...system Turn on any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers d Follow the lighting instr...

Page 10: ...atmosphere and all flue gases are discharged to the outside atmosphere or 2 enclosed furnaces which incor porate an integral total enclosure and use only outside air for combustion and dilution of flu...

Page 11: ...BTU of the total input rating of all equipment in the enclosure Inlet Air Ventilation louvers for unheated crawl space Alternate air inlet Ventilation louvers each end of attic Equipment Located in Co...

Page 12: ...ombustion ventilation and dilution of flue gases 5 3 5 Louvers and Grilles In calculating free area in 5 3 3 consideration shall be given to the blocking effect of louvers grilles or screens protectin...

Page 13: ...CSA B149 1 and CAN CSA B149 2 latest editions and amendments NOTE The vertical height of the Category I venting system must be at least as great as the horizontal length of the venting system WARNING...

Page 14: ...death or personal injury due to electrical shock disconnect electrical power 2 Remove the round cutout from the side of the fur nace NOTE The assembly starting from the outside is induced draft blower...

Page 15: ...held it in place Note There are several screw holes but only four screws This is intentional and not a manufacturing defect 3 As shipped the rollout protection device is located near the flame sensor...

Page 16: ...pplicablecodes Thefurnacemustbeelectricallygrounded in accordance with local codes or in their absence with the latest edition of The National Electric Code ANSI NFPA 70 and or The Canadian Electric C...

Page 17: ...wire should run from the furnace ground screw located inside the furnace junction box all the way back to the electrical panel NOTE Do not use gas piping as an electrical ground To confirm proper uni...

Page 18: ...e as follows Humidifier 1 0 Amp maximum at 120 VAC Electronic Air Cleaner 1 0 Amp maximum at 120 VAC Turn OFF power to the furnace before installing any accessories Follow the humidifier or air cleane...

Page 19: ...ppliances on that line that could be operated simultaneously Gas Supply and Piping Inlet Gas Pressure Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C Inlet Gas Pressure Must Not Exc...

Page 20: ...itude ranges and corresponding manufacturer s pressure switch kits Gas Piping Connections The gas piping supplying the furnace must be properly sized based on the gas flow required specific gravity of...

Page 21: ...ough the right side of the furnace the installer must supply the following fittings starting from the gas valve 90 degree elbows 2 Close nipple Straight pipe to reach the exterior of the furnace A gro...

Page 22: ...essure testing supply piping system with test pressures equal to or less than 1 2 psig 3 48 kPa Gas Supply and Piping Propane Gas and or High Altitude Installations WARNING Possible death personal inj...

Page 23: ...nits to propane gas See Specification Sheet for kit part number for this model All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters See NBFU Manual...

Page 24: ...8 19 39 66 100 187 54 112 209 439 665 250 8 17 36 60 93 172 48 100 185 390 590 Data in accordance with NFPA pamphlet NO 54 Sizing Between First and Second Stage Regulator Maximum Propane Capacities l...

Page 25: ...etween 55 F and 100 F When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace the return air shall also be handled by a d...

Page 26: ...installed NOTE An interlock switch prevents furnace operation if the blower door is not in place Keep the blower access doors in place except for inspection and maintenance FURNACE STARTUP 1 Close the...

Page 27: ...from the table make necessary adjustments to pressure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manomete...

Page 28: ...sec ft3 Input 106 000 BTU hr 5 Repeat steps 1 through 3 on high stage 2nd stage NOTE The final manifold pressure cannot vary by morethan 0 3 w c fromthespecifiedsetting Consult yourlocalgassupplierif...

Page 29: ...nd the adjustment to minus NOTE Continuous Fan Speed will be 56 of high stage cooling 4 Locate the blower speed selection DIP switches on the integrated control module Select the desired cool ing spee...

Page 30: ...djust Taps indicates factory setting Startup Procedure and Adjustment Adjust Blower Heat Off Delay The integrated control module provides a selectable heat off delay function The heat off delay period...

Page 31: ...motor will run on the high heating speed for thirty seconds and then switch to the low heating speed for the balance of the heat off delay period 30 60 90 or 150 seconds Circulator blower and electron...

Page 32: ...fixed 45 second cool off delay period The speed run during this period depends on the last cooling call from the thermostat If the call was for low cool the blower will operate at 88 of low cool speed...

Page 33: ...tion Example 1 Continuous Call For Low Stage Heat Only 0 10 30 33 34 64 94 0 15 30 60 90 90 120 120 or 150 or 180 210 Circulator Blower Gas Valve Igniter Pressure Switches Induced Draft Blower Thermos...

Page 34: ...losed Open High Low Off High Low Off 0 10 30 33 34 64 94 0 15 60 90 90 120 120 or 150 or 180 210 Circulator Blower Gas Valve Igniter Pressure Switches Induced Draft Blower Thermostat High Low Off High...

Page 35: ...hermostat Time sec Call For Cool High Low Off High Low Off 88 of Low Example 2 Continuous Call For High Stage Cooling Only 0 5 35 0 45 High Low Off Circulator Blower Outdoor Fan And Compressor Thermos...

Page 36: ...air circulation blower will run continuously The diagnostic light will flash four times These symptoms are identical to a trip of the primary limit control The auxiliary limit control is designed to...

Page 37: ...e causes unit over heating and will produce the following reactions The gas valve to close and extinguish flame The induced draft blower to deenergized after a fifteen second postpurge and The circula...

Page 38: ...heat exchanger compart ment temperatures They are a normally closed electri cally manual reset temperature activated sensor These limits guard against overheating as a result of insufficient conditio...

Page 39: ...ontrol from its container Follow steps 1 through 3 if in stalling the control on a furnace Return any old or new controls to their containers before touching any un grounded object Furnace Lockout Fur...

Page 40: ...ort Furnace fails to operate Integrated control module diagnostic LED is flashing TWO 2 flashes 2 2 FLASHES Induced draft blower pressure switch contacts sticking Shorts in pressure switch circuit Ins...

Page 41: ...ction Check circulator blower speed and performance Correct speed or replace blower if necessary Check burners for proper alignment Check flue and air inlet piping for blockage proper length elbows an...

Page 42: ...leakage Check the outside termination and the connections at and internal to the furnace Heat exchanger Check for corrosion and or buildup within the heat exchanger passageways Burners Check for prop...

Page 43: ...Turn OFF electrical power to furnace 2 Remove the blower compartment door 3 Grasp the lower portion of the filter and lift up 4 Angle the filter towards the blower until the filter is clear of the bot...

Page 44: ...he igniter should be replaced FLUE PASSAGES Inspect the heat exchanger flue passageways at the be ginning of each heating season If it is necessary to clean them follow the steps outlined below 1 Turn...

Page 45: ...nctional parts are shown in the parts list all sheet metal parts doors etc may be ordered by description FUNCTIONAL PARTS LIST Two Stage Gas Valve Blower Box Gasket Natural Gas Orifice Rollout Limit S...

Reviews: